background image

Modbus Interface

CoolPlug PRM   Rev 0.1

5

www.coolautomation.com

© 2017 CoolAutomation

2.1 Modbus Register Map

Holding Register

 Address*

Description

Read

Write

Required**

Notes

Hex

Dec

Version Type

CoolPlug Internals

0002

2

 Reset

w

1 - Enter Boot Mode
2 - Reset CoolPlug
CoolPlug does not respond to the
write request into this register.

Configuration and Status

0020

32

HVAC Type index

r

Internal use

0021

33

Firmware Version

r

Major * 100 + Minor* 10 +
SubMinor

0022

34

Serial Number low word

r

0023

35

Serial Number high word

r

0024

36

Modbus Device address

w

Effective only after reset

0025

37

Master/Slave on HVAC line if another RC is
connected

r/w

0.0.4

0 - Slave
1 - Master
2 - Auto

0026

38

Indoor Centralized Address

r

Line/Indoor Status

0060

96

Line state (bit fields)

r

bit0: 

0 - not connected to indoor, 
1 - connected to indoor

bir1: - Reserved
bit2: 

0 - no failure, 
1 - indoor reports failure

bit3: 

0 - normal operation, 
1 - device in boot mode

bit4: 

0 - line configured, 
1 - line not configured

bits5..15: - Reserved

0061

97

Compact indoor status

r

bit0: 0  - on/off
bits: 1-5 - mode 
see 

mode encoding

bits 6-9: - fan speed
see 

fan speed encoding

bits 10-12: - louver
see

 louver position encoding

bit13: - filter sign
bit14: - therm on

0062

98

Set temperature

r/w

º

Celsius (x10)

0063

99

Ambient temperature

r

º

Celsius (x10)

0064

100

HVAC Failure code

r

0 - OK, else - HVAC failure code

0065

101

Own ambient temperature

r/w

º

Celsius (x10)

Line/Indoor Status (alternative)

0090

144

Line state (bit fields)

r

Same as 0x0060

0091

145

On/Off

r/w

0 - Off, other - On

0092

146

Mode

r/w

see 

mode encoding

0093

147

Fan speed

r/w

see 

fan speed encoding

0094

148

Swing

r/w

see

 louver position encoding

0095

149

Filter sign

r/w

0 - no filter sign 
1 - filter cleaning required

0096

150

Set temperature

r/w

º

Celsius (x10)

0097

151

Ambient temperature

r

º

Celsius (x10)

0098

152

HVAC Failure code

r

0 - OK, else - failure code

0099

153

Own ambient (feed) temperature

r/w

º

Celsius (x10)

Содержание CoolPlug

Страница 1: ... 2017 CoolAutomation CoolPlug PRM Document Revision 0 1 10 3 2017 www coolautomation com CoolPlug Universal Interface Adapter for HVAC Systems ...

Страница 2: ...2 Contents CoolPlug PRM www coolautomation com 2017 CoolAutomation Table of Contents 1 Document Revision History 3 2 Modbus Interface 4 5 2 1 Modbus Register Map ...

Страница 3: ...Document Revision History CoolPlug PRM Rev 0 1 3 www coolautomation com 2017 CoolAutomation 1 Document Revision History 0 1 Initial ...

Страница 4: ...tion to Modbus is Two Wire EIA TIA 485 standard interface via 485 A and 485 B terminals recommended by Modbus specification On such 2W bus at any time only one driver has the right for transmitting thus a Modbus communication is always initiated by the master CoolPlug will never transmit without receiving a request from Modbus master A number of CoolPlug devices can be connected to single 2W bus E...

Страница 5: ...lure 1 indoor reports failure bit3 0 normal operation 1 device in boot mode bit4 0 line configured 1 line not configured bits5 15 Reserved 0061 97 Compact indoor status r bit0 0 on off bits 1 5 mode see mode encoding bits 6 9 fan speed see fan speed encoding bits 10 12 louver see louver position encoding bit13 filter sign bit14 therm on 0062 98 Set temperature r w ºCelsius x10 0063 99 Ambient temp...

Страница 6: ...s on wire are less by 1 then specified in table If nothing specified register is supported in any version and or type N A means future option Mode Encoding Cool 0 Heat 1 Auto 2 Dry 3 HAux 4 Fan 5 Fan Speed Encoding Low 0 Medium 1 High 2 Auto 3 Top 4 Very Low 5 Louver swing position Encoding Vertical 0 30º 1 45º 2 60º 3 Horizontal 4 Auto 5 Off 6 No 7 ...

Отзывы: