Where the relative humidity of air inlet or 
ambient air exceeds 80%, an auxiliary water pan 
shall be fabricated at installation site and placed 
under the indoor unit, as shown in Fig. 6.2.

Indoor Unit

Water Outlet

Condensate Pan

Field-Supplied

Fig. 6.2 Auxiliary Water Pan

a.Turn on the power.

b.Fill the water pan with 2L or 2.5L of water.

c. Check and ensure the water flows without

obstruction and no leakage exists. Pour 2L of

water if no water flows out of pipe end.

&$87,21

(1) The drain pipe installed shall slope down; otherwise,

the condensate may flow back and leak into the room
when the indoor unit is turned off.

(2) The drain pipe shall not be connected with sewage

pipe or other drain pipes.

(3) Where the main drain is connected to other indoor

units, each indoor unit must be higher than the main.
Select drain pipes in ample size depending on the
refrigerating capacity and quantity of indoor units.

(4) Check if water flows without obstruction following

the procedure shown below after the proper
connection of wires and drain pipes.

'UDLQ3LSH

(1) The position of the drain pipe

connection is shown 

.

(2) Prepare a polyvinyl chloride pipe with a

32mm outer diameter.

(3) Fasten the tubing to the drain hose with the

adhesive agent and the factory-supplied

clamp. The drain pipe must be performed

with a down-slope pitch of 1/25 to 1/100.

perform the drain piping work as shown in the figure above.

(4) Insulate the drain pipe after connecting the drain hose.

The total length a+b+c shall be ≤3.6ft

.

(1.1m).

In case of lifting the drain pipe at the outlet part,

Hose Clamp (Accessory)

Packing(Accessory)

● Inject water via air outlet.

Insert the end of hose between 
heat exchanger and water pan.

Water Pan

Water Pump

Water (2L or 2.5L)

separating from other pipes.

Fig. 6.1 Drain Pipe

a (11-13/16(300) max.)

Hose Clamp

(Accessory)

c (1-31/32(50) max.)

3332(

850

)

Max.

1/25 to 1/100

Down-Slope

Drain Hose (Accessory)

Drain Pipe 
Connection

Hose Clamp
(Accessory)

Drain Hose 

(Accessory)

Vinyl Chloride VP25
(Field Supplied)

Unit

Upward Slope

Rising Part

Drain Pipe 
Connection

3-15/16(

100

) Min.

1/25 to 1/100Down-Slope

Common Drain Pipe

This drain pipe shall be 

6

7-41/64(

19

4)

Connected to Drain Pipe

● Inject water via access opening.

Insert the end of hose between 
heat exchanger and water pan.

Access Opening

Water Pump

Water (2L or 2.5L)

&$87,21

t

in.(mm)

t

in.(mm)

3-15/64(82)

2-11/64(55)

Содержание CHV-09MCC4W

Страница 1: ...NDITIONER PLEASE READ AND UNDERSTAND THIS MANUAL BEFORE USING THE AIR CONDITIONER KEEP THIS MANUAL FOR FUTURE REFERENCE 4 WAY CASSETTE TYPE ORIGINAL INSTRUCTIONS CHV 09SCC4W CHV 12SCC4W CHV 15SCC4W CH...

Страница 2: ......

Страница 3: ...at pump air conditioner within this range Do not have the air outlet directly faced towards animals or plants since this may bring about an adverse effect thereon The installation and service engineer...

Страница 4: ...imals damaging the wiring and electrical components Bitten unprotected parts may cause a fire Firmly fix the connection wires The external force of terminal may result in looseness of terminal that ma...

Страница 5: ...responsible for any consequence arising from the modification to equipment without our written consent 03257 17 127 Correct Disposal of this product This marking indicates that this product should not...

Страница 6: ......

Страница 7: ...Materials 5 2 Piping Connection 8 Test Run 9 Protection Control Devices 10 Field Operation Electrical Wiring 7 1 General Check 7 2 Wiring 7 3 Field Wire Size for Power Source Line 2 4 5 6 Drain Pipe...

Страница 8: ......

Страница 9: ...e etc may occur 87 21 Be careful not to cause damage to insulation materials of the unit surface when it s lifted 7RROV QVWUXPHQWV IRU QVWDOODWLRQ QVWDOODWLRQ RI QGRRU 8QLW Transport the product as cl...

Страница 10: ...unit where the electromagnetic wave is directly radiated to the electrical box remote control cable or remote control B Install the indoor unit and components as far as practical or at least 9 8ft 3m...

Страница 11: ...asher Suspension Bolt Suspension Bracket Water Pan Fig 4 6 Mounting Nuts and Washers Suspension Bolt Field Supplied Nut Field Supplied Insulating Washer Accessory Bracket for Fixing Indoor Unit Washer...

Страница 12: ...ctors between the indoor unit and air panel Flange Surface Indoor Unit Bottom View Ceiling Indoor Unit Surface of Suspended Ceiling Suspension Bolt Surface of Ceiling Indoor Unit Bolt M6 Pattern Board...

Страница 13: ...nance Manual for outdoor unit Excessive and inadequate refrigerant is a leading cause of system anomaly Please inject the right amount of refrigerant Pipe Size mm Tightening Torque ft N m 10 3 13 3 14...

Страница 14: ...e drain pipe connection is shown 2 Prepare a polyvinyl chloride pipe with a 32mm outer diameter 3 Fasten the tubing to the drain hose with the adhesive agent and the factory supplied clamp The drain p...

Страница 15: ...p the wires with adhesive tape or other materials and plug the wiring connection hole with seal material to protect the product from any condensate water or insects The electrical box entrance hole sh...

Страница 16: ...Amps A MOP Max Overcurrent Protective Device A kW Fan Motor Rated Output kW FLA Full Load Amps A Connecting Hole for Power Supply Wiring Connecting Hole for Communication Cables and Wire Controller Ca...

Страница 17: ...ot operate the system until the electrical leakage is found and repaired B Check to ensure the stop valves of outdoor unit are fully opened and then start the system C Check to ensure the switch on ma...

Страница 18: ...ls 1 and 2 of TB2 the PCB fuse will be blown In such a case it s essential to correct the wiring and then to set switch No 1 to ON position Note Symbol indicates the location of DIP switch The positio...

Страница 19: ......

Страница 20: ...3DFNLQJ LVW Details Remarks 1 Set 1 pc pc pcs pc 1 pc 6 pcs 2 pcs 1 pc 1 pc 1 pc Indoor Unit Operation Installation Maintenance Manual Pipe Clamp 1 pc 08 20 V01...

Отзывы: