- 14 -
E. Actual step motor of electronic expansion valve.
6. Operate the heat pump water heater
6.1
Checking the parameters
When the unit is under running status, depress and hold in the
ELEC.HEATING button, the screen will display the user
parameter. Pressing the up and down arrows to check all
parameters from P1 to PE. Both parameter numbers and its
value are flashing. See parameter on the table. You can use both
the CLOCK+ELEC.HEATING button to check the professional
parameter.
6.2
Changing the parameters
Parameters can be changed in standby and running status. When
the unit is in standby and running status, select the parameter as
described above. Then press and holds the ELEC.HEATING
button for 5 seconds, user parameter number value will flash,
and it can be changed with up and down arrows. Press the
ELEC.HEATING again to save the change, or the new value
will be saved automatically after 5 seconds.
Press and hold the CLOCK+ELEC.HEATING button to check
the professional parameter, and the press CLOCK to change the
professional parameters.