SUPPLY AIR/ACCESSORY
Supply of combustion air
When a stove is installed in a room, the demand for air supply to the
room increases. Air can be provided indirectly via a vent in the outer
wall or via a duct from the outside that is connected to the connector
on the underneath of the stove. The amount of air needed for
combustion is approx. 15m
3
/h.
The connector has an external diameter of 67 mm. When duct
routing further than 1 m the pipe diameter must be increased to 100
mm and a correspondingly larger wall vent must be selected.
In hot areas the duct should be insulated with 30 mm mineral wool
covered with a moisture inhibitor (plastic). It is important that the
lead-in between the pipe and the wall (or floor) is sealed using
jointing compound.
A 1 m length of condensation-insulated ducting for combustion air is
available as an accessory.
Through the external wall.
Indirect air supply through the external wall.
Through floor and foundation slab.
Through floor and wall-and-cavity foundation.
In the back and floor plates there are
knockouts that must be removed to insert
the pipe.
Installation variants
Leave a 40 mm gap between
the condensation insulation
and the bottom of the stove.
Содержание C 790K
Страница 1: ...www contura eu C 790K Installation instructions...
Страница 9: ...4 6 5 105 GB ASSEMBLY...
Страница 10: ...8 7 9 90 10 2 3 4 1 2 1 106 GB ASSEMBLY...
Страница 11: ...107 GB ASSEMBLY...
Страница 12: ...2 1 10 10 VANA DIUM No 7 CHROME 108 GB ASSEMBLY Installing suspension profiles...
Страница 13: ...3 4 109 GB ASSEMBLY...
Страница 14: ...6 5 10 10 VAN ADI UM No 7 CH RO M E 2 1 90 110 GB ASSEMBLY...
Страница 15: ...7 8 111 GB ASSEMBLY...
Страница 16: ...2 3 mm 1 2 3 4 3 mm 112 GB ASSEMBLY Installing tiles...
Страница 17: ...5 7 6 113 GB ASSEMBLY...
Страница 18: ...8 9 114 GB ASSEMBLY...
Страница 19: ...1 2 3 4 115 GB ASSEMBLY Installing heat tank stone on top...
Страница 22: ...1 2 3 118 GB ASSEMBLY Installing the base door...
Страница 23: ......