Controlli MVE5-65 Series Скачать руководство пользователя страница 1

Controlli S.p.A.

16010 Sant’Olcese (GE)

Tel. 010 73 06 1

Fax. 010 73 06 870/871

www.controlli.eu

MVE5xx-65

IP65 Globe Valves Actuators

APPLICATION AND USE

MVE5xx-65 is a flexible electro mechanical actuator for the control 

of two and three-way globe valves in:

• 

heating and cooling systems;

• 

Air Handling Units;

• 

district heating plants;

• 

industrial temperature control systems.

The actuator can be controlled either by a proportional (modulat

-

ing) signal or by an increase/decrease (Floating) signal.

It is easy to mount and connect the actuator. Direct mounting is pos

-

sible to any CONTROLLI flanged valve. Linkage kits are available for 

CONTROLLI threaded valves as well as for valves of other manufac

-

turers (table p. 3). The actuator has a fine resolution (500 steps on the 

full stroke range) for exacting fluid control and it is able to self-cali

-

brate on a different stroke without the need of any user action (this 

function is DIP switch selectable on the field). 

MVE5xx-65 has intelligent behaviour and alarm functionality in case 

of unexpected operation, feedback of alarms to the user is provided 

by LEDs (GREEN and RED) on the control board.

N.B.: Do not use the actuator if not coupled with its relating valve.

MVE5xx-65 is suitable for harsh environment requiring IP65 protection 

degree.

OPERATION

The  actuator  translates  the  control  signal  (modulating  or  3  point 

floating) from the controller into a valve position. A modern brushless 

DC motor in the actuator drive a gear train and a worm gear – screw 

jack  mechanism  convert  the  motor  revolutions  into  accurate  and 

repeatable linear movements.

Control Signal

MVE5xx-65 can be controlled by one of 2 main control types:

• 

3 point floating ;

• 

Modulating (or proportional) signal with filed selectable 

range (e.g., 0-10Vdc, 2-10Vdc, 0-5/2-6Vdc, 5-10/6-10Vdc and 

4-20mA).

Manual Override

There is a manual operation handle on the actuator. When it is low

-

ered (manual override ON), the power supply to the motor power 

stage circuitry is cut and the motor stops. The actuator can be oper

-

ated manually and the valve positioned accordingly.

The manual override lever stays in position until it is raised again, then 

board and motor will be powered again. At the end of this operation 

the actuator moves to initial position (on the basis of DIP n. 1 setting) 

then  it  follows  the  control  signal.  When  the  manual  override  is  en

-

gaged the GREEN and the RED LED are ON.

Manual operation handle can also be used to modify any DIP switch 

setting or as re-set function after any alarm occurrence.

The actuator is supplied with the manual override lowered (ON). It 

is not necessary to remove power supply to modify DIP switches set

-

ting.

Position Feedback

The actuator utilizes a 2-10Vdc position feedback (look at DIP n. 1 

setting).

Calibration

The actuator has both auto and manual stroke calibration, DIP n. 7. 

In factory delivery the auto stroke calibration is enabled – manual 

calibration is not necessary unless maintenance is required on the 

valve or certain alarm functions are desired.

End Point Auxiliary Switches (with accessory DMVE)

End  point  switches  change  over  when  the  valve  is  fully  open  or 

closed. They are free contacts with 24V AC/DC, 4A max voltage on 

terminals. End point switches can be utilized to indicate valve stroke 

end  positions  and  for  relay  control  of  additional  plant  equipment.  

When the actuators are controlled individually or in sequence, it is 

possible  to  use  the  end  switches  to  toggle  when  the  valve  is  fully 

open or fully closed. The auxiliary switch position according to con

-

trol signal (Y) is shown in the picture below.

MODEL

FORCE 

[N]

POWER 

SUPPLY

DESCRIPTION

MVE504-65 

400

24Vac/dc

long yoke, modulating/

floating control, IP65

MVE506-65 

600

MVE510-65 

1000

MVE515-65

1500

MVE504S-65 

400

24Vac/dc

short yoke, modulating/

floating control, IP65

MVE506S-65 

600

MVE510S-65 

1000

MVE515S-65

1500

1

st

 Issue rev. b

04/2018

DBL564e

Page 1

Содержание MVE5-65 Series

Страница 1: ...peration handle on the actuator When it is low ered manual override ON the power supply to the motor power stage circuitry is cut and the motor stops The actuator can be oper ated manually and the val...

Страница 2: ...Modulating 5 15mm 15s Modulating 15 25mm 20s Modulating 25 60mm 30s Floating 60s Transformer Size VA 20 20 30 50 Stroke 5 60mm limited to 30mm for MVE5xxS 65 Force N 400 600 1000 1500 Duty cycle max 5...

Страница 3: ...el To guarantee Nema Type 2 protection use flexible metal conduit not supplied Push the listed conduit fitting device over the actuator s cable to butt against the enclosure Screw in conduit connector...

Страница 4: ...electronic components caused by the PCB bending do not press too much while fixing the terminal block WIRING DIAGRAMS 3 point floating control sink connection Controller 3 point floating control sink...

Страница 5: ...rol 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc with DIP n 4 ON only DIP n 3 ON on...

Страница 6: ...tial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and pow...

Страница 7: ...tor arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is...

Отзывы: