Switchpack:

Designed to be mounted externally to any junction box.  When mounted, line connections are

inside the box and the Class 2 wiring exits through the rear of the switchpack housing.  In areas
where  Class  2  wiring  is  not  permitted,  the  switchpack  can  be  mounted  internally  to  any 
standard electrical box.

Limited Warranty

Wiring

LED will not turn ON:

• Verify 10-30 VDC across the red and black wires of the sensor. 
• If there is no power at the sensor, check for 12-18 VDC at the switchpack output and 

correct voltage at the switchpack input.  Verify correct primary connections.  

• If the voltage is OK at the switchpack, recheck all wiring and connections.
• If the LED still does not operate, please contact Cooper Controls’ technical service.

Lights will not turn ON:

• Confirm that no other switches or equipment are interrupting or bypassing power to the 

switchpack or load.

• Short the blue and red switchpack control leads together to energize the relay.
• If the lights turn on, contact Cooper Controls’ technical service.
• If the lights do not turn on, check wiring on the switchpack load side and check the 

switchpack contacts for continuity.  Replace the switchpack if necessary.

Lights will not turn OFF:

In smaller rooms, the sensor may be activated by people moving in the hallway outside the room.  Adjust the

Range control 1/8 of a turn decrements in the counter-clockwise direction or relocate the sensor.  If the lights
will not turn OFF after the time period set on the sensor, and the LED has not lit during the time period:

• Confirm that no other switches or equipment are interrupting or bypassing power to the switchpack or load.
•  Verify that the override switch on all sensor circuit boards is in the “auto” position.
•  Check all connections to the switchpack.
•  Temporarily unplug the sensor circuit board(s).
•  If the lights turn off, the sensor is defective, and the circuit board should be replaced.
•  If the lights do not turn off, replace the switchpack.

NOTE:

If multiple sensors/switchpacks are installed, check one at a time.

Manual-On Override Switch:

The OEC-U-XXXX-AF has a built-in override switch on the printed circuit board designed to turn the load

on in the event of sensor failure when the sensor can not be replaced immediately.  The switchpack must
be operative for this switch to work.  If the switchpack is defective, it must be replaced or bypassed to 
activate the load.  

To operate this switch, remove the cover of the sensor and move the override switch from the “auto” posi-

tion to the “on” position.   All switchpacks connected to the sensor will now  be energized.  If multiple sensors
control  the  same  switchpack(s),  activating  the  override
switch on any one sensor will activate all switchpacks.

Sensor Cover Removal: 

1. To  remove  the  cover  from  the  sensor  unit,  grasp 

the end of the cover opposite the adjustment controls
and pull down gently.  Unit will snap open.

2. Locate override switch.
3. To replace the cover, position controls to line 

up with the holes in the center of the cover.  
Unit will snap closed.

Wiring Diagrams

Checkout and Adjustment

Troubleshooting

Installation

Sensor:

Step  1:   

Pass  wires  through  the

threaded  mounting  post  and 
interlock to the backplate.  

Step  2:

The  sensor  mounts  to

normal  ceiling  tile  through  a 
single 3/4” hole.  

Step 3:

When  mounted,  the 

sensor’s  slotted  grills  must  point
along the path where motion is to
be detected.  

Step 4:  

An adapter plate (ACMP)

is available to allow mounting to a standard fixture ring and junction box.  

Step 5:  

The threaded mounting post may be cut down if it is too long to fit into the junction

box. When a flat ceiling is not available or mounting to an angled surface is necessary, please
use the mounting adapter (ACMA-03).

CAUTION:  Finger-tighten the nut to avoid stripping the mounting post.

All products manufactured by Cooper Controls and identified with the Greengate brand are warranted to be free from

defects in material and workmanship and shall conform to and perform in accordance with Seller’s written specifica-

tions for a period of :

Five (5) years from date of shipment for all occupancy sensors and Three (3) years from date of factory invoice for our

hardware and software on Lighting Control Panels.

We warranty all our standard relays for a period of 10 years from date of factory invoice.  We guarantee the perfor-

mance of our system to specifications or your money back.

This warranty will be limited to the repair or replacement, at Seller’s discretion, of any such goods found to be defec-

tive, upon their authorized return to Seller.  This limited warranty does not apply if the goods have been damaged by

accident, abuse, misuse, modification or misapplication, by damage during shipment or by improper service.  There are

no  warranties,  which  extend  beyond  the  hereinabove-limited  warranty,  INCLUDING,  BUT  NOT  LIMITED  TO,  THE

IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS.  No employee, agent,

dealer, or other person is authorized to give any warranties on behalf of the Seller or to assume for the Seller any other

liability in connection with any of its goods except in writing and signed by the Seller.  The Seller makes no representa-

tion that the goods comply with any present or future federal, state or local regulation or ordinance.  Compliance is the

Buyer’s  responsibility.  The  use  of  the  Seller’s  goods  should  be  in  accordance  with  the  provision  of  the  National

Electrical Code, UL and/or other industry or military standards that are pertinent to the particular end use.  Installation

or use not in accordance with these codes and standards could be hazardous

.

Sensor Adjustments:

Once installed, the sensors must be adjusted for suitable sensi-

tivity  and  time  delay.   These  adjustments  can  be  made  only  after
the  entire  system  is  installed  and  power  is  applied  to  the  switch-
pack and to the lighting circuit.  Adjustments should be made with
the HVAC system on.

1.    Using  a  small  screwdriver,  set  the “Minutes”  control  to  minimum  by  turning  the  adjustment   

completely counter-clockwise.  Set the “Range” control to the midpoint. 

2.  If override switches were installed, check their operation.  Leave in the automatic position.
3.  Stand completely still or leave the room.  In approximately 15 seconds, the lights will go out.
4.  Test the area of coverage by watching the red LED on the sensor.  The LED lights only when 

the sensor is detecting motion.  Adjust the Range control to the lowest position that provides 

adequate motion detection.  Do not set higher than necessary.  Test and set Range control for 
each sensor if more than one was installed.

5.   If the red LED blinks when no motion is being made or does not go off at all, air motion from 

the HVAC system may be activating the sensor.  Reduce the Range control until the LED goes 

out  and  stays  out  when  no  one  is  moving.    If  this  setting  is  too  low    to  respond  to  normal 

motion, the sensor may need to be relocated away from the air turbulence.

6.  In smaller rooms, the sensor may be activated by people moving by the doorway outside the 

room.  Adjust the Range control toward minimum to prevent this.

7. Set the time delay Minutes control to the desired time for the lights to remain on after leaving 

the  area.    Minimum  time  is  approximately  15  seconds  (for  installer  testing)  -  maximum  is 

about  30  minutes.   The  recommended  time  delay  is  usually  6-8  minutes.   An  eight-minute 

time delay is approximately 11 o’clock on the Minutes control.  People who remain very still 

for long periods may need a longer time delay.  If the lights go out while the room is occupied, 
increase the time slightly until optimum time delay is reached.  

Cooper Controls
203 Cooper Circle, Peachtree, GA 30269
800-553-3879
www.coopercontrol.com 

P/N 910-0433      
REV C

MOUNTING

POST

SENSOR UNIT

NUT

WASHER

ADAPTER

PLATE

NO. ACMP

SCREW

CAUTION:  OEC-U-XXXX-AF is for use with 10-30 VDC only.  For other voltages, refer to Greengate Tech
Sheets.  Do not wire to control receptacle circuits. Confirm supply voltage before wiring the switchpack.
Make sure the switchpack is the correct model for the voltage being used. VERIFY that the connected
load  does  not  exceed  the  switchpack  ratings.  Use  twist-on  wire  connectors  for  all  connections.    All
installations should be in compliance with the National Electric Code and all state and local codes.
DO NOT control more than ten switchpacks with a single sensor.

Greengate  sensors  are  provided  with  Teflon-insulated  pigtails.    The  components  are  interconnected
using  18  AWG  Class  2  wiring  per  NEC  725.    Use  UL-recognized  Teflon  insulated  wire  approved  for
plenum areas per NEC 725-2(b) where required.  

Wire the sensor(s), switchpack(s) and load as shown in the Wiring Diagram.

Controlling  Multiple  Circuits:    CAUTION:    In  situations  where  an  office  is  wired  for  multiple  circuits
using separate hot leads, it is very important to connect only one circuit to each switchpack.  You
may combine the low voltage wiring from switchpacks connected to different circuits.  Consult with
the building manager and occupant to determine which lights should be off when the toggle switch
is open.

Multiple Switchpacks One Sensor

One Switchpack 

Multiple Sensors

MANUAL-ON

OVERRIDE SWITCH

LED

Отзывы: