Modbus Interface

CoolPlug PRM   Rev 0.1

4

www.coolautomation.com

© 2017 CoolAutomation

  2   Modbus Interface

CoolPlug is fully compliant with following Modbus specifications:

·

MODBUS over Serial Line Specification and Implementation Guide V1.02

·

MODBUS application protocol specification V1.1b

CoolPlug supports Modbus RTU Transmission Mode. The default frame format for CoolPlug is:

Baud Rate   9600

Start Bits   1
Data Bits   8

Parity   No

Stop Bits   1

CoolPlug physical connection to Modbus is Two-Wire EIA/TIA-485 standard interface via 485-A and 485-B
terminals, recommended by Modbus specification. On such 2W-bus, at any time only one driver has the right for
transmitting thus a Modbus communication is always initiated by the master. CoolPlug will never transmit without
receiving a request from Modbus master. 
A number of CoolPlug devices can be connected to single 2W-bus. Each CoolPlug in this case must have
unique Modbus slave address.

Supported Modbus Functions

Function Code

Function Description

03 (0x03)

 Read Holding Registers

06 (0x06)

 Write Single Register

16 (0x10)

 Write Multiple registers

43 14 (0x2B 0x0E)  Read Device Information

Содержание CoolPlug

Страница 1: ... 2017 CoolAutomation CoolPlug PRM Document Revision 0 1 10 3 2017 www coolautomation com CoolPlug Universal Interface Adapter for HVAC Systems ...

Страница 2: ...2 Contents CoolPlug PRM www coolautomation com 2017 CoolAutomation Table of Contents 1 Document Revision History 3 2 Modbus Interface 4 5 2 1 Modbus Register Map ...

Страница 3: ...Document Revision History CoolPlug PRM Rev 0 1 3 www coolautomation com 2017 CoolAutomation 1 Document Revision History 0 1 Initial ...

Страница 4: ...tion to Modbus is Two Wire EIA TIA 485 standard interface via 485 A and 485 B terminals recommended by Modbus specification On such 2W bus at any time only one driver has the right for transmitting thus a Modbus communication is always initiated by the master CoolPlug will never transmit without receiving a request from Modbus master A number of CoolPlug devices can be connected to single 2W bus E...

Страница 5: ...lure 1 indoor reports failure bit3 0 normal operation 1 device in boot mode bit4 0 line configured 1 line not configured bits5 15 Reserved 0061 97 Compact indoor status r bit0 0 on off bits 1 5 mode see mode encoding bits 6 9 fan speed see fan speed encoding bits 10 12 louver see louver position encoding bit13 filter sign bit14 therm on 0062 98 Set temperature r w ºCelsius x10 0063 99 Ambient temp...

Страница 6: ...s on wire are less by 1 then specified in table If nothing specified register is supported in any version and or type N A means future option Mode Encoding Cool 0 Heat 1 Auto 2 Dry 3 HAux 4 Fan 5 Fan Speed Encoding Low 0 Medium 1 High 2 Auto 3 Top 4 Very Low 5 Louver swing position Encoding Vertical 0 30º 1 45º 2 60º 3 Horizontal 4 Auto 5 Off 6 No 7 ...

Отзывы: