4
7
Installation and Maintenance
Service Manual
Steps
Procedure
12. Remove connection pipe sub-assy
Remove all spot welds connected with
connection pipe, and then remove the
connection pipe sub-assy.
Remove the 3 foot nuts fixing compressor and
then lift the compressor upwards to remove
the compressor and damping cushion.
Note:
Keep the ports of discharge pipe and suction
pipe from foreign objects.
Unsolder spot welds connected with vapour
liquid separator, remove screws connected
vapour liquid separator and middle isolation
sheet, and then remove the vapour liquid
separator.
13. Remove compressor
14. Remove vapour liquid separator
Connection pipe
sub-assy
Compressor
vapour liquid
separator