Specifications

Specifications

2. Specifications

2.1 Unit Specifications

Parameter

Unit

Value

Value

Model 

--

CH-S09FTXC

CH-S12FTXC

Product Code

--

SCB001N0610_A0023

SCB001N0620_A0023

Power Supply

Rated Voltage

V~

220-240

220-240

Rated Frequency

Hz

50

50

Phases

--

1

1

Power Supply Mode

--

outdoor

outdoor

Cross-sectional Area of Power Cable Conductor

mm2

1.0 

1.0 

Recommended Power Cable(Core)

N

3

3

Min/Max. Voltage

V

198/264

198/264

Cooling Capacity

Btu/h

8530

 

1160

1

 

Min. Cooling Capacity

Btu/h

1638

 

2047

 

Max. Cooling Capacity

Btu/h

9895

 

1330

7

 

Heating Capacity

Btu/h

9554

12283

Min. Heating Capacity

Btu/h

2491

 

2730 

Max. Heating Capacity

Btu/h

11260

14330

Cooling Power Input

W

775

1055

Min. Cooling Power Input

W

125

165

Max. Cooling Power Input

W

1430

1560

Heating Power Input

W

7

75

995

Min. Heating Power Input

W

1

65

1

90

Max. Heating Power Input

W

1550

1650

Cooling Current

A

3.

4

4.7

Heating Current

A

3.4

4.4

Rated Input

W

1550

1650

Rated Current

A

6.

9

 

7.3 

EER 

W/W

3.

23

3.22

COP 

W/W

3.

61

3.62

Air Flow Volume

m3/h

520/440/230/150

580/500/300/230

Dehumidifying Volume

L/h

0.80

1.40

Dehumidifying Volume

PINT/D

1.69

2.96

Application Area

m2

12-18

16-24

Indoor  Unit 

Indoor Unit Model

--

CH-S09FTXC

CH-S12FTXC

Fan Type

--

Cross-flo

Cross-flo

Fan Diameter Length(D×L) 

mm

Ф97.5×579

Ф97.5×579

Cooling Speed

r/min

1300/1150/750/600

1350/1200/800/650

Heating Speed

r/min

1300/1150/850/800

1350/1200/900/850

Fan Motor Power Output

W

18

20

Fan Motor RLA

A

0.2

0.2

4

Fan Motor Capacitor 

μF

1

1

.5

Evaporator Form 

--

Alumium Tube

Alumium Tube

Evaporator Pipe Diameter

mm

φ5

φ5

Evaporator Row-fin Ga

mm

2-1.4

2-1.4

Evaporator Coil Length (L×D×W)  

mm

584.4×22.8×266.7

584.4×22.8×266.7

Swing Motor Model

--

24BJ-A

2

24BJ-A

2

Swing Motor Power Output

W

1.5

1.5

Fuse Current

A

3.15

3.15

Set Temperature Range 

16~31

16~31

Set Temperature Range 

61~88

61~88

Sound Pressure Level

dB (A) 

38/34/21/19

40/35/22/20

Sound Power Level

dB (A) 

51/47/34/32

53/48/35/33

Dimension (W×H×D) 

mm

792x279x195

792x279x195

Dimension of Carton Box (W×H×D) 

mm

868x280x349

868x280x349

Dimension of Package (W×H×D) 

mm

871x290x352

871x290x352

Stacked Layers

-

7

7

Net Weight  

kg

9

9

Gross Weight

kg

 11

 11

Parameter

Unit

Value

Value

Outdoor Unit 

Outdoor Unit Model

--

CH-S09FTXC

CH-S12FTXC

Compressor Trademark 

panasonic

panasonic

Compressor Model

--

9RS092ZAB21

 

 9RS102ZAA21

Compressor Oil

--

FV50S

FV50S

Compressor Type

--

Rotary

Rotary

Compressor LRA.  

A

20.2

16.5

Compressor RLA  

A

6.22

6.48

Compressor Power Input

W

855

970

Fan Type

--

Axial-flo

w

Axial-flo

w

Fan Diameter

mm

405

405

Fan Diameter

inch 

15.9

15.9

Fan Motor Speed

rpm

880

880

Fan Motor Power Output

W

30

30

Fan Motor RLA  

A

0.4

0.4

Outdoor Unit Air Flow Volume

m3/h

1800

1800

Condenser  Form 

--

Alumium Tube

Alumium Tube

Condenser  Pipe Diameter 

mm

φ7

φ7

Condenser  Rows-fin Ga

mm

1-1.4

2-1.4

Condenser  Coil Length (L×D×W)  

mm

742×19.05×506

719×38.1×506

Permissible Excessive Operating Pressure for the 

Discharge Side

MPa

4.3

4.3

Permissible Excessive Operating Pressure for the 

Suction Side

MPa

2.5

2.5

Maximum Allowable Pressure

MPa

4.3

4.3

Cooling Operation  Ambient Temperature Range 

18~

52

18~

52

Cooling Operation  Ambient Temperature Range 

64~

126

64~

126

Heating Operation  Ambient Temperature Range 

 -15~24

 -15~24

Heating Operation  Ambient Temperature Range 

5~75

5~75

Throttling Method

--

Capillary

Capillary

Defrosting Method

--

Automatic Defrosting

Automatic Defrosting

Climate Type

--

T1

T1

Climate Zone

--

Temperate Zone

Temperate Zone

Isolation

--

I

I

Moisture Protection

--

IP24

IP24

Sound Pressure Level

dB (A) 

52

53

Sound Power Level

dB (A) 

61

62

Dimension (W×H×D) 

mm

830X540X325

830X540X325

Dimension of Carton Box (W×H×D) 

mm

876x585x363

876x585x363

Dimension of Package (W×H×D) 

mm

879x605x366

879x605x366

Stacked Layers

--

5

5

Net Weight  

kg

29

30

Gross Weight

kg

3

1.5

3

2.5

Refrigerant 

--

R

32

R

32

Refrigerant Charge

kg

0.

52

0.

78

 

Connection Pipe

Length

m

5

5

Length

ft

16.4

16.4

Gas Additional Charge

g/m

20

20

Gas Additional Charge

oz/ft.

0.2

0.2

Outer Diameter of  Liquid Pipe(GREE Allocation)

(Metric)

mm

φ6

φ6

Outer Diameter of  Liquid Pipe(British System 

Allocation)

inch 

1/4"

1/4"

Outer Diameter of  Gas Pipe(GREE Allocation)

(Metric)

mm

φ9.52

φ9.52

Outer Diameter of  Gas Pipe(British System 

Allocation)

inch 

3/8"

3/8"

Max Distance Height

m

10

10

Max Distance Height

ft

32.8

32.8

Max Distance Length

m

20

20

Max Distance Length

ft

65.6

65.6

Содержание CH-S09FTXC

Страница 1: ...MODELS CH S09FTXC CH S12FTXC CH S18FTXC CH S24FTXC Refrigerant R32...

Страница 2: ...rol Operation 16 7 Installation Manual 18 7 1 Notices for Installation 18 7 2 Installation Dimension Diagram 20 7 3 Installation Indoor Unit 21 7 4 Installation Outdoor Unit 24 7 5 Check after install...

Страница 3: ...site after installation Make sure no foreign objects are left in the unit Always ensure effective grounding for the unit Incorrect handling could result inpersonal injury or death Incorrect handling...

Страница 4: ...mm 871x290x352 871x290x352 Stacked Layers 7 7 Net Weight kg 9 9 Gross Weight kg 11 11 Parameter Unit Value Value Outdoor Unit Outdoor Unit Model CH S09FTXC CH S12FTXC Compressor Trademark panasonic pa...

Страница 5: ...4x304x374 1155x342x410 Dimension of Package W H D mm 1047x314x377 1158x352x413 Stacked Layers 7 7 Net Weight kg 13 16 Gross Weight kg 15 5 19 Parameter Unit Value Value Outdoor Unit Outdoor Unit Model...

Страница 6: ...80 70 60 50 40 Outdoor temp C 50 60 70 80 90 100 110 120 130 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 Capacity ratio Outdoor temp C Capacity ratio 15 10 5 110 100 90 80 70 60 50 40 0 5 7 10 Condit...

Страница 7: ...Model W mm H mm D mm CH S09FTXC 792 279 195 CH S12FTXC 792 279 195 CH S18FTXC 972 302 224 CH S24FTXC 1081 327 248 CH S09FTXC CH S12FTXC CH S18FTXC 3 2 Outdoor Unit Unit mm Model CH S09FTXC CH S12FTXC...

Страница 8: ...mm 9 12K 1 2 12mm 18K 5 8 16mm 24K 5 Schematic Diagram 5 1 Electrical Wiring Symbol OG WH YE RD YEGN BN BU BK VT Color symbol ORANGE WHITE YELLOW RED YELLOW GREEN BROWN BLUE BLACK VIOLET Symbol COMP C...

Страница 9: ...3 12 Function and Control Function and Control 6 Function and Control 6 1 Remote Control Operations Health button Wi button I feel button I feel Wi fi There is no this function for some remote control...

Страница 10: ...rom the aircon when press this button Default WIFI open on remote control WIFI button for air conditioner WIFI link Note Health button Note Note Note Note Turn on the back cover of the remote control...

Страница 11: ...sensor AD is above or equal 250 5s continually or the environment sensor or pipe sensor AD is below 5 when the unit is on it means sensor malfunction 4 Motor blockage When mainboard can not find the i...

Страница 12: ...4 Select a location which is out of reach for children 5 The location should be ableto withstand the weight of indoor unit and won t increase noise and vibration 6 The appliance must be installed 2 5m...

Страница 13: ...f the plastic expansion particle is loose please drill another fixing hole nearb Step 3 Open piping hole 1 Choose the position of piping hole according to the direction of outlet pipe The position of...

Страница 14: ...e clip 4 Put wiring cover back and then tighten the screw 5 Close the panel Note All wires of indoor unit and outdoor unit should be connected by a professional If the length of power connection wire...

Страница 15: ...ew on the right handle of outdoor unit and then remove the handle 2 Remove the screw cap of valve and aim the pipe joint at the bell mouth of pipe 3 Pretightening the union nut with hand 4 Tighten the...

Страница 16: ...wing requirement after finishing installation Items to be checked Possible malfunction Has the unit been installed firmly The unit may drop shake or emit noise Have you done the refrigerant leakage te...

Страница 17: ...to the diameter of liquid pipe See the following sheet Additional refrigerant charging amount for R22 R407C R410A and R134a Diameter of connection pipe Outdoor unit throttle Liquid pipe mm Gas pipe mm...

Страница 18: ...fan motor clamp board S22020002 S22020002 1 16 fan motor S16800001 S16800001 1 17 fan motor clamp board S22020001 S22020001 1 18 drain pipe S1301000101 S1301000101 1 19 step motor S17000001 S17000001...

Страница 19: ...007 1 16 fan motor clamp board S22020004 1 17 fan motor S16800003 1 18 fan motor clamp board S22020007 1 19 connction pipe pressed plate S22020005 1 20 motor stand S22020006 1 21 drain pipe S130100010...

Страница 20: ...0200007 1 15 wall frame S10620017 1 16 fan motor clamp board S22020008 1 17 fan motor S16800008 1 18 connction pipe pressed plate S22020005 1 19 drain pipe S1301000104 1 20 step motor S17000003 1 21 c...

Страница 21: ...ion sponge inside S61410002 S61410002 1 16 noise absorption sponge outside S61410019 S61410019 1 17 big handle apricot grey S22210001 S22210001 1 18 right side panel apricot grey S10600002P S10600002P...

Страница 22: ...S20305138 1 14 big handle apricot grey S22210006 1 15 wiring compressor S3320000501 1 16 valve cover S21420007 1 17 valve support subassembly apricot grey S11200002P 1 18 stop valve 1 4 S1420001705 1...

Страница 23: ...right side panel apricot grey S10600004P 1 16 big handle apricot grey S22210002 1 17 valve cover S21420007 1 18 valve support apricot grey S11200002P 1 19 noise absorption sponge outside S61410003 1 2...

Страница 24: ...s below see the process below see the process below see the process below see the process below see the process below see the process below see the process below see the process below see the process...

Страница 25: ...cause of poor radiating 1 Check the voltage of power supply 2 Check the system see the process below see the process below 1 the wiring terminal between the mainboard and wifi module loosened or poorl...

Страница 26: ...47 46 Troubleshooting Troubleshooting...

Страница 27: ...2 11 1 Cold pasma zero wire connector 2 Power supply zero wire connector 3 PG fan contral connector 4 Cold pasma fire wire connector 5 PG fan feedback connector 6 Auto key 7 Vertical swing connector 8...

Страница 28: ...del Insert the jumper cap tightly Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Replace the mainboard with the same model End Yes Yes Yes Yes Yes No No No No No 2 IDU A...

Страница 29: ...nated Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Is the motor started up No Replace PG motor Replace the mainboard with the same model End Reinstall the blade and mo...

Страница 30: ...inal between temperature sensor and controller is loosened or poorly contacted yes yes yes yes Insert the temperature sensor tightly no no no no Eliminate the malfunction Check whether the temperature...

Страница 31: ...ording to the service manual Noted the detection method of the coil of the eletric expansion valve there is five pieces of the coil of the eletric expansion valve the resistance of one of them the lef...

Страница 32: ...expansion valve 6 Compressor start failure protection L1 Main checking points If the connection wire of the compressor is connected properly Flow chart If the stop duration of the compressor is suffic...

Страница 33: ...itable Flow chart 8 ODU Charging malfunction U1 Main checking points If the mainboard is broken If the wiring of the induction is connected well and if the induction is broken Flow chart Energize the...

Страница 34: ...it Refrigerant is leaking Discharged air temperature during cooling is higher than normal discharged wind temperature Discharged air temperature during heating is lower than normal discharged wind tem...

Страница 35: ...ormal phenomenon Abnormal sound will disappear after a few minutes When turn on or turn off the unit there s abnormal sound due to flow of refrigerant inside airconditioner Water running sound can be...

Страница 36: ...08 42 24 128 78 6 542 114 2 2409 29 853 66 7 113 37 43 23 186 79 6 3315 115 2 1816 28 799 98 8 107 96 44 22 286 80 6 1288 116 2 1242 27 750 18 9 102 85 45 21 425 81 5 9336 117 2 0686 26 703 92 10 98 0...

Страница 37: ...shaft on both sides of the panel to make it separate from the groove Remove the panel 3 Remove guide louver Remove axial sleeve of guide louver Procedure Note 5 Remove the filter 4 Remove electric box...

Страница 38: ...at the joint of the evaporator and rear case B Adjust slightly the pipe on the evaporator to separate the pipe with the evaporator C Remove the evaporator to separate the evaporator with rear case ass...

Страница 39: ...3 Remove protective grille Remove the screws fixing protective grille and then remove the protective grille Procedure 4 Remove axial flow blad Remove the nut fixing the blade and then remove the axial...

Страница 40: ...iring terminals Then lift the electric box to remove it Right side plate Electric box assy Screw Left side plate Note Procedure 10 Remove motor and motor support Remove tapping screws fixing the motor...

Страница 41: ...valve assy When unsoldering the spot weld wrap the 4 way valve with wet cloth completely to avoid damaging the valve due to high temperature 4 way valve assy Isolation sheet Screw Note Procedure 14 Re...

Страница 42: ......

Отзывы: