15.1

 

Rebuilding the wireless mesh network 

In some cases, rebuilding the mesh network topology may be required. For example, when 
changing the position of a number of CoolPlugs.  

To ensure the network is built in the most optimal way, follow the reconnection procedure: 

To reconnect all paired devices to the wireless network mesh 

1

 

On the CooLinkHUB, press the 

OK

 button. An options menu is displayed on the screen. 

2

 

With the arrow buttons select the 

Wireless

 option. 

 

3

 

Press the 

OK

 button. A new options menu is displayed on the screen. 

4

 

With the arrow buttons select the 

Reconn

 option.  

 

5

 

Press the 

OK

 button. 

6

 

Upon successful reconnection, the expected number of CPs is displayed on the screen 
in L5 GXXX (as in the image below). 

 

Note

: To reconnect devices, no actions need to be performed on the CoolPlug devices. 

 

Содержание CooLinkHub

Страница 1: ...CoolPlug CooLinkHUB HVAC Bridge Quick Installation Guide Version 2 2 11 07 19 Document Number 2 2 Contact information info coolautomation com HVAC Control Made Simple ...

Страница 2: ... General Option 1 11 6 2 FJ Fujitsu General Option 2 12 6 3 FJ Fujitsu General Option 3 13 7 Connecting CoolPlug ME Mitsubishi Electric 14 7 1 Option 1 CN 105 14 8 Connecting CoolPlug MH Mitsubishi Heavy 15 8 1 Option 2 1 2 15 9 Connecting CoolPlug HT Hitachi 16 10 Connecting CoolPlug LG LG 17 11 Connecting CoolPlug Gree GRTS 18 11 1 Gree Option 1 18 11 2 Gree Option 2 19 11 3 Gree Option 3 H1 H2 ...

Страница 3: ...r radiation water high relative humidity or dust Install the equipment only in a restricted access location When wall mounting be sure to fix firmly on a stable surface and in accordance to the instructions below When DIN rail mounting fix the devices properly to the DIN rail following the instructions below When mounting on DIN rail inside a metallic cabinet be sure to properly connect to earth U...

Страница 4: ...PLUG IN THE FOLLOWING LOCATIONS a Where mineral oil mist or oil spray or vapor is produced for example in a kitchen Plastic parts may deteriorate and fall off b Where corrosive gas such as sulfurous acid gas is produced c Near machinery emitting electromagnetic waves Electromagnetic waves may disturb or damage the operation of the CooLinkHUB d Where flammable gas may leak where there is carbon fib...

Страница 5: ...CooLinkHUB on the other via a PBUS Network The CooLinkHUB protocol converter allows integration to any Home Automation system 1 2 Network Topology The PBUS is a Cool Automation s proprietary Bus running on a shielded twisted pair cable 24AWG The PBUS utilizes free network topology star daisy chain etc No loops allowed Up to 10 CoolPlugs can be connected in a single PBUS network 1 3 CoolPlug Models...

Страница 6: ...oLinkHUB CooLinkHUB Unit USB cable RS 232 cable Power supply Universal or EU according to SN 1 4 2 CoolPlug CoolPlug Unit CoolPlug back plate for adding two magnets CoolPlug back plate for adding two stamps Two stamps Two magnets Optional Terminal cable according to the specific plug model as indicated on the above table ...

Страница 7: ...e CoolPlug between the CoolPlugRJ 11 connectorandthe S21 port on the indoor unit s PCB Consult HVAC manufacturer s installation manual for location of S21 on Control Board 2 Connecting the CoolPlug to the CooLinkHUB Connect the signal wires of the PBUS cable between CoolPlug terminals 1 and 2 and CooLinkHUB terminals VDC 1 and 2 respectively See page 5 for system overview no point to point connect...

Страница 8: ...in unit Connect the CoolPlug s P1 P2 terminals to the P1 P2 terminals on the indoor unit 2 Connecting theCoolPlug to the CooLinkHUB Connect the signal wires of the PBUS cable coming from the VDC 1 and 2 terminals on the CooLinkHUB to the corresponding 1 and 2 terminals on the CoolPlug respectively Optional Connect the Wired Remote Controller W R C in parallel mode No Polarity requirements ...

Страница 9: ...t the cable supplied with the CoolPlug to the port labeled Indoor on CoolPlug and the corresponding connector on the indoor unit 2 Connecting the CoolPlug to the CooLinkHUB Connect the signal wires of the PBUS cable using VDC 1 and 2 terminals on the CooLinkHUB to the corresponding 1 and 2 terminals on the CoolPlug 3 Optional Connect the wired remote to the W R C socket on the CoolPlug The cable i...

Страница 10: ... the PN SA TO Indoor Unit Connect the CoolPlug s A B terminals to A B terminals on indoor unit To connect to Panasonic indoor unit use R1 R2 terminals 2 Connecting theCoolPlug to theCooLinkHUB Connect the signal wires of the PBUS cable coming from the VDC 1 and 2 terminals on the CooLinkHUB to the corresponding 1 and 2 terminals on the CoolPlug 3 Optional Connect the Wired Remote Controller W R C ...

Страница 11: ... R1 terminals to corresponding terminals on the indoor unit keeping the wire colors consistency 2 Connecting the CoolPlug to the CooLinkHUB Connect the signal wires of the PBUS cable using the VDC 1 and 2 terminals on the CooLinkHUB to the corresponding 1 and 2 terminals on the CoolPlug 3 Optional Connect the Wired Remote Controller W R C For indoors that work with APG000 or compatible W R C model...

Страница 12: ...nkHUB to the corresponding 1 and 2 terminals on the CoolPlug 2 Connecting the CoolPlug HVAC Line to the Fujitsu Indoor Unit Connect the CoolPlug s W1 B1 R1 terminals to indoor unit Consult HVAC manufacturer s Installation Manual for instructions 3 Optional Connect the CoolPlug s W2 B2 R2 terminals to the Fujitsu Wired Remote Controller W R C For indoors that work with EZ 099 or compatible type wir...

Страница 13: ...g s W1 B1 R1 terminals to the corresponding terminals on the indoor unit keeping the wire colors consistent 2 Connecting the CoolPlug to the CooLinkHUB Connect the signal wires of the PBUS cable using the VDC 1 and 2 terminals on the CooLinkHUB to the corresponding 1 and 2 terminals on the CoolPlug 3 Optional Connect the Wired Remote Controller W R C For indoors that work with 2 wire compatible W ...

Страница 14: ... Connect the ME CN 105 cable supplied with the CoolPlug between the CoolPlug RJ 11 connector and the CN 105 port on the indoor unit s Control Board Consult the HVAC manufacturer s installation manual for the location of the CN 105 port on the Control Board 2 Connecting theCoolPlug to theCooLinkHUB Connect the signal wires of the PBUS cable using the VDC 1 and 2 terminals on the CooLinkHUB to the c...

Страница 15: ...r Unit Connect the CoolPlug s HVAC 1 HVAC 2 terminals to the 1 2 terminals on the indoor unit Consult the HVAC manufacturer s installation manual for the location of the 1 and 2 terminals 2 Connecting theCoolPlug to theCooLinkHUB Connect the signal wires of the PBUS cable using the VDC 1 and 2 terminals on the CooLinkHUB to the corresponding 1 and 2 terminals on the CoolPlug 3 Optional Connect the...

Страница 16: ...Plug to the Hitachi unit Connect the CoolPlug s HVAC 1 2 terminals to the 1 2 terminals on the indoor unit 2 Connecting the CoolPlug to the CooLinkHUB Connect the signal wires of the PBUS cable coming from the VDC 1 and 2 terminals on the CooLinkHUB to the corresponding 1 and 2 terminals on the CoolPlug 3 Optional Connect the Wired Remote Controller W R C ...

Страница 17: ...ied with the CoolPlug between the CoolPlug HVAC Y B R terminals and the port on the indoor unit s PCB Consult the HVAC manufacturer s installation manual 2 Connecting the CoolPlug to the CooLinkHUB Connect the signal wires of the PBUS cable between CoolPlug terminals 1 and 2 and CooLinkHUB terminals VDC 1 and 2 respectively 3 Optional Connect the Wired Remote Controller W R C in parallel mode ...

Страница 18: ...d the connector on the indoor unit s PCB Consult the HVAC manufacturer s Installation manual for the location of the indoor unit connector on the Control Board 2 Connecting the CoolPlug to the W R C Connect the short cable supplied with the CoolPlug between the 2 W R C ports and the W R C cable to the CoolPlug s W R C port 3 Connecting the CoolPlug to the CooLinkHUB Connect the signal wires of PBU...

Страница 19: ...VAC manufacturer s Installation manual for location of indoor unit cable 2 Connecting the CoolPlug to the W R C Connect the short cable supplied with the CoolPlug between the 2 W R C ports Connect the W R C cable to the connector of the adapter cable supplied with the CoolPlug Then connect the CoolPlug adapter to the CoolPlug W R C port 3 Connecting the CoolPlug to the CooLinkHUB Connect the signa...

Страница 20: ...1 H2 terminals to terminals H1 and H2 on the indoor unit Consult HVAC manufacturer s Installation manual for location of terminals H1 and H2 Note W R C can be connected to H1 H2 in parallel to the CoolPlug connection 2 Connecting the CoolPlug to the CooLinkHUB Connect the signal wires of the PBUS network cable using VDC 1 and 2 terminals on the CooLinkHUB to the corresponding 1 and 2 terminals on ...

Страница 21: ...CoolPlug CooLinkHUB HVAC Bridge Connecting Home Automation BMS CoolRemote QIG Version 2 2 21 CoolPlug CooLinkHUB 12 Connecting Home Automation BMS CoolRemote ...

Страница 22: ... code from the type label to auto fill in all the CooLinkHUB details for the CoolRemote App 2 Register your username email and password to remotely control and monitor all your HVAC units Option B Manual 1 Go to https coolremote net register Enter the CooLinkHUB SN number and PIN code printed on the sticker 2 Register your username email and password to remotely control and monitor your HVAC units...

Страница 23: ...power to the CoolPlug the Firmware version is displayed by flashing LEDs followed by the operational state of the system 14 2 CoolPlug Normal Operation In normal operation the blue LED blinks periodically The green and amber LEDs are not lit Normal operation Problems LED OFF LED ON LED Blinking Green HVAC Line OK HVAC Line not connected HVACLine errors Amber PBUS OK PBUS not connected PBUS errors ...

Страница 24: ...Plug UID The CoolPlug UID is flashed after one Short press on the CoolPlug push button Toggling the HVAC ON OFF Toggle the HVAC state ON OFF with one Long press on the CoolPlug push button Resetting the CoolPlug Reset the CoolPlug with one Short press followed by one Continuous press on the CoolPlug push button ...

Страница 25: ...CoolPlug with the CooLinkHUB 1 On the CooLinkHUB press the OK button 2 An Option menu is displayed on the LCD screen 3 With the up down arrow buttons select the Wireless option 4 Press the OK button A new options menu is displayed on the screen 5 With the arrow buttons select the Pair option 6 On the CoolPlug press the button five consecutive times A fast blinking red light is displayed while pair...

Страница 26: ...gy may be required For example when changing the position of a number of CoolPlugs To ensure the network is built in the most optimal way follow the reconnection procedure To reconnect all paired devices to the wireless network mesh 1 On the CooLinkHUB press the OK button An options menu is displayed on the screen 2 With the arrow buttons select the Wireless option 3 Press the OK button A new opti...

Страница 27: ...e CoolPlug back plate has two magnets that allow you to mount it on any metal surface On the Wall Attach the CoolPlug back plate to the wall using screws as shown The wires can be fed through the hole in the center of the cover or from the side as shown On DIN Rail Use back plate for DIN rail to attach it to the DIN rail utilizing magnets ...

Страница 28: ...CoolPlug CooLinkHUB HVAC Bridge Mounting the CoolPlug QIG Version 2 2 28 CoolPlug CooLinkHUB Need more help Visit us https coolautomation com support HVAC Control Made Simple ...

Отзывы: