APPLICATION AND USE
NR9000 is a digital controller for 2- or 4-pipe terminal units (eg. Fan
Coil) with ON/OFF, 3-POINT floating or modulating control valves as
well as with 3-speed or modulating fan. NR9000 is equipped with
MODBUS (SLAVE) communication protocol enabling the communi-
cation with other MODBUS devices (MASTER).
NR9000 is composed by a M6 DIN rail unit and a remote terminal
(NR9000-RT) with integrated room terminal sensor. It is possible to use
the NR9000-TC remote control (optional) to set a daily switching on
and switching off; time table control can be carried out through the
supervisory system too.
NR9000-RT is the remote terminal which can be connected to the
controller (further details on page 16).
NR9000 can be connected to a receiver module (NR9000-RX, techni
-
cal characteristics on page 18) and controlled by a infrared remote
control (NR9000-TC, technical characteristics on page 17).
TECHNICAL CHARACTERISTICS
Power supply NR9000:
85-265Vac (isolated);
Power supply NR9000-RT:
12Vdc (from controller);
Protection Degree:
IP 20;
Operation temperature:
2T45°C;
Storage temperature:
-25T65°C;
Dimensions [mm]:
see page 18.
NR9000 controller inputs
•
Digital Input (DI1)
Window Contact
•
Digital Input (DI2)
Remote Power off *
•
Digital Input (DI3)
Winter/Summer Change Over
•
Digital Input (DI4)
Comfort/Economy *
•
Analogue Input (S1) Return Temperature Sensor **
•
Analogue Input (S2) Remote Temperature Set **
•
Analogue Input (S3) Auxiliary loop sensor
•
Analogue Input (S4) Auxiliary loop set selector
*”Remote Power off” or “Comfort/Economy” digital inputs can be
used to interface the controller with a Presence Detector to mini-
mize costs for heating and cooling.
When digital inputs are in use they have priority on remote sensor
and supervisory system.
** Sensors with a sensing element NTC10K Ohm @ 25°C.
Accuracy ± 1K, β @ 25°C = 3435
(reference Controlli room sensors S4xxA/B and SNTC-xL)
Digital inputs can be enabled using a configuration tool called
“Configuratore NR9000” thanks to which you can also reverse the in
-
puts action. It can be downloaded by our web site www.controlli.eu.
The default status of digital inputs (factory setting) is the following:
DIGITAL INPUT
DEFAULT
DESCRIPTION
WINDOW
CONTACT***
N.C (normally
closed)
OPEN – window opened
CLOSED – window
closed
REMOTE POWER
OFF
N.O (normally
open)
OPEN – Comfort/
economy
CLOSED – off
WINTER/SUMMER
CHANGEOVER***
N.O (normally
open)
OPEN – winter
CLOSED – summer
COMFORT/
ECONOMY***
N.O (normally
open)
OPEN – Comfort
CLOSED – economy
***
These inputs are disabled by default because of the controller status word
(look at table page 15). If you need to enable them a supervisory system
is required.
For example, in case the window switch is normally opened (closed
window is equivalent to open contact), it is necessary to reverse the
action of the digital input.
NR9000/NR9000-RT
Energon
Fan Coil Digital Controller
Code
Description
NR9000
Fan coil digital controller
NR9000-RT1A Flush-mounting remote sensor charcoal colour
NR9000-RT1B Flush-mounting remote sensor white colour
NR9000-RT2A Wall mounting remote sensor charcoal colour
NR9000-RT2B Wall mounting remote sensor charcoal colour
NR9000-RX
NR9000
NR9000-RT
N.B.: NR9000-TC and NR9000-RX