T H E O R Y   O F   O P E R A T I O N

   

Battery Handling / Storage

   

 Refer to the battery manufacturer’s Safety Data Sheets 

(01-30839 "MSDS Sheets, Battery, Standard"). LiftMaster

®

 

does not recommend storage of batteries in the field. 

Batteries are intended for immediate use.

   

•  The battery connections in the system are tested once 

every hour. If the batteries are not connected, the 

operator will attempt to close the door after DIP switch 

selected Alarm Delay to Close. The alarm within the 

operator will sound pattern of one second on, one 

second off until the batteries are reconnected or 

replaced in the event of a major fault.

   

•  During a power loss, the operator will activate the 

warning system and automatically close the door 

whenever the battery voltage drops below the minimum 

voltage. When this occurs the strobe will flash until the 

battery is sufficiently charged.

  2.2  UNIT HAS AC POWER & NO ALARM CONDITION:
   

•  The B2/C2 control station is used to operate the door 

electrically.

   

•  Activation of the safety edge while door is closing will 

cause it to reverse to full open limit.

   

•  Activation of safety edge while the door is opening will 

cause it to stop.

   

•  Activating the optional key-test switch for at least 6 

seconds will put the operator in alarm active mode  

(see ACTIVE ALARM section for detail operation of 

alarm active mode).

  2.3 UNIT HAS AC POWER & ACTIVE ALARM CONDITION:
   

•  The warning system will activate. The door will 

automatically close after the preset time delay. The time 

delay is set by means of DIP switches 1 and 2,  

(See page 12).

   

•  The door will reverse to full open limit if obstruction is 

encountered while closing. The door will automatically 

close again after the preset time delay. If the obstruction 

is not cleared, upon the 3rd attempt to close, the door 

will stop on the obstruction and activate the warning 

system then release the brake. Subsequent obstruction 

will cause the door to stop for two (2) seconds then 

release the brake. 

   

•  After the 3rd attempt to close, the integrated braking 

system controls the door’s descending speed.

  2.4  UNIT HAS NO AC POWER & NO ALARM CONDITION:
   

•  The CLOSE and STOP buttons of the B2/C2 control 

station are functional. The door’s descending speed is 

controlled by the integrated braking system.

   

•  The door will stop if obstruction is encountered while 

closing. 

   

•  The OPEN button is NOT functional.

  2.5  UNIT HAS NO AC POWER & ACTIVE ALARM CONDITION:
   

•  The warning system (optional) will activate. The door will 

automatically close after the preset time delay. The time 

delay is set by means of DIP switches 1 and 2, (See  

page 12).

   

•  If an obstruction is encountered the door will stop for 2 

seconds then release the brake. Subsequent obstruction 

will cause the door to stop for 2 seconds then release the 

brake.

Содержание FDO AC

Страница 1: ...AC BC SOLID STATE INDUSTRIAL DUTY FIRE DOOR OPERATOR NOT FOR RESIDENTIAL USE FDO 1 1 2 HP FDO AC BC LM PLC C O N TR O L LMPLC B2 C2 Wiring C O N T R O L W I R E D Serial Box Installation Date 2 YEA R...

Страница 2: ...arnings 10 Control Station Wiring 10 Mounting Instructions 10 DIAGRAMS Standard Power and Control Connection Diagrams 11 Logic Board Illustration 12 Optional Control Settings 13 1 Phase Wiring Diagram...

Страница 3: ...ICAL TRANSFORMER 24 Vac 75 VA CONTROL STATION NEMA 3 Button Station OPEN CLOSE STOP WIRING TYPE C2 Standard B2 Optional To convert to B2 see pages 14 thru 17 note 4 LIMIT ADJUST Linear driven fully ad...

Страница 4: ...However to insure proper and safe operation it is recommended that the batteries be replaced every two years Battery testing is conducted automatically See the Battery Test Description GENERAL DESCRIP...

Страница 5: ...LARM section for detail operation of alarm active mode 2 3 UNIT HAS AC POWER ACTIVE ALARM CONDITION The warning system will activate The door will automatically close after the preset time delay The t...

Страница 6: ...n secure the operator to wall or mounting bracket Figure 3 7 Align sprockets and secure FIGURE 1 FIGURE 2 Before your operator is installed be sure the door has been properly aligned and is working sm...

Страница 7: ...cord take up installation instructions for details WIRING For wiring of your sensing device to the operator refer to the wiring diagram provided with your operator See field connection terminals ident...

Страница 8: ...ttom of the door even with top of door opening 4 Repeat Steps 1 and 2 for close cycle Adjust close limit nut so that actuator is engaged as door fully seats at the floor Retaining Plate CLOSE Limit Sw...

Страница 9: ...x as the power wiring IMPORTANT NOTE This unit must be properly grounded Failure to properly ground this unit could result in electric shock and serious injury P O W E R W I R I N G G R O U N D W I R...

Страница 10: ...eep Clear Door May Move at any Time Without Prior Warning Do Not Let Children Operate the Door or Play in the Door Area C O N T R O L S T AT I O N W I R I N G A N D I N S T A L L AT I O N To reduce th...

Страница 11: ...J1 L1 L2 L3 GREEN GROUND SCREW OPEN CLOSE STOP 2 WIRE NON MONITORED REVERSE EDGE 2 WIRE NON MONITORED REVERSE EDGE HOT NEUTRAL CHASSIS GROUND J2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 2...

Страница 12: ...12 Terminal Block J1 Heat Sink Dip Switches S1 L O G I C B O A R D I L L U S T R AT I O N Terminal Block J2 NOTE For DIP switch field settings see page 13...

Страница 13: ...Y For dip switch location and orientation refer to illustration on page 12 ALARM DELAY TO CLOSE S1 1 and S1 2 set the Alarm Delay to Close time of the operator Alarm Delay to Close is the time between...

Страница 14: ...SFORMER WH BK Y R A M I R P Y R A D N O C E S OPTIONAL USER INTERFACE BR BR SEE NOTE 2 REVERSE EDGE C NO KEY TEST OPEN CLOSE STOP VOICE BOARD PU BK RD YE SPEAKER AUXILIARY TERMINAL BLOCK RD BK 250 MA...

Страница 15: ...RD YE SPEAKER AUXILIARY TERMINAL BLOCK RD BK 250 MA MAX BR PU YE STROBE LIGHT 24V BK BL PU GY YE BK C C _ 115V ONLY BL RD BL RD RPM BOARD BK 25 OHM 50 W RESISTOR _ _ _ _ _ RD BK 12 VDC BATTERY BK WH W...

Страница 16: ...O ALARM SYSTEM TRANSFORMER WH BK Y R A M I R P Y R A D N O C E S OPTIONAL USER INTERFACE BR BR SEE NOTE 2 REVERSE EDGE C NO KEY TEST OPEN CLOSE STOP VOICE BOARD PU BK RD YE SPEAKER AUXILIARY TERMINAL...

Страница 17: ...K RD YE SPEAKER AUXILIARY TERMINAL BLOCK RD BK 250 MA MAX BR PU YE STROBE LIGHT 24V C C _ J21 BK BK BK BK T3 T2 T1 BK BK BK 95 96 L3 T3 L2 T2 L1 T1 460V 3 PH MOTOR CONNECTION INTERNAL MOTOR CONNECTION...

Страница 18: ...eck for excessive slack Check and adjust as required Lubricate Sprockets Check set screw tightness Fasteners Check and tighten as required Bearings and Shafts Check for wear and lubricate Battery Main...

Страница 19: ...K20 1050C 2PSF MOTOR KIT ITEM DESCRIPTION QTY M1 Motor 1 K75 32620 BRAKE ASSEMBLY KIT ITEM PART DESCRIPTION QTY B1 10 10190 Brake Release Lever 1 B2 10 10191 Brake Disc 1 B3 10 14646 Brake Cover 1 B4...

Страница 20: ...6 L 5 S 6 S 2 S 3 S 7 S 5 B 0 1 B 4 S 9 S 5 1 E 3 1 B 2 B 1 1 B 1 B 2 1 B 6 B B8 7 B 4 1 B 4 B 9 B 5 1 B S8 1 S 3 B 9 E 1 L 6 L 1 E 6 E7 L8 3 L 1 E 3 1 E 4 E 4 1 E 2 1 E 4 1 1 M 2 3 E17 E2 I L L U S T...

Страница 21: ...00 Roll Pin 1 8 x 1 long 1 L7 87 E 038 E Ring 3 8 1 K20 1050C 2PSF MOTOR KIT ITEM DESCRIPTION QTY M1 Motor 1 K75 32621 BRAKE ASSEMBLY KIT ITEM PART DESCRIPTION QTY B1 10 10191 Brake Disc 1 B2 10 11545...

Страница 22: ...9 S 4 S 4 B 8 S 1 S 2 1 B 7 1 B M1 1 4 4 1 B 3 B 3 1 B 5 1 B 6 B 9 B 1 B 0 1 B 6 1 B 5 B 7 B 8 B 2 B 1 1 B 7 S 8 1 B 2 S 4 E 5 L 7 L 2 L 5 S 6 S 3 S 0 1 E 5 E 7 E 1 E 2 3 L3 L1 I L L U S T R AT E D P...

Страница 23: ...PART DESCRIPTION QTY M1 07 10179 2 Brake Hub 1 M2 20 3100C 4T Motor 1 Hp 230 460V 3Ph TEFC 1 K75 32620 BRAKE ASSEMBLY KIT ITEM PART DESCRIPTION QTY B1 10 10190 Brake Release Lever 1 B2 10 10191 Brake...

Страница 24: ...E 5 L 6 L 5 S 6 S 2 S 3 S 7 S 5 B 0 1 B 4 S 9 S 5 1 E 3 1 B 2 B 1 1 B 1 B 2 1 B 6 B B8 7 B 4 1 B 4 B 9 B 5 1 B S8 1 S 3 B 9 E 1 L 6 L 1 E 6 E7 L8 3 L 1 E 3 1 E E4 4 1 E 2 1 E 4 1 1 M 2 E17 3 I L L U S...

Страница 25: ...L7 87 E 038 E Ring 3 8 1 K75 13742 MOTOR KIT ITEM PART DESCRIPTION QTY M1 07 10179 2 Brake Hub 1 M2 20 3100C 4T Motor 1 Hp 230 460V 3Ph TEFC 1 K75 14998 K75 15006 BRAKE ASSEMBLY KIT ITEM PART DESCRIP...

Страница 26: ...4 S 4 B 8 S 1 S 2 1 B 7 1 B M1 4 1 B 3 B 3 1 B 5 1 B 6 B 9 B 1 B 0 1 B 6 1 B 5 B 7 B 8 B 2 B 1 1 B 7 S 8 1 B 2 S 4 E 5 L 7 L 2 L 5 S 6 S 3 S 0 1 E 5 E 7 E 1 E L3 L1 1 M 1 4 2 3 3 1 5 2 6 E 9 E 3 E 8 E...

Страница 27: ...27 O P E R AT O R N O T E S...

Страница 28: ...trol Inputs Sensing Edges and Sensing Devices For any other devices not mentioned please consult the factory Keyswitch 6 7 8 Stop Close Open 9 10 Stop Close Open 6 7 8 LIFTMASTER MONITORED ENTRAPMENT...

Отзывы: