4.0 Operating procedures:
There are 3 factors to consider when determining where to place the COOL-SPACE
®
unit.
1.
Fresh air supply:
The inlet side of the unit (pad side) requires a constant,
uninterrupted supply of fresh air for maximum performance. A distance of 3 ft clear
space is recommended.
2.
Discharge air flow:
The cool air discharged from the unit should be free of
obstruction to allow the air to circulate in order to maximize the cooling zone.
3.
Ventilation:
In order to operate at maximum effectiveness, it is helpful to have
provisions to remove the air discharged from the COOL-SPACE
®
unit from the
cooling area. This ensures that the COOL-SPACE
®
unit does not recirculate air that
has already been through the evaporative cooling process.
The COOL-SPACE
®
unit must be placed on a level surface to operate correctly. The
units create an oval shaped air pattern that can reach out as far as 70 feet with large fans.
Obstacles such as racks and workbenches may interfere with the cooling zone. An
attempt should be made to locate the unit in such a manner that interruption of the air
pattern is held to a minimum. Multiple units may be required to cover larger areas.
When the COOL-SPACE
®
unit is placed near a wall or other vertical obstruction, it is
recommended that there be a space of at least 3 feet between the back (pad side) of the
unit and the obstruction. This ensures that a clear supply of fresh air is able to get to the
inlet of the unit.
A platform or framework may be built to support the COOL-SPACE
®
unit in order to
place the unit out of the way of obstacles. When constructing a framework, ensure that it
will not allow the COOL-SPACE
®
unit to tip over. Also, the structure must be able to
accommodate the unit plus the added weight of the water in both the pads and the
reservoir.
16” Unit: 84 lbs. (unit) + 24 lbs. (pad operating weight) + 120 lbs. (15 gal. reservoir) =
228 lbs.
36” Unit: 295 lbs. (unit) + 60 lbs. (pad operating weight) + 384 lbs. (48 gal. reservoir) =
739 lbs.
48” Unit: 497 lbs. (unit) + 100 lbs. (pad operating weight) + 512 lbs. (64 gal. reservoir) =
1,109 lbs.
4.1 Filling the unit with water:
Once the COOL-SPACE
®
unit has been hooked up to a water source as described in 3.1,
turn the water supply valve on and the unit will fill with water. The float valve will shut
off the water flow when the sump is full.