THEORY OF OPERATION

GENERAL DESCRIPTION:

The UL-325 compliant Fire Door Operator, FDO-A10, is an integrated fire door control system. It is
designed to interface with Normally Closed (NC) or Normally Open (NO) dry contacts from the alarm

1. FDO-A10 MODEL: (With entrapment detection devices installed and working properly.

  1.1  UNIT HAS AC POWER & NO ALARM CONDITION:

NOTICE

THIS OPERATOR IS NOT A FIRE ALARM SYSTEM.

IT CAN NOT DETECT A FIRE CONDITION

The B2 control station is used to operate the door
electrically.

Activation of the sensing edge or Photo eyes while door is closing
will cause it to reverse to full open limit.

  1.2  ALARM CONDITION W/ AC POWER:

Door begins closure after a preset time delay of 0 or 10 seconds (Set at 10 seconds

If obstruction is encountered by entrapement protection device(s), door will reverse to
OPEN position and attempt closure again. The door will cycle up to 3 times before
resting on the obstruction. If the obstruction is removed, the door will continue to the
fully CLOSED position.
The OPEN button will raise the door to the fully open position, and after a 10 second
delay will begin closing again. This will work until the third attempt to close has been
used, and then all OPEN functions will be disabled until the alarm has been reset.

system or initiating device to control the operation of a fire door. The control station will operate

TO REDUCE THE RISK OF INJURY TO PERSONS,

USE THIS OPERATOR ONLY WITH ROLLING DOORS.

WARNING

3

with either standard B2 or C2 wiring. This operator will require the proper self diagnostic entrapment
protection device(s) to be connected and working properly to allow B2 (Momentary Pressure on the
Close button) to close the door.

on basic unit, 0 second selectable if unit is equipped with expansion module).

Note: All OPEN functions initiated by the photo eyes or sensing edge can be disabled
in the event of an active alarm condition, if the unit is equipped with the expansion module.
When this feature is selected, and an obstruction is detected by the entrapement
protection device(s), the door will rest on the obstruction. If the obstruction is later

9001(7) ECN 1057  4/10/010

removed, the door will travel to the fully CLOSED position.

The FDO-A10E medium duty motor operator is designed for use only with Service Counter Fire
Door models FD1O-1M and FD10-2M as manufactured by the Cookson Company Inc.
Door sizes range from 4'-0" x 4'-0" to 14' max opening width to 9'-0" max clear opening height.
(Smaller doors may be available with Engineering approval on a case-by-case basis.

Содержание FDO-A10E

Страница 1: ...KSON OWNER S MANUAL INDUSTRIAL DUTY FIRE DOOR OPERATOR FDO A10E 9001 7 ECN 1057 4 10 010 XXXXXXX R US SERIAL OPERATOR IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING NOT FOR RESIDENTIAL...

Страница 2: ...STATION OPEN CLOSE STOP WIRING TYPE C2 B2 STANDARD LIMIT ADJUST LINEAR DRIVEN FULLY ADJUSTABLE SCREW TYPE CAMS MECHANICAL DRIVE REDUCTION 43 1 REDUCTION IN LINE GEAR REDUCED MOTOR OUTPUT SHAFT SPEED 2...

Страница 3: ...to close has been used and then all OPEN functions will be disabled until the alarm has been reset system or initiating device to control the operation of a fire door The control station will operate...

Страница 4: ...AC power The door system must be able to generate a minimum backdriving torqueof 50 in lbs at the operator output shaft Sticking or binding doors must be repaired Doors door springs brackets and their...

Страница 5: ...rained door systems technician make repairs to cables spring assemblies and other hardware 6 SAVE THESE INSTRUCTIONS ELECTRICAL 1 DISCONNECT POWER AT THE FUSE BREAKER BOX DISCONNECT BEFORE PROCEEDING...

Страница 6: ...ntroller 6 When a second entrapment protection device is desired any device with a normally OPEN N O dry contact type output is compatible with this door See control connection diagram for connections...

Страница 7: ...plate and ensure it seats fully in slots of both nuts 2 To increase door travel spin nut away from actuator To decrease door travel spin limit nut toward actuator 3 Adjust open limit nut so that door...

Страница 8: ......

Страница 9: ...ALLED OVER DOOR BRACKET MOTOR SPROCKETS WHEN MOVING PARTS ARE EXPOSED LESS THAN 8 FT FROM THE FLOOR 9 9001 7 ECN 1057 4 10 010 FDO A10 COVER PLEASE REFER TO DOOR INSTALLATION MANUAL FOR PROPER MOTOR C...

Страница 10: ...S WIRE SCHEDULE VOLTAGE 120VAC 24VDC 18GA 18GA WIRE GAGE 10 9001 7 ECN 1057 4 10 010 10 FOR ADDITIONAL WIRING CONNECTIONS 2 RIGHT HAND DOORS SHOWN FOR LH DOORS SWITCH ORANGE AND PURPLE WIRES ON SMART...

Страница 11: ...CLOSURE DELAY FROM 10 SECONDS TO IMMEDIATE TO 21 WILL CAUSE DOOR TO RETURN TO THE FULLY OPEN POSITION ON ALARM RESET TO 22 WILL DISABLE ANY OPEN FUNCTION DURING AN ACTIVE ALARM CONDITION DOOR WILL STO...

Страница 12: ...OL WIRING TYPES ALL CONTROL WIRING TYPES ALL CONTROL WIRING TYPES NORMALLY CLOSED ALARM 3 11 12 13 CLOSED CIRCUIT N C ALARM 12 STOP CLOSE OPEN 4 3 2 1 WITH KEY LOCKOUT 3 BUTTON PUSH BUTTON STATION KEY...

Страница 13: ...CONTROL CONNECTION DIAGRAM 13 9001 7 ECN 1057 4 10 010 EXPANSION MODULE TERMINAL STRIP WITH OUTPUT TO SOUNDER STROBES SMOKE DETECTOR WIRING SINGLE DOUBLE SOUNDER STROBE SOUNDER STROBE...

Страница 14: ...SERT FOR BATTERY CHARGER CONNECTIONS NOTE BATTERY BOX WILL NOT OPERATE MOTOR IT WILL KEEP CIRCUITS AND BRAKE ENERGIZED IN THE EVENT OF POWER LOSS IT WILL MONITOR ALARM SYSTEM AND CLOSE DOOR IF ACTIVE...

Страница 15: ...BATTERY BOX WIRING DIAGRAM 15 9001 7 ECN 1057 4 10 010...

Страница 16: ...7 4 10 010 INSTALL MOVING DOOR WARNING PLACARD IN A CONSPICUOUS PLACE NEAR OPEN CLOSE STOP STATION AS INDICATED WARNING PLACARD OPEN CLOSE STOP STATION PLEASE REFER TO DOOR INSTALLATION MANUAL FOR PRO...

Страница 17: ...lubricate motor Motor bearings are lubricated and sealed at the factory Inspect and service whenever a malfunction is observed or suspected CAUTION BEFORE SERVICING ALWAYS DISCONNECT OPERATOR FROM PO...

Страница 18: ...s but door does not move Sprocket key missing or drive chain broken Check drive train for operation Intermediate shaft or key damaged Close lock off door remove motor and inspect check cause Motor hum...

Отзывы: