DIP SWITCHES SETTINGS
Set the DIP switches according to the tables here below. Power
down and power up again the actuator or act on the manual over
-
ride to be sure that settings will be recognized.
DIP
switch
OFF
ON
1
Direct Action
Reverse Action
2
Modulating Control (MOD) (Input between Y [+] and M [-])
3 point floating (INC) ( Y1 open-extend , Y2 close-retract
connected L1 or Ln if powered in Vac; if powered in Vdc
connected necessarily to Ln )
3
-
Selection of sequence mode, control range defined by DIP n. 5
4
Modulating Control 0-10Vdc
(DIP n. 2 OFF only)
Modulating Control 2-10Vdc
(DIP n. 2 OFF only)
5
Sequence Control 0-5Vdc with DIP n. 4 OFF only
Sequence Control 2-6Vdc with DIP n. 4 ON only
(DIP n. 3 ON only)
Sequence Control 5-10Vdc with DIP n. 4 OFF only
Sequence Control 6-10Vdc with DIP n. 4 ON only
(DIP n. 3 ON only)
6
Voltage Input Signal
(input between Y [+] and M [-])
Current Input Signal 4-20mA (input between Y [+] and M [-]).
In this case DIP n. 4 must be set to ON.
7
Automatic Calibration: the actuator updates the stroke
range every time an unexpected mechanical stop is
detected for at least 10s
Manual Calibration: the actuator calibration is started moving
the DIP from OFF to ON or vice versa. With DIP in ON in case
of extra stroke or if an unexpected endpoint is detected, the
actuator will never update the stroke
U=10V
Y1
Y2
U = 10V
U = 2V
U= feedback
U= feedback
U = 2V
Factory settings
1
st
Issue rev. b
04/2018
DBL564e