background image

DIP 5-7

DIP 5-7

DIP 8

DIP 8

DIP 8

Impianto

OFF

2 tubi

ON

4 tubi

DIP 8

SYSTEM

OFF

2 pipes

ON

4 pipes

FUNZIONALITA’ LED 

LED FUNCTIONALITY

N.B.: Il manuale relativo al regolatore e lo strumento di configurazione “Configuratore NR9000” possono essere scaricati dal nostro sito www.

controlli.eu

N.B.: The User Manual relating to the controller and the configuration tool “Configuratore NR9000” can be downloaded by our web site www.

controlli.eu.

ESEMPIO DI UTILIZZO VALVOLE MODULANTI E/O VENTILATORE

EXAMPLE OF USE OF MODULATING VALVE AND/OR FAN

DIAGRAMMA DI 

FUNZIONAMENTO

IMPIANTO 2 

TUBI

USCITA AO1

USCITA AO2

6

NO

---

VENTILATORE

6

SI

---

VENTILATORE

7

NO

SEQUENZA 

CALDO/FREDDO

VENTILATORE

7

SI

VALVOLA 

CALDO/FREDDO

VENTILATORE

CONTROL MODES 

DIAGRAMS

2-PIPE PLANT

AO1 OUTPUT

AO2 OUTPUT

6

NO

---

FAN

6

SI

---

FAN

7

NO

HEATING/COO-

LING SEQUENCE

FAN

7

SI

HEATING/COO-

LING VALVE

FAN

DIP5 DIP6 DIP7

Diagramma di configurazione

OFF OFF OFF

Valvole ON/OFF e ventilatore a 3 velocità 

(impostazione di fabbrica)

ON

OFF OFF

Valvole ON/OFF e ventilatore a 3 velocità 

“FAST” (Diagramma di funzionamento 1)

OFF

ON

OFF

Valvole ON/OFF e ventilatore a 3 velocità 

(Diagramma di funzionamento 2)

ON

ON

OFF

Valvole 3-punti e ventilatore a 3 velocità 

(Diagramma di funzionamento 3)

OFF OFF

ON

Valvole ON/OFF e velocit à ventilatore 1 

(Diagramma di funzionamento 4)

ON

OFF

ON

Valvole 3 punti e velocità ventilatore 1 

(Diagramma di funzionamento 5)

OFF

ON

ON

Valvole ON/OFF e ventilatore modulante (0 – 

10 V) (Diagramma di funzionamento 6)

ON

ON

ON

Valvole in sequenza 0-5/6-10  e ventilatore 

modulante (0 – 10 V) (Diagramma di 

funzionamento 7)

DIP5 DIP6 DIP7

CONFIGURATION DIAGRAM

OFF

OFF

OFF

ON/OFF Valves and 3 FAN speed (factory 

setting)

ON

OFF

OFF

ON/OFF Valves and 3 FAN speed “FAST” 

(Operating Diagram 1)

OFF

ON

OFF ON/OFF Valves and 3 FAN speed (Operating 

Diagram 2)

ON

ON

OFF

3-point Valves and 3 FAN speed (Operating 

Diagram 3)

OFF

OFF

ON

ON/OFF Valves and 1 FAN speed (Operating 

Diagram 4)

ON

OFF

ON

3-point Valves and 1 FAN speed (Operating 

Diagram 5)

OFF

ON

ON

ON/OFF Valves and Modulating FAN (0 – 10 

V) (Operating Diagram 6)

ON

ON

ON

0-5/6-10 Sequence Valves and Modulating 

FAN (0 – 10 V). (Operating Diagram 7)

LED ROSSO/RED LED

LED VERDE/GREEN LED

LAMPEGGIO/BLINKING RATE

DESCRIZIONE/DESCRIPTION

LAMPEGGIANTE

BLINKING

OFF

1Hz – DUTY CYCLE 50%

VALVOLA CALDO APERTA/HEATING VALVE OPEN

OFF

LAMPEGGIANTE

BLINKING

1Hz - DUTY CYCLE 50%

VALVOLA FREDDO APERTA/COOLING VALVE OPEN

LAMPEGGIANTE

BLINKING

LAMPEGGIANTE

BLINKING

1Hz – DUTY CYCLE 10%

VALVOLE CALDO E FREDDO CHIUSE/HEATING AND COOLING VALVE CLOSED

ON

ON

NA

COMUNICAZIONE CON SONDA REMOTA FALLITA/COMMUNICATION WITH 

REMOTE SENSOR FAILED

ON

LAMPEGGIANTE

BLINKING

2 Hz – DUTY CYCLE 50%

ERRORE SONDA LOCALE/LOCAL SENSOR ERROR

1

a

 Emissione / 1

st

 Issue rev. e

03/2020

3

DIM228

Содержание Energon

Страница 1: ...ando ad infrarossi NR9000 TC TERMINAL BOARD MORSETTIERA MONTAGGIO MOUNTING NR9000 needs to be mouted on a DIN bar M6 Il regolatore NR9000 deve essere montato su barra DIN M6 NR9000 CONN pin Segnale Si...

Страница 2: ...gue output 1 Valvola caldo modulante 1 sequenza Modulating heating valve 1 sequence 25 AOC output COM COM Shield 24 485 Bidir BUS RS485 Bus supervisore supervisor Bus 23 485 Bidir BUS RS485 Bus superv...

Страница 3: ...entilatore 1 Diagramma di funzionamento 4 ON OFF ON Valvole 3 punti e velocit ventilatore 1 Diagramma di funzionamento 5 OFF ON ON Valvole ON OFF e ventilatore modulante 0 10 V Diagramma di funzioname...

Страница 4: ...OFF a 230V Example of 4 pipe plant with 230V 3 point valves Example of 4 pipe plants with 230V ON OFF valves Oppure Limite minima Fan Or fan min limit Oppure Or Changeover Auto Oppure ingresso Badge O...

Страница 5: ...of 4 pipe plants with 24V 3 point valves Example of 4 pipe plant with 24V ON OFF valves Oppure Limite minima Fan Or fan min limit Oppure Or Changeover Auto Oppure ingresso Badge Oppure Limite minima F...

Страница 6: ...of 2 pipe plant with 230V 3 point valves Example of 2 pipe plant with 230V ON OFF valves Oppure Limite minima Fan Or fan min limit Oppure Or Changeover Auto Oppure ingresso Badge Oppure Limite minima...

Страница 7: ...impianto 2 tubi con valvole ON OFF a 24V Example of 2 pipe plant with 24V ON OFF valves Oppure Limite minima Fan Or fan min limit Oppure Or Changeover Auto Oppure ingresso Badge Oppure Limite minima F...

Страница 8: ...esauste attendere 10 minuti prima di installare quelle nuo ve NR9000 TC INFRARED REMOTE CONTROL MOUNTING INSTRUCTIONS NR9000 TC infrared remote control is supplied together with a sup port for wall m...

Страница 9: ...ulo ricevitore seguire unicamente le istruzioni riportate ai punti 5 e 6 NR9000 RX INFRARED RECEIVER MODULE MOUNTING INSTRUCTIONS The receiver module is supplied together with a flat connector 80cm to...

Отзывы: