CONTROL PANEL ANALOG AND DIGITAL INPUTS
The panel is shipped from the factory with the
bold
print inputs pre-wired and enabled in the panel.
Inputs not in bold print need to be enabled to be used.
Analog & Digital Inputs
Input
Heading
Default
Options
Connector Pin
Analog 1
Function
None
14 Pin
13
Message
None
Digital 1
Function Auto Start
14 Pin
14
ANALOG FUNCTIONS
1)
Fuel Level S-W – Fuel amount, in percentage, can be measured and displayed on the C3
module using a standard Stewart Warner scale sender of 240 ohms – 33 ohms. 240 = Empty
and 33 = Full. Sender ground must be common with battery negative.
2)
Fuel Level VDO – Fuel amount, in percentage can be measured and displayed on the C3
module using a VDO scale sender of 10 ohms – 180 ohms. 10 = Empty and 180 = Full.
Sender ground must be common with battery negative.
3)
Oil Pressure SW 100 PSI – Oil pressure, in PSI, can be measured and displayed on the C3
module using a standard Stewart Warner scale sender of 240 ohms – 33 ohms. 240 = 0 PSI
and 33 = 100 PSI. Sender ground must be common with battery negative.
4)
Oil Pressure SW 125 PSI – Oil pressure, in PSI, can be measured and displayed on the C3
module using a standard Stewart Warner scale sender of 240 ohms – 33 ohms. 240 = 0 PSI
and 33 = 125 PSI. Sender ground must be common with battery negative.
5)
Oil Pressure SW bar – Oil pressure, in bar, can be measured and displayed on the C3 module
using a standard Stewart Warner scale sender of 240 ohms – 33 ohms. 240 = 0 bar and 33 =
7 bar. Sender ground must be common with battery negative.
6)
Oil Pressure VDO PSI – Oil pressure, in PSI, can be measured and displayed on the C3 module
using a standard VDO scale sender of 10 ohms – 180 ohms. 10 = 0 PSI and 180 = 150 PSI.
Sender ground must be common with battery negative.
7)
Oil Pressure VDO bar – Oil pressure, in bar, can be measured and displayed on the C3 module
using a standard VDO scale sender of 10 ohms – 180 ohms. 10 = 0 bar and 180 = 7 bar.
Sender ground must be common with battery negative.
8)
Switch – This setting allows for a switch to be connected rather than an analog sender. Set
Analog 1 Message to assign a label to the switch device.
9)
None – Set to None when no functionality is required.