DIP SWITCHES SETTINGS

Set  the  DIP  switches  according  to  the  tables  here  below.  Power 

down and power up again the actuator or act on the manual over

-

ride to be sure that settings will be recognized.

DIP 

switch

OFF

ON

1

Direct Action

Reverse Action

2

Modulating Control (MOD) (Input between Y [+] and M [-])

3 point floating (INC) ( Y1 open-extend , Y2 close-retract 

connected L1 or Ln if powered in Vac; if powered in Vdc 

connected necessarily to Ln )

3

-

Selection of sequence mode, control range defined by DIP n. 5

4

Modulating Control 0-10Vdc

 

(DIP n. 2 OFF only)

Modulating Control 2-10Vdc

 

(DIP n. 2 OFF only)

5

Sequence Control 0-5Vdc with DIP n. 4 OFF only

 

Sequence Control 2-6Vdc with DIP n. 4 ON only

 

(DIP n. 3 ON only)

Sequence Control 5-10Vdc with DIP n. 4 OFF only

 

Sequence Control 6-10Vdc with DIP n. 4 ON only

 

(DIP n. 3 ON only)

6

Voltage Input Signal

 

(input between Y [+] and M [-])

Current Input Signal 4-20mA (input between Y [+] and M [-]). 

In this case DIP n. 4 must be set to ON.

7

Automatic Calibration: the actuator updates the stroke 

range every time an unexpected mechanical stop is 

detected for at least 10s

Manual Calibration: the actuator calibration is started moving 

the DIP from OFF to ON or vice versa. With DIP in ON in case 

of extra stroke or if an unexpected endpoint is detected, the 

actuator will never update the stroke 

U=10V

Y1

Y2

U = 10V

U = 2V

U= feedback

U= feedback

U = 2V

Factory settings

1

st

 Issue rev. b

04/2018

DBL564e

Page 5

Содержание MVE5-65 Series

Страница 1: ...peration handle on the actuator When it is low ered manual override ON the power supply to the motor power stage circuitry is cut and the motor stops The actuator can be oper ated manually and the val...

Страница 2: ...Modulating 5 15mm 15s Modulating 15 25mm 20s Modulating 25 60mm 30s Floating 60s Transformer Size VA 20 20 30 50 Stroke 5 60mm limited to 30mm for MVE5xxS 65 Force N 400 600 1000 1500 Duty cycle max 5...

Страница 3: ...el To guarantee Nema Type 2 protection use flexible metal conduit not supplied Push the listed conduit fitting device over the actuator s cable to butt against the enclosure Screw in conduit connector...

Страница 4: ...electronic components caused by the PCB bending do not press too much while fixing the terminal block WIRING DIAGRAMS 3 point floating control sink connection Controller 3 point floating control sink...

Страница 5: ...rol 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc with DIP n 4 ON only DIP n 3 ON on...

Страница 6: ...tial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and pow...

Страница 7: ...tor arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is...

Отзывы: