1
st
Issue 10/00 13
DMP025E
DEFAULT DATA AND RELATED MODIFICATION RANGES
Description
Range
Pre-program.
value
NR. of controllers.
1...160
100
Existing groups
1...4
1
Single controllers
0...160
0
RC/RF cooling qualification
Yes/No
No
Set point in NM mode
11...29°C
21°C
Dead zone
0...6k
3K
C channel actuator stroke
0...100%
34%
F channel actuator stroke
0...100%
34%
Control type
P / P+I
P
C channel proportional band
0,8.... 7,2
4.0°C
F channel proportional band
0,8.... 7,2
4.0°C
C channel integration time
1... 30
5 S.
F channel integration time
1... 30
5 S.
Summer comp. start point
20...35°C
27°C
Authority comp.
0...99%
40%
Winter comp. start point
0...20°C
5°C
Authority compensation
0...99%
60%
There are four default time schedules :
Schedule 1
Schedule 2
Schedule 3
Schedule 4
time
mode
time
mode
time
mode
time
mode
7:30
NM
6:00
NM
6:00
RC
7:00
NM
12:30
RC
12:00
RC
7:30
NM
12.00
RC
14:00
NM
13:00
NM
12:00
RC
13:00
RF
17:00
RC
17:00
RC
13:30
NM
19:00
AF
21:00
RF
17:30
RC
----
----
19:00
AF
Minimum interval 10 minutes: resolution 10 minutes.