What Is A Short-Circuit Current Rating

(SCCR)?

SCCRs on components and equipment represent the

maximum level of short-circuit current that the 

component or equipment can withstand and is used for

determining compliance with NEC

®

110.10. This rating

can be marked on individual components or 

assemblies. The new SCCRs represent the maximum

amount of fault current that the 

assembly

can withstand

under fault conditions. Assembly ratings take into

account all components contained within the equipment

rather than just the main overcurrent protective device.

A common mistake is to assume that the interrupting

rating of the overcurrent protective device protecting

the circuit represents the SCCR for the entire circuit.

Interrupting ratings, used for compliance with NEC

®

110.9, apply solely to the overcurrent protective device.

It is the characteristics of the overcurrent protective

device (e.g. opening time, let-through energy) that

need to be used in determining compliance with NEC

®

110.10, not the interrupting rating.

Who Is Affected By The SCCR Markings

The 2005 NEC

®

has requirements for anyone building

equipment listed to the 2005 NEC

®

or to UL508A and

requires the following to be marked with an SCCR:

• Industrial Control Panels [409.110]

• Industrial Machinery Electrical Panels [670.3(A)]

• Certain HVAC Equipment [440.4(B)]

• Meter Disconnect Switches [230.82(3)]

• Certain Motor Controllers [430.8]

Effective April, 2006, all equipment listed to UL508A will

be required to be marked with an assembly SCCR.

Inspectors and installers need this information in order

to ensure compliance with NEC

®

110.10. Equipment

installed where fault current levels exceed their short-

circuit current limit can be hazardous to persons and

property. SCCRs marked on components and 

equipment make it easier to verify proper protection for

components and equipment for specific applications —

whether it be the initial installation or relocation of

equipment.

How Is SCCR Determined?

For meter disconnect switches and motor controllers,

this withstand level, or SCCR, is often determined by

product testing. For assemblies, the marking can be

determined through product listing or by an approved

method. With the release of the UL508A Industrial

Control Panel standard, an industry method is now

available. Any method used, whether UL508A or 

another approved method, should be based on the

weakest link

” approach. In other words, the assembly

should be limited to installation where fault levels do

not exceed the 

withstand rating of devices with the 

lowest SCCR

. The marking determined should 

represent the limits of the assembly for a safe 

installation. Current-limiting overcurrent protective

devices can be used in the feeder or branch circuits to

increase the assembly SCCR where lower rated 

components are used. When current-limiting devices

(that limit fault current levels to within the lower rated

components' ratings) are used, they provide protection

for the assembly — provided the current-limiting

Overcurrent Protective Device (OCPD) is used within

its ratings.

Are You Ready For The New SCCR Marking Requirements?

CAUTION: Short-circuit current ratings (SCCRs) are
different than interrupting ratings marked on 
overcurrent protective devices.

Who Is Affected

How Are They Affected

Facility/Process Engineers/

Need to specify end use equipment with ratings adequate for available 

Consulting Engineers

short-circuit current. Need adequate ratings so equipment has flexibility to be 
moved around.

Control Panel Builders/

Need to determine and mark the assembly short-circuit current rating on the 

Machine Builders/

equipment they build. Need to market equipment with ratings as least as high 

HVAC Manufacturers

as their competition.

Electrical Contractors

Need assurance that the equipment they install is adequate for the available 
short-circuit current at the point of installation, to avoid red tags, and lost time 
and labor.

Electrical Inspectors

Need to assure that the available short-circuit current where equipment is 
being installed does not exceed the rating marked on the equipment.

Содержание Electronics Short-Circuit Current Rating

Страница 1: ...Simplified Guide To Understanding Short Circuit Current Rating F I N D I T F I X I T F O R G E T I T ...

Страница 2: ... How Is SCCR Determined For meter disconnect switches and motor controllers this withstand level or SCCR is often determined by product testing For assemblies the marking can be determined through product listing or by an approved method With the release of the UL508A Industrial Control Panel standard an industry method is now available Any method used whether UL508A or another approved method sho...

Страница 3: ...d e d C a s e S w i t c h U L 9 8 F u s i b l e D i s c o n n e c t S w i t c h e s U L 4 8 9 C i r c u i t B r e a k e r s B r a n c h C i r c u i t F u s e s U L 9 8 N o n F u s i b l e D i s c o n n e c t S w i t c h e s P o w e r D i s t r i b u t i o n B l o c k s F u s e H o l d e r U L 9 8 F u s i b l e D i s c o n n e c t S w i t c h e s U L 4 8 9 C i r c u i t B r e a k e r s U L 9 8 F u ...

Страница 4: ...h associated wiring terminal blocks pilot lights and similar components Interrupting Rating The highest current at rated voltage that a device is intended to interrupt under standard test conditions Short Circuit Current Rating The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding the defined accep...

Страница 5: ...mbly short circuit current rating they can also provide enhancements to your design in the areas of flexibility of installation increased workplace safety and reliable protection through the life of your equipment These enhancements take care of the hassle associated with equipment with limited ratings so you can FORGET IT Benefits of Using Cooper Bussmann Current Limiting Fuses Straight Voltage R...

Страница 6: ... or will call Customers pay only standard price for the circuit protection device rush freight charges and a modest emergency fee for this service Emergency and after hours orders should be placed through the Customer Satisfaction Team Call 8 00 a m 4 30 p m Central Time 636 527 3877 After hours 314 995 1342 Application Engineering Application Engineering assistance is available to all customers T...

Отзывы: