Controlli MVE5-65 Series Скачать руководство пользователя страница 3

Linkage

MVE5xx-65

MVE5xxS-65

Current Controlli valves 

 

(except for 2TGB.F/3TGB.F PN16) (not required)

/

VSXT09PBP, VSXT10PBP ***

2TGB.F/3TGB.F PN16

/

(not required)

Controlli valves with threaded 

M40 connections

 

(except for VSB/VMB/VSBF/

VMBF PN16)

AG51

/

VSB/VMB/ VSBF/VMBF PN16

AG52

AG63

Other manufacturers

Landis *

AG70-10 

 

AG70-14

/

Danfoss (VR/VF (S) models)

AG60-07

/

TAC DN15-V298

AG 60-08

/

TAC DN15-V2XX/V3XX

AG 60-09

/

Honeywell**

AG 60-10

/

Airtek

AG 60-11/

AG60-12

/

Johnson Controls code VB7816-

2111

AG 66

/

Johnson Controls code BM-

3018-3300

AG 67

/

Tac Venta

(not required)

/

(/) this model can not be assembled
(*) AG70-10 for valves having stem Ø 10mm

 

     AG70-14 for valves having stem Ø 14mm
(**) valid for the following models: M6: V176A. B, V538C

1/4”: V5011A
(***) assembled only with MVE504S-65 actuator

ELECTRIC CONNECTIONS

Remove the cover screw with a screwdriver and then remove the 

cover as shown in the picture beside.

The actuator is equipped with a 8 poles removable terminal block; 

the each pole of the plug is clearly marked and the same label are 

reported on the electronic board. Before powering up the actuator 

make sure the plug is properly connected to the board and the label 

on the plugs and on the board match.

 

Use cable gland IP65 PG13,5 model.

* To guarantee “Nema Type 2” protection:

• 

use flexible metal conduit (not supplied);

• 

Push the listed conduit fitting device over the actuator’s cable 

to butt against the enclosure. Screw in conduit connector. Jack

-

et the actuators input wiring with listed flexible conduit. Properly 

terminate the conduit in a suitable junction box.

ASSEMBLING

The actuator can be mounted with any orientation but never up-side 

down. When the fluid temperature exceed 120°C the actuator shall 

be mounted leaning 45°.

T fluid ≥ 120°C

T fluid MAX 120°C

T fluid ≥ 120°C

To mount the actuator on to a valve, position the valve stem to the 

bottom of its travel, slide the actuator onto the valve neck, adjusting 

with the manual override the screw jack position so the square nut 

on the valve spindle fits into the groove on the cross bar. Then slide 

the brace into the groove on the valve neck and secure the nuts.

See mounting instructions for full details (MVE_DIM223).

MAINTENANCE

The actuator is free of maintenance.

ACCESSORIES

DMVE

  

End point auxiliary switches (electrical rate 24V AC/DC, 

4A max)

248

 

Stem heater (suggested when the fluid temperature is be

-

low 0°C) *

GMVE

 

Thermal insulation for MVE actuators *

GMVE.S

  Thermal insulation for MVE.S actuators *

89404-05 

PG13.5 cable gland for cables with Ø variable between 6 

and 12 mm

It is not possible to install both thermal insulation (Gxxxx) and stem 

heaters.

1

st

 Issue rev. b

04/2018

DBL564e

Page 3

Содержание MVE5-65 Series

Страница 1: ...peration handle on the actuator When it is low ered manual override ON the power supply to the motor power stage circuitry is cut and the motor stops The actuator can be oper ated manually and the val...

Страница 2: ...Modulating 5 15mm 15s Modulating 15 25mm 20s Modulating 25 60mm 30s Floating 60s Transformer Size VA 20 20 30 50 Stroke 5 60mm limited to 30mm for MVE5xxS 65 Force N 400 600 1000 1500 Duty cycle max 5...

Страница 3: ...el To guarantee Nema Type 2 protection use flexible metal conduit not supplied Push the listed conduit fitting device over the actuator s cable to butt against the enclosure Screw in conduit connector...

Страница 4: ...electronic components caused by the PCB bending do not press too much while fixing the terminal block WIRING DIAGRAMS 3 point floating control sink connection Controller 3 point floating control sink...

Страница 5: ...rol 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc with DIP n 4 ON only DIP n 3 ON on...

Страница 6: ...tial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and pow...

Страница 7: ...tor arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is...

Отзывы: