CONTROLS, INCORPORATED
C O N T R O L S Y S T E M S & S O L U T I O N S
- 3 -
Connections
The XCAN-AC module has two twelve-pin sockets that are keyed and color-coded to make identification
easy and prevent miswiring. The right socket (black) is the DC side connection and the left socket (gray) is
the AC side connection.
Note the Pin 1 locations are not in the same orientation on both connectors.
Pin Assignments
DC Socket: [BLACK]
Pin #
Assignment
1
V B (12-24)
2
Alternate CAN Addrs
3
Not Used
4
Not Used
5
CAN L
6
Ground (V-)
7
Ground (V-)
8
CAN H
9
Not Used
10
Not Used
11
Not Used
12
V B
AC Power Socket: [GREY]
Pin #
Assignment
1
CT Phase A Return
2
CT Phase B Return
3
CT Phase C Return
4
Generator Neutral
5
Not Used
6
Not Used
7
Generator Phase B
8
Generator Phase C
9
Generator Phase A
10
CT Phase C
11
CT Phase B
12
CT Phase A