DUCT TYPE SPLIT AIR CONDITIONER                                           MAINTENANCE 

 

35

INSTALLATION 

1 INDOOR UNIT INSTALLATION 

1.1 Before Installation 

1.

 

The preparation of all pipes (connecting pipes and drainage pipes) and cables (connecting 
lines of wired controller, indoor unit and outdoor unit) must be ready before the installation, 
so as to achieve smooth installation. 

2.

 

Drill an opening on the ceiling. Maybe it is required to support the ceiling to ensure the 
evenness of it and avoid the vibration of it. Consult with the user or a construction company 
for details. 

3.

 

In case the strength of ceiling is not enough, use angle iron sections to set up a beam support. 
Place the unit at the beam and fix it. 

1.2 Installation Site   

1.

 

Ensure the top hanging piece has strong strength to withstand the weight of the unit. 

2.

 

The drainage pipe has convenient flow of water. 

3.

 

There is no obstacle blocking the air intake and exhaust outlet, so as to ensure sound air 
circulation. 

4.

 

The installation spaces required by the drawing must be ensured, so as to provide enough 
space for the service and maintenance. 

5.

 

The installation site must be far away from heat source, leakage of inflammable gas or 
smoke. 

6.

 

The indoor unit is of ceiling mount (indoor unit is hidden inside the ceiling). 

1.3 Dimension Data 

 

Unit

mm 

Model 

a b c  d e f 

FG20/C-M  FGR20/C-M 

1560 910  332  1194 292 342 

Содержание FG20/C-M

Страница 1: ...Duct Type Split Air Conditioner Service Manual ooper Hunter International Corporation USA...

Страница 2: ...2 5 Fan Mode 20 3 WIRELESS REMOTE CONTROLLER 20 3 1 Operation View 20 3 2 Display View 22 4 WIRED REMOTE CONTROLLER 24 4 1 Operation View 24 4 2 Display View 25 4 3 Dimension 26 4 4 Installation 26 5...

Страница 3: ...h 43 MAINTENANCE 45 1 TROUBLE TABLE 45 2 FLOW CHART OF TROUBLESHOOTING 47 2 1 E1 Compressor High Pressure Protection 47 2 2 E3 Compressor Low Pressure Protection 48 2 3 E4 Compressor Discharge Temp Pr...

Страница 4: ...COMMERCIAL AIR CONDITIONER DUCT TYPE SPLIT AIR CONDITIONER 1 PRODUCT...

Страница 5: ...5 6 4 FG20 C M 19 5 5 5 R2 2 FGR25 C M 24 5 6 9 27 5 7 8 FG25 C M 24 5 6 9 R2 2 FGR30 C M 29 5 8 4 32 5 9 3 FG30 C M 29 5 8 4 R2 2 FGR40 C M 38 10 8 41 11 7 Duct Type FG40 C M 38 10 8 R2 2 Note 1Ton...

Страница 6: ...Production method Self control omitted 380V 3Ph 50Hz M Power type The unit to be exported must be expressed Outdoor unit O Indoor unit I Indoor and outdoor unit code The entire unit is not expressed...

Страница 7: ...n make the temperature and humidity of the whole room equality meanwhile it can lead in fresh air makes well indoor unit air quality All units are provided with filters that are easily accessible from...

Страница 8: ...Height 500 673 500 673 500 673 Width 1500 1840 1500 1840 1500 1840 Dimensions Outline Package Depth mm 1000 1200 1000 1200 1000 1200 Weight Net Gross kg 150 200 150 200 150 200 System Operation Contro...

Страница 9: ...5 24 5 29 5 Btu h Nominal Capacity At Rated ESP Heating kW Power Supply V Ph Hz 380 3 50 Cooling 8 5 10 2 12 1 Power Consumption Heating kW Cooling 15 8 18 9 21 8 Running Current Heating A Refrigerant...

Страница 10: ...V Ph Hz 380 3 50 Compressor Type Scroll Nominal Current 12 21 15 27 15 5 L R A A 98 142 111 Vibration Isolator Rubber Compressor Protection Device Auto Reset Thermal Overload Fan Type Drive Inner Gro...

Страница 11: ...ntrifugal Belt Drive CFM 4120 Air flow m3 h 7000 Input Power kW 2 2 Running Current A 4 2 in wg 0 60 Rated ESP Pa 150 Fan Motor Protection Overload protection Fan Sound Pressure Level H M L SL dB A 58...

Страница 12: ...ction Device Auto Reset Thermal Overload Fan Type Drive Inner Groove Copper Tube Fan Speed rpm 730 Blade Material Plastic Fan Diameter mm 750 Tube Material Inner Groove Copper Tube Material Aluminum C...

Страница 13: ...elt Drive CFM 4120 Air flow m3 h 7000 Input Power kW 2 2 Running Current A 4 2 in wg 0 60 Rated ESP Pa 150 Fan Motor Protection Overload protection Fan Sound Pressure Level H M L SL dB A 58 Material I...

Страница 14: ...0 Tube Material Inner Groove Copper Tube Material Aluminum Coil Fin No of Rows FPI 2 14 Coil Area Sqm 2 71 Sound Pressure Level dB A 69 Height 1772 1950 Width 1290 1370 Dimension Outline Package Depth...

Страница 15: ...AM 5 1 Cooling Only Name compressor 4 way valve Stop Valve Check Valve Capillary Filter Electronic Expansion Valve Sign Name Temperature Sensor Pressure Switch Heat Exchanger with Axial Flow Fan Heat...

Страница 16: ...DUCT TYPE SPLIT AIR CONDITIONER PRODUCT 13 5 2 Heat Pump...

Страница 17: ...DUCT TYPE SPLIT AIR CONDITIONER PRODUCT 14 Note FG R 40 C M has oil separator The electric expansion valve is connected with the throttle capillary...

Страница 18: ...COMMERCIAL AIR CONDITIONER DUCT TYPE SPLIT AIR CONDITIONER 15 CONTROL...

Страница 19: ...COMMERCIAL AIR CONDITIONER DUCT TYPE SPLIT AIR CONDITIONER 16 CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation...

Страница 20: ...COMMERCIAL AIR CONDITIONER DUCT TYPE SPLIT AIR CONDITIONER 17 1 2 Heating Operation 2 MAIN LOGIC...

Страница 21: ...The outdoor fan will run for 15s before the compressor runs When T ambient T setting 1 the unit stops cooling In that case the compressor the outdoor fan will stop running while the indoor fan will ru...

Страница 22: ...ting 2 T ambient T setting 2 the compressor A and the outdoor fan A will repeat running for 6min and stopping for 4min while the compressor will remain the previous running state When T ambient T sett...

Страница 23: ...osting Condition When the heating time accumulates to 44min and T condenser 5 lasts for 1min the unit will start defrosting In that case the selector valve the outdoor fan and auxiliary e heater will...

Страница 24: ...rt or close unit 2 Mode button Press the button to select the mode cooling heating fan or auto mode 3 Increase Decrease button Press this button to increase decrease the setup temp 4 LCD Screen Displa...

Страница 25: ...button to set swing function 2 Increase Decrease button Press this button to increase decrease the setup temp 3 Mode button Press the button to select the mode cooling heating fan or auto mode 4 ON OF...

Страница 26: ...n description 1 Fan Speed auto fan speed low fan speed middle fan speed high fan speed 2 Run Mode Auto running Cool running Dry Running Fan Running Heat running Heat and Cool unit only 3 Setup temp Te...

Страница 27: ...button to set sleep swing function 6 Timer button Press the button to set timer function 7 On off button Press the button to set start or close unit 8 Remote window Get remote information 9 LCD displ...

Страница 28: ...an is off nothing displays 4 Set temp display Display set temp value its range is 16 30 5 Run mode display auto mode cool mode dry mode fan mode heat mode only cool and heat unit 6 Indoor temp display...

Страница 29: ...7 No matter if surface mounting or concealed mounting is selected it is required to drill 2 holes in the same level which distance shall be the same as the distance 60mm of installation holes in the...

Страница 30: ...agram of Installation No Name 1 Wall Surface 2 Bottom Plate of Wire Controller 3 Screw M4X10 4 Panel of Wire Controller Caution The communication distance between the main board and the wire controlle...

Страница 31: ...it Up to 16 sets of units can be controlled simultaneously by the centralized controller not with week timer 5 1 2 Operation View NO Name Function description 1 ON button Press the button to set start...

Страница 32: ...ek timing functions Up to 16 sets of units can be controlled simultaneously by the centralized controller weekly timer The weekly timer has the function of invalidating the lower unit The weekly timin...

Страница 33: ...can set week part of time 4 CANCEL DELETE button short press cancel delete to back to default page or last process long press cancel delete to cancel timer of a certain time period in a certain day 5...

Страница 34: ...displays on when set unit on on will display off when set unit off off will display 7 timer on time displays Display starts time 8 on control displays When set unit or group on it will display 9 off c...

Страница 35: ...1 switch from right to left ON represents 0 while OFF represents 1 Example 1 The dial up value is 0111 Switch 1 2 3 should be on the opposite side of ON while switch 4 at ON position Example 2 The di...

Страница 36: ...1 unit code 15 1110 unit code 16 1111 5 4 Control Wiring Design 16UnitsinMax Weektimer Wiredremotecontroller LCD LCD LC Wiredremotecontrolle Telephonewirebox Telephonewirebox Telephonewirebox Twisted...

Страница 37: ...COMMERCIAL AIR CONDITIONER DUCT TYPE SPLIT AIR CONDITIONER 34 INSTALLATION...

Страница 38: ...ing is not enough use angle iron sections to set up a beam support Place the unit at the beam and fix it 1 2 Installation Site 1 Ensure the top hanging piece has strong strength to withstand the weigh...

Страница 39: ...1194 292 342 FG30 C M FGR30 C M 1560 910 1194 1194 292 342 b d a f e c mm Model a b c d e f FG40 C M FGR40 C M 1780 1040 868 1450 347 555 1 4 Installation Clearance Data Air supply Air return Suspend...

Страница 40: ...irm conveying route and method of the unit to avoid damage to the unit and possible injuries For protection and safety of the unit it is recommended to convey the unit together with the packing contai...

Страница 41: ...00 1772 A 880 840 C 2 B 2 844 2 Fig 27 Schematic of the Outdoor unit Don t connect any air leading duct to the outdoor unit at neither the air inlet nor the air outlet The outdoor unit will drop conde...

Страница 42: ...and dimension of the unit Unit mm Model A B C FG R 30 C M O 990 787 337 FG R 40 C M O 1290 1160 850 2 4 Installation Clearance Data 1200 1000 1000 1000 3000 300 300 300 3 REFRIGERATION PIPING WORK 3...

Страница 43: ...nt should be tightly connected when a pipe joint is employed between two pipes It is better to use only one connecting pipe if the distance is not far The pipes should not be shriveled when the pipes...

Страница 44: ...em The air switch should have hot and magnetic auto turn off function to protect the system from overloading or short power Please accord to electrical diagram on the unit when connecting the wires 1...

Страница 45: ...outdoor unit and indoor unit The power cord must be copper inside while the working temp can not be over its standard one If the total length of the power cord is over 15m please increase the size by...

Страница 46: ...FGR25 C M I 380V 3Ph 50Hz 16 2 5 2 5 FGR30 C M I 380V 3Ph 50Hz 20 2 5 2 5 FGR40 C M I 380V 3Ph 50Hz 25 4 0 4 0 FG20 C M I 380V 3Ph 50Hz 10 1 0 1 0 FG25 C M I 380V 3Ph 50Hz 10 1 0 1 0 FG30 C M I 380V...

Страница 47: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 44 MAINTENANCE...

Страница 48: ...protection Compressor discharge temp sensor After the running of compressor if detect that discharge temp is higher that 130 in continuously 30s it is believed that there is high temp protection of di...

Страница 49: ...ayed and the buzzer will beep F0 Indoor ambient temp sensor error Indoor ambient temp sensor If detect that AD value exceeds 250 short circuit with corresponding temp 160 or less than 5 open circuit w...

Страница 50: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 47 2 FLOW CHART OF TROUBLESHOOTING 2 1 E1 Compressor High Pressure Protection...

Страница 51: ...indoor unit have been set correctly Check if the refrigeration capacity of the system is too low Check if the filter and heat exchange fins of the outdoor unit are dirty or clogged Check if the capaci...

Страница 52: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 49 2 3 E4 Compressor Discharge Temp Protection 2 4 E5 Overcurrent Protection Compressor Overloading Protection...

Страница 53: ...nit connected correctly Is communication cable fluent Is communication cable of indoor and outdoor unit connected rightly Is there magnetic ring on both sides of the communication cable Confirm the di...

Страница 54: ...main board of the indoor unit No No replace temperature sensor check the directions of the plug and socket Yes Overload of indoor fan Is wire of indoor fan connected rightly Connect the wire rightly I...

Страница 55: ...nsor Error F4 Discharge Temperature Sensor Error yes no yes no yes Temperature sensor error Is the plug of temperature sensor connected correctly with the socket of the mainboard Is the resistance val...

Страница 56: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 53 3 WIRING DIADRAM FGR20 C M I FGR25 C M I FGR30 C M I with e heater FGR30 C M I...

Страница 57: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 54 FGR40 C M I FG20 C M I FG25 C M I FG30 C M I FG40 C M I...

Страница 58: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 55 FGR20 C M O FGR25 C M O...

Страница 59: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 56 FG20 C M O F G25 C M O...

Страница 60: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 57 FGR30 C M O...

Страница 61: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 58 FG30 C M O FGR40 C M O...

Страница 62: ...DUCT TYPE SPLIT AIR CONDITIONER MAINTENANCE 59 FG40 C M O...

Страница 63: ...lour of wire corresponding to the terminal when Removing the wire and the mixture can be avoided when recovering the wire connection 2 Cut off the connection between compressor and pipes Don t leave t...

Страница 64: ...ce to circuit diagram and check if there is any leakage after welding Disassembly and Assembly of 4 way valve Remark Make sure that there isn t any refrigerant in pipe system and the power supply is c...

Страница 65: ...cting pipe Don t leave welding slag inside pipes Disconnect the pipe site S in illustration of 4 way valve and connecting pipe Don t leave welding slag inside pipes Remove the 4 way valve Remove 4 way...

Страница 66: ...letree 1 10549057 4 Fan Motor for indoor unit 1 15018303 5 Motor Fixed Board 1 01845309 6 Belt Pulley 1 10548148 7 Taper Sleeve 1 10548208 8 Condenser assy and evaporator assy 1 01025359 9 Right Side...

Страница 67: ...1394921 23 back girder 1 01875330 24 place with a draught of Connection board 2 01375225 25 Fan Motor Sub assy 1 15705225 26 Left Side Plate Sub Assy 1 01315383 27 front girder 1 01779106 28 Electric...

Страница 68: ...minal board 42011043 1 8 AC Contactor 44010213 1 9 Over Current Protector 46020122 1 10 Electric Box Assy 01395694 1 11 Collecting Gas Pipe Sub Assy 04675422 1 12 Inhalation Tube Sub Assy 04675424 1 1...

Страница 69: ...7 valve support sub assy 01805386 1 28 compressor 00205245 1 29 retaining plate sub assy 01845233P 1 30 Inhalation Tube Sub Assy 04675423 1 31 clapboard sub assy 01245243 1 32 motor support sub assy 0...

Страница 70: ...or unit 1 15018303 5 Motor Fixed Board 1 01845309 6 Belt Pulley 1 10548148 7 Taper Sleeve 1 10548208 8 Condenser assy and evaporator assy 1 01025359 9 Right Side Plate Sub Assy 1 1 01315319 10 overhau...

Страница 71: ...01394921 23 back girder 1 01875330 24 Place with a draught of Connection board 2 01375225 25 Fan Motor Sub assy 1 15705225 26 Left Side Plate Sub Assy 1 01315383 27 front girder 1 01779106 28 Electri...

Страница 72: ...213 1 9 Over Current Protector 46020122 1 10 Electric Box Assy 01395834 1 11 Collecting Gas Pipe Sub Assy 04675422 1 12 Inhalation Tube Sub Assy 04675424 1 13 LOW Pressure switch 4602001510 1 14 Front...

Страница 73: ...or 00205245 1 28 retaining plate sub assy 01844120 1 29 Inhalation Tube Sub Assy 04675423 1 30 clapboard sub assy 01245243 1 31 motor support sub assy 01804174 1 32 Axial flow fan 10338701 2 33 fan mo...

Страница 74: ...Board 1 01845223 6 Belt Pulley 1 10548150 7 Taper Sleeve 1 10548213 8 Condenser assy and evaporator assy 1 001025347 9 Right Side Plate Sub Assy 1 1 01315319 10 overhauling side 1 01545322 11 Belt SP...

Страница 75: ...a draught of Connection board 2 01375225 25 Fan Motor Sub assy 1 15705225 26 Left Side Plate Sub Assy 1 01315383 27 front girder 1 01779106 28 Electric Fixed Plate 1 01339099 29 Main Board 1 30224206...

Страница 76: ...plate sub assy 01315358P 1 18 4 way valve sub assy 04145327 1 19 4 way valve 430004061 1 20 4 way valve fittings 4300040043 1 21 electric expansion valve sub assy 07335255 1 22 collecting liquid pipe...

Страница 77: ...SteelBar 1 01805367 3 rotate axletree 1 10549057 4 Fan Motor for indoor unit 1 15014805 5 Motor Fixed Board 1 01845223 6 Belt Pulley 1 10548150 7 Taper Sleeve 1 10548213 8 Condenser assy and evaporato...

Страница 78: ...2 Electric Box 1 01394921 23 back girder 1 01875330 24 place with a draught of Connection board 2 01375225 25 Fan Motor Sub assy 1 15705225 26 Left Side Plate Sub Assy 1 01315383 27 front girder 1 017...

Страница 79: ...oard 30224208 1 9 electric box assy 01395684 1 10 phase reverse protector 46020052 1 11 collecting gas pipe sub assy 04675415 1 12 inhalation tube sub assy 04675388 1 13 low pressure switch 460200157...

Страница 80: ...00205247 1 28 retaining plate sub assy 01845224P 1 29 inhalation tube sub assy 04675387 1 30 clapboard sub assy 01245238 1 31 motor support sub assy 01805368 1 32 axial flow fan 10338701 2 33 fan mot...

Страница 81: ...76318317 13 Hook 4 02205302 14 Side beam sub assy 1 01875302 15 Belt Pulley 2 SPA140 1 10548156 16 Taper Sleeve 2012 25 1 10548218 17 Right Side Plate 2 1 01309105 18 FrontPanel_OutsideMachine 1 0128...

Страница 82: ...Twin Pair Signal Cable 1 40010232 38 measure staff 1 02169050 39 Filter Sub Assy 1 11129070 FGR30 C M O No Name Qty Product Code 1 Base Plate Sub Assy 1 01195230P 2 4 way Valve with coil 1 04145295 3...

Страница 83: ...port 1 1 01804632 21 Support 3 1 01804634 22 Support plate 1 Electric Box 1 01894602 23 Support plate sub assy 1 1 01894607 24 Support plate 3 1 017987834 25 Supporting Strip 1 01894605 26 Supporting...

Страница 84: ...38 4 Cut off Valve 1 07130127 5 Liquid valve sub assy 1 07109068 6 Discharge Tube 1 04615486 7 Compressor and Fittings 1 00100298 8 Gas liquid Separator 1 072290571 9 Inhalation Tube Sub Assy 1 046753...

Страница 85: ...987834 25 Supporting Strip 1 01894605 26 Supporting Strip 1 01798808 27 Front plate 1 1 01538736 28 Front plate 2 1 01538734 29 Electric Box Cover 1 01419059 30 Electric Box 1 01395728 31 Base Frame S...

Страница 86: ...b Assy 1 01265209 2 Retaining Plate Sub Assy 1 01845205 3 Return Air Frame Sub Assy 1 01375208P 4 Return Air Frame Sub Assy 1 01875208P 5 Evaporator Assy 1 01025335 6 Retaining Plate Sub Assy 1 018452...

Страница 87: ...r Sleeve 1 10548218 23 Sheet Metal Piece 1 01805212P 24 Base Plate Sub Assy 1 01285222P 25 Electric Box Cover 1 01425304P 26 Electric Box Sub Assy 1 01395346 27 Air Outlet Frame 1 01375210P 28 Air Out...

Страница 88: ...1 4 Motor Assy 1 15404601 5 Motor SW650A 1 15704601 6 Rear Panel 1 01544104P 7 Rear Lining Board Sub Assy 1 01264113P 8 Rear isolation sheet 1 22414101 9 Rear Strengthen Girder 1 01854102P 10 right Co...

Страница 89: ...ate panel 1 01894104P 30 Front Lining Board Sub Assy 1 01264111P 31 Liquid by pass sub assy 1 04615396 32 Electric Expansion Valve Sub Assy 1 07335239 33 Discharge Tube Sub Assy 1 04635362 34 Oil Sepa...

Страница 90: ...3P 8 Rear isolation sheet 1 22414101 9 Rear Strengthen Girder 1 01854102P 10 right Cover Plate 1 01264116P 11 Right Side Plate 1 01315344P 12 Condenser Assy 1 01125724 13 4 way Valve Sub Assy 0 041452...