KEY1 KEY2 OV SHIELD
CAN
TERM
KEY3
OV
(green
Pair)
CAN-L
(blue)
SHIELD
(brown
pair)
CAN-H
(blue/
white)
+12V
(orange
pair)
Device
Device
Device
Device
Termination on
Termination off
The Chilli Control Panel uses Chilli Network connections
to ensure reliable and responsive transfer of control
signals between multiple devices.
Cable connections are made to a removable 5-way
connector block located at the rear of the Classic Control
Panel main body:
The front cover plate should only be cleaned gently with
a clean, damp cloth. Abrasive cleaners, polishes, solvent
based cleaning agents, or alkali based cleaners should
not be used.
The Chilli Network is a ‘daisy chain’ protocol that requires
termination on the device located at either end of the
chain.
The Chilli Control Panel is supplied with termination enabled
as standard. If the Chilli Control Panel is not connected as
an end device in the chain, you need to disable termination.
To disable termination, move the jumper from the upper two
pins to the lower pins, as shown here:
The following cable strategies may be used for wiring
the Chilli Network.
It is not recommended to mix cable types in a single
installation.
Use Belden cable to maximise network runs up to
1000m without a bridge/repeater.
Use CAT5 FTP for economy and wide availability, but
there are tighter limitations on the network run without a
bridge/repeater.
Cable type:
Belden 1502R or 1502P
Maximum cable length: 1000m (3275 ft.)
Devices per segment:
100 (without bridge or repeater)
Cable type:
CAT 5 FTP
Maximum cable length: 305m (1000 ft.)
Devices per segment: 100
Care and Maintenance
Control Wiring
Termination
Chilli Network