DIP 5-7
DIP 5-7
DIP 8
DIP 8
DIP 8
Impianto
OFF
2 tubi
ON
4 tubi
DIP 8
SYSTEM
OFF
2 pipes
ON
4 pipes
FUNZIONALITA’ LED
LED FUNCTIONALITY
N.B.: Il manuale relativo al regolatore e lo strumento di configurazione “Configuratore NR9000” possono essere scaricati dal nostro sito www.
controlli.eu
N.B.: The User Manual relating to the controller and the configuration tool “Configuratore NR9000” can be downloaded by our web site www.
controlli.eu.
ESEMPIO DI UTILIZZO VALVOLE MODULANTI E/O VENTILATORE
EXAMPLE OF USE OF MODULATING VALVE AND/OR FAN
DIAGRAMMA DI
FUNZIONAMENTO
IMPIANTO 2
TUBI
USCITA AO1
USCITA AO2
6
NO
---
VENTILATORE
6
SI
---
VENTILATORE
7
NO
SEQUENZA
CALDO/FREDDO
VENTILATORE
7
SI
VALVOLA
CALDO/FREDDO
VENTILATORE
CONTROL MODES
DIAGRAMS
2-PIPE PLANT
AO1 OUTPUT
AO2 OUTPUT
6
NO
---
FAN
6
SI
---
FAN
7
NO
HEATING/COO-
LING SEQUENCE
FAN
7
SI
HEATING/COO-
LING VALVE
FAN
DIP5 DIP6 DIP7
Diagramma di configurazione
OFF OFF OFF
Valvole ON/OFF e ventilatore a 3 velocità
(impostazione di fabbrica)
ON
OFF OFF
Valvole ON/OFF e ventilatore a 3 velocità
“FAST” (Diagramma di funzionamento 1)
OFF
ON
OFF
Valvole ON/OFF e ventilatore a 3 velocità
(Diagramma di funzionamento 2)
ON
ON
OFF
Valvole 3-punti e ventilatore a 3 velocità
(Diagramma di funzionamento 3)
OFF OFF
ON
Valvole ON/OFF e velocit à ventilatore 1
(Diagramma di funzionamento 4)
ON
OFF
ON
Valvole 3 punti e velocità ventilatore 1
(Diagramma di funzionamento 5)
OFF
ON
ON
Valvole ON/OFF e ventilatore modulante (0 –
10 V) (Diagramma di funzionamento 6)
ON
ON
ON
Valvole in sequenza 0-5/6-10 e ventilatore
modulante (0 – 10 V) (Diagramma di
funzionamento 7)
DIP5 DIP6 DIP7
CONFIGURATION DIAGRAM
OFF
OFF
OFF
ON/OFF Valves and 3 FAN speed (factory
setting)
ON
OFF
OFF
ON/OFF Valves and 3 FAN speed “FAST”
(Operating Diagram 1)
OFF
ON
OFF ON/OFF Valves and 3 FAN speed (Operating
Diagram 2)
ON
ON
OFF
3-point Valves and 3 FAN speed (Operating
Diagram 3)
OFF
OFF
ON
ON/OFF Valves and 1 FAN speed (Operating
Diagram 4)
ON
OFF
ON
3-point Valves and 1 FAN speed (Operating
Diagram 5)
OFF
ON
ON
ON/OFF Valves and Modulating FAN (0 – 10
V) (Operating Diagram 6)
ON
ON
ON
0-5/6-10 Sequence Valves and Modulating
FAN (0 – 10 V). (Operating Diagram 7)
LED ROSSO/RED LED
LED VERDE/GREEN LED
LAMPEGGIO/BLINKING RATE
DESCRIZIONE/DESCRIPTION
LAMPEGGIANTE
BLINKING
OFF
1Hz – DUTY CYCLE 50%
VALVOLA CALDO APERTA/HEATING VALVE OPEN
OFF
LAMPEGGIANTE
BLINKING
1Hz - DUTY CYCLE 50%
VALVOLA FREDDO APERTA/COOLING VALVE OPEN
LAMPEGGIANTE
BLINKING
LAMPEGGIANTE
BLINKING
1Hz – DUTY CYCLE 10%
VALVOLE CALDO E FREDDO CHIUSE/HEATING AND COOLING VALVE CLOSED
ON
ON
NA
COMUNICAZIONE CON SONDA REMOTA FALLITA/COMMUNICATION WITH
REMOTE SENSOR FAILED
ON
LAMPEGGIANTE
BLINKING
2 Hz – DUTY CYCLE 50%
ERRORE SONDA LOCALE/LOCAL SENSOR ERROR
1
a
Emissione / 1
st
Issue rev. e
03/2020
3
DIM228