Supply of combustion air
Combustion air can be provided directly via a duct from outside, or
indirectly via a vent in the outer wall of the room where the stove is to be
placed.
Some installation alternatives are shown to the right.
Before fitting an air supply duct to the air inlet, the heat reflector under
the stove body must be removed.
The air duct connection on the stove has an external diameter of Ø64 mm.
The base plate has a punched hole to lead in the air supply hose. The hole
is offset in relation to the air inlet to give more space for the niche in the
base. This means that the supply air hose must be bent backwards slightly,
close to the bottom of the stove before it can be lead down through the
hole in the base plate.
Important! In hot areas, the duct should be insulated with 30
mm mineral wool covered with a moisture inhibitor (plastic). It
is important that the lead-in between the pipe and the wall (or
floor) is sealed using jointing compound. When duct routing for
further than 1 m the pipe diameter must be increased to 100
mm and a correspondingly larger wall vent must be selected.
A 1 m length of condensation insulated ducting for combustion
air is available as an accessory.
SUPPLY AIR/ACCESSORY