COOK PLC Скачать руководство пользователя страница 7

7

1

2

4

3

5

6

7

PLC Parts List - Arrangement 3

4

l

3

2

1

Part

No.

Description

Sizes 

1

Shaft

2

Drive Side Bearing

3

Housing

4

Wheel

5

Inlet Cone

6

Extended Lube Line

7

Inlet Side Bearing

Troubleshooting

Problem and Potential Cause

Low Capacity or Pressure

•Incorrect direction of rotation. Make sure the fan rotates in same direc-

tion as the arrows on the motor or belt drive assembly.

•Poor fan inlet conditions. There should be a straight clear duct at the 

inlet.

•Improper wheel alignment.

Excessive Vibration and Noise

•Damaged or unbalanced wheel.
•Belts too loose; worn or oily belts.
•Speed too high.
•Incorrect direction of rotation. Make sure the fan rotates in same direc-

tion as the arrows on the motor or belt drive assembly.

•Bearings need lubrication or replacement.
•Fan surge or incorrect inlet or outlet conditions.

Overheated Motor

•Motor improperly wired.
•Incorrect direction of rotation. Make sure the fan rotates in same direc-

tion as the arrows on the motor or belt drive assembly.

•Cooling air diverted or blocked.
•Improper inlet clearance.
•Incorrect fan RPMs.
•Incorrect voltage.

Overheated Bearings

•Improper bearing lubrication
•Excessive belt tension.

r. Test run and retighten all setscrews and bolts. Trim 

balance as necessary (.0785 in/sec max.).

After 24 hours of operation, retighten the setscrews to 

the appropriate torque. This assures full locking of the 
inner race to the shaft. Make sure the socket key or 
driver is in good condition with no rounded corners. The 
key should be fully engaged in the setscrew and held 
squarely to prevent rounding out of the setscrew socket 
when applying maximum torque.

PLC-D Parts List

Part

No.

Description

Sizes 

1

Inlet Cone

2

Wheel

3

Motor

4

Motor Base

Содержание PLC

Страница 1: ... units of the PLC Centrifugal Plenum Fans Carefully read this publication prior to any installation or maintenance procedure Carefully read this publication and any supplemental documents prior to any installation or maintenance procedure Loren Cook Company s PLC catalog provides additional information describing the equipment fan performance available accessories and specification data For additi...

Страница 2: ...mmon rigid base running the full length of the fan and motor The base must have sufficient rigidity to resist belt pull and prevent drive distortion which can lead to excessive belt and bearing wear Isolators should be located between this rigid base and the floor NOTICE Although a certain amount of vibration is inherent in operating centrifugal fans extreme vibra tion is a serious problem that ma...

Страница 3: ...No 6 thread forming screw To reverse interchange T 1 and T 4 Single Speed Single Phase Motor When ground required attach to ground A or B with No 6 thread forming screw To reverse interchange T 1 and T 4 leads 2 Speed 2 Winding Single Phase Motor Single Speed Single Phase Dual Voltage 2 Speed 2 Winding 3 Phase When ground required attach to ground A or B with No 6 thread forming screw To reverse i...

Страница 4: ...TER DISTANCE CD GAP GAP NOTICE Follow the wiring diagram in the disconnect switch and the wiring diagram provided with the motor Correctly label the circuit on the main power box and always identify a closed switch to promote safety i e red tape over a closed switch Wheel Rotation Test the fan to ensure the rotation of the wheel is the same as indicated by the arrow marked Rotation 115 and 230 Sin...

Страница 5: ...he cause of the trouble See Trouble shooting Inspection Inspection of the fan should be conducted at the first 30 minute 8 hour and 24 hour intervals of satisfactory opera tion During the inspections stop the fan and inspect as per the Conditions Chart 30 Minute Interval Inspect bolts setscrews and motor mounting bolts Adjust and tighten as necessary 8 Hour Interval Inspect belt alignment and tens...

Страница 6: ... Size Up to and including 184T 213T 365T 404T and larger 1800 RPM and less Over 1800 RPM 1800 RPM and less Over 1800 RPM 1800 RPM and less Over 1800 RPM Standard 3 yrs 6 months 2 yrs 6 months 1 yr 3 months Severe 1 yr 3 months 1 yr 3 months 6 months 1 months Bearing Replacement The fan bearings are pillow block ball bearings Bearings should be replaced individually for each side of fan An emery cl...

Страница 7: ...cation or replacement Fan surge or incorrect inlet or outlet conditions Overheated Motor Motor improperly wired Incorrect direction of rotation Make sure the fan rotates in same direc tion as the arrows on the motor or belt drive assembly Cooling air diverted or blocked Improper inlet clearance Incorrect fan RPMs Incorrect voltage Overheated Bearings Improper bearing lubrication Excessive belt ten...

Страница 8: ... serial numbers of your fan Upon receipt by Loren Cook Company of your written complaint you will be notified within thirty 30 days of our receipt of your complaint in writing as to the manner in which your claim will be handled If you are entitled to warranty relief a warranty adjustment will be completed within sixty 60 business days of the receipt of your written complaint by Loren Cook Company...

Отзывы: