NR9000 outputs

• 

4 TRIAC Outputs to drive 3P valves (HOT valve and COOL valve). 

Contact Rating 24-250V 4 A;

• 

3 RELAY Outputs to drive 3 speed FAN (V1, V2, V3). Contact Rat

-

ing 24..250V 8 A;

• 

2 Analogue Output 0-10V to drive proportional valves. It is possi

-

ble to use 0-10V outputs to drive a modulating FAN plus modu

-

lating valves in sequence (0-5/6-10);  

• 

2  Open  Collector  Outputs:  OC1  and  OC2.  They  have  a  max

-

imum  load  of  18mA  and  can  be  used  to  drive  12Vdc  relays 

whose  maximum  power  is  220mW  and  winding  resistance  >= 

640Ohm (ref. Controlli relay module mod. DGSRMV);

• 

OC1 output follows the ON/OFF input and it can be used, 

through an external relay, to enable electrical loads. If the 

local operation mode is enabled (through controller pass-

word) OC1 follows the input DI2 (override turn off), so if DI2 

is open, OC1 is ON too, instead if DI2 input is closed, OC1 is 

OFF too. If the local operation mode is disabled, OC1 fol-

lows the value set at 9011 ModBus address;

• 

OC2 output is used to enable auxiliary functions described 

in the “Controller functions” paragraph. If the temperature 

sensor S3 is present, the ON/OFF auxiliary loop which con-

trols OC2 will be automatically enabled; otherwise it is pos-

sible to enable the electrical coil in emergency (through 

controller password) which controls OC2. If the sensor S3 

is not present, OC2 follows the value set at 9013 ModBus 

address;

• 

1 Bus to connect remote terminal NR9000-RT;

• 

1 Bus Modbus to connect supervisor system;

• 

1 Bus Link to connect IO expansion;

• 

1  communication  connector  with  infrared  receiver  module 

NR9000-RX (through a 80cm flat cable)

Directives and Standards

Standard CEI EN 60730-1 for EMC directive.

Standard CEI EN 60730-1 and CEI EN 60730-2-9 for LVD directive.

INSTALLATION

Installation of NR9000 controller

NR9000 are suitable for mounting on a DIN rail with a quick coupling. 

Connections shall be in compliance with existing rules and using max 

2,5mm

2

 cross section wires for J1 and J2 terminals and 1,5mm

2

 cross 

section wires for J3 and J4.

To use wire terminals on power supply wires follow the instructions in 

order to prevent accidental contacts between cables at different 

voltages in case of wrong installation. 

The main power is fully isolated but we suggest to install a protection 

device compliant to existing national rules with a 125mA intervention 

threshold and a minimum 3mm contact opening. The device is not 

supplied with the product.

To use the infrared remote control (NR9000-TC) it is necessary to con-

nect NR9000 to the receiver module NR9000-RX through the cable 

supplied with the controller. 

The connection port of the receiver module is placed on the upper 

side  of  the  NR9000  controller.  The  receiver  can  be  installed  in  the 

range of the infrared remote control through the double-side tape 

supplied with the receiver. The infrared remote control NR9000TC is 

powered by 2 AAA batteries (included) and it is equipped with a 

support for wall mounting (further information on page 17).

Installation of NR9000-RT remote sensor

NR9000-RT is suitable for flush mounting in standard box 503E or for 

wall mounting on the basis of the model. The supporting frame is 

compatible  with  BTicino  cover  plates  Livinglight  (square  cover)  or 

Living International (round cover) otherwise with Vimar Plana cover 

plates modifying the supplied supporting frame as shown in the fol-

lowing figure.

Using  a  screwdiver 

press the snap and 

push down.

ACCESSORIES

NR9000 accessories

NR9000-TC   infrared remote control

NR9000-RX 

  infrared receiver module

NR9000-RT accessories

54609-02

 

BTicino LivingLight series (square cover) finishing cover 

plate;

54609-03

 

BTicino Living International series (round cover) finish

-

ing cover plate.

Note

: In case of orders for wall mounting models, back plate and 

BTicino Living International (round cover) finishing plate are in

-

cluded. 

MAINTENANCE

The controller is maintenance free.

TERMINALS

NR9000-RT terminals

NR9000 terminals

Pluggable terminals (J1 & J2) 5,08mm pitch for low voltage signals 

(230Vac) and 3,5mm pitch (J3 & J4) for very low voltage signals.

Look at the table on the next page for details.

1

st

 Issue rev. c

12/2015

DBL408e

Page 2

Содержание NR9000

Страница 1: ...elector Remote Power off or Comfort Economy digital inputs can be used to interface the controller with a Presence Detector to mini mize costs for heating and cooling When digital inputs are in use they have priority on remote sensor and supervisory system Sensors with a sensing element NTC10K Ohm 25 C Accuracy 1K β 25 C 3435 reference Controlli room sensors S4xxA B and SNTC xL Digital inputs can ...

Страница 2: ...mm2 cross section wires for J3 and J4 To use wire terminals on power supply wires follow the instructions in order to prevent accidental contacts between cables at different voltages in case of wrong installation The main power is fully isolated but we suggest to install a protection device compliant to existing national rules with a 125mA intervention threshold and a minimum 3mm contact opening T...

Страница 3: ...al 4 24Vac Comfort economy contact 36 DI_COM input digital COM COM 35 S1 input analogue input Return sensor 34 S2 input analogue input Remote set 33 S3 input analogue input Auxiliary Loop Return Sensor 32 S4 input analogue input Remote Set Auxiliary Loop 31 S_COM input COM COM 30 OCC output COM Open Collector 12V Com Open Collector 12V 29 OC1 output Open Collector 1 Open Collector for external REL...

Страница 4: ...WIRING DIAGRAMS Example of 4 pipe plant with 230V 3 point valves Example of 4 pipe plants with 230V ON OFF valves 1st Issue rev c 12 2015 DBL408e Page 4 ...

Страница 5: ...Example of 4 pipe plants with 24V 3 point valves Example of 4 pipe plant with 24V ON OFF valves 1st Issue rev c 12 2015 DBL408e Page 5 ...

Страница 6: ...Example of 2 pipe plant with 230V 3 point valves Example of 2 pipe plant with 230V ON OFF valves 1st Issue rev c 12 2015 DBL408e Page 6 ...

Страница 7: ...Example of 2 pipe plant with 24V 3 point valves Example of 2 pipe plant with 24V ON OFF valves 1st Issue rev c 12 2015 DBL408e Page 7 ...

Страница 8: ...et point and the fan speed all other parameters can be modified only through the su pervisory system or the dedicated configuration tool The controller can operate also without the Remote Sensor using a dedicated an alogue input Return Sensor The controller will consider the data acquired by the Sensor and by the Supervisory system if present and will perform a P or PI or PID regulation to drive t...

Страница 9: ... economy mode will be increased with the set correction during sum mer and decreased during winter This information can be defined through a dedicated digital input or via parameter and it can be set by the supervisory system or by a configuration tool using MODBUS protocol N B by default Summer Winter changeover is set by local mode in plants equipped with a supervisory system it has to be precon...

Страница 10: ...1 speed fan Operation Diagram 4 5 3 point Valves and 1 speed fan Operation Diagram 5 6 ON OFF Valves and Modulating FAN 0 10V Operation Dia gram 6 7a 2 pipe plant Proportional Valve 0 10V and Modulating Fan 0 10V Operation Diagram 7a 7b 4 pipe plant Sequence Valves 0 5 6 10V and Modulating Fan 0 10V Operation Diagram 7b In case of use of 3 speed fans 3 relays the 0 10V outputs are always available...

Страница 11: ... aside 4 ON OFF valves and 1 Speed FAN The valves are activated in ON OFF mode with hysteresis Speed 1 follows to the Proportion al Band as shown in the diagram aside 5 3 point valves and 1 Speed FAN The valves are activated in Pro portional mode 0 100 using a proportional band Speed 1 follows to the Proportion al Band as shown in the diagram aside 1st Issue rev c 12 2015 DBL408e Page 11 ...

Страница 12: ... the Proportion al Band as shown in the diagram aside generating a 0 10V output control signal Control modes diagrams 2 pipe plant Out AO1 Out AO2 6 No Fan 6 Yes Fan 7 Yes Hot cool valve Fan 7 No Hot cool sequence Fan Modulating valve and or fan application example 7b 0 5 6 10 V Sequence Valves and Proportional Speed Fan 0 10V 4 pipe plant The valves are activated in Pro portional mode 0 100 using...

Страница 13: ...ory Setting default address1 ON OFF OFF OFF 1 OFF ON OFF OFF 2 ON ON OFF OFF 3 OFF OFF ON OFF 4 ON OFF ON OFF 5 OFF ON ON OFF 6 ON ON ON OFF 7 OFF OFF OFF ON 8 ON OFF OFF ON 9 OFF ON OFF ON 10 ON ON OFF ON 11 OFF OFF ON ON 12 ON OFF ON ON 13 OFF ON ON ON 14 ON ON ON ON Controller used as IO expansion DIP5 DIP6 DIP7 CONFIGURATION DIAGRAM OFF OFF OFF ON OFF Valves and 3 FAN speed factory setting ON ...

Страница 14: ...on Time Hot loop 1 min 30 min 5 min Integration Time Cool loop 1 min 30 min 5 min Cut Off Function with Extra stroke of 33 0 1 1 ENABLE Summer Winter Changeover 0 1 0 WINTER Operation Mode COMFORT 0 Economy 1 Frost 2 0 2 0 COMFORT Delay Time Fan Start 0 255 0 DISABLE Delay Time Fan Stop 0 255 0 DISABLE minimum fan speed 0 50 0 DISABLE Controller Modbus Address 1 250 1 Operation Diagram 1 7 2 2 4 P...

Страница 15: ...tact Disable digital input DI1 Enable digital input DI1 0 5 Temperature Set Correction Mode 10 35 C 3K 0 6 DIP switch Enable Disable 0 7 Electrical Battery Disable Enable 0 STATUS WORD parameter NR9000 RT Value Default 0 Display Off 1 Display Only Room Temperature in page 0 2 Display Only Temperature Set in page 0 3 Display Room Temperature in page 0 with T Set Fan e Mode fixed 4 Display Room Temp...

Страница 16: ...case the controller does not allow the user to change all the function listed above and the remote terminal can show and send to controller only the room temperature It is possible to calibrate the room temperature displayed on the re mote sensor of 3 C label tAr and to read and set the MODBUS ad dress label Add of the controller connected to the sensor following these instructions press button 4 ...

Страница 17: ...s Press SELECT button to stop the set up Press ON SEND button to send information to the unit TIMER PROGRAM Start time Press SELECT button twice the word PROGRAM and the word START lighting will be displayed Press or button the word START will become fix and the hours value will start lighting Use button to increase or to decrease the hours Press SELECT button the minutes value will light Use butt...

Страница 18: ... connected to NR9000 controller and a double side tape for fixing on smooth surfaces In case the flat cable is not connected to the receiver proceed as follows 1 unscrew the two screws on the receiver to open the back cov er a 6 terminal connector will be visible 2 insert one end of the cable inside the connector The connector can be mounted in one direction only as it is polarized 3 close again t...