The existing actuator is 
cabled directly inside the 
actuator, and not with a 
junction box

The existing actuator is 
not a 0-10V / 24V, but 
have a different power 
supply or signal

The LED stays off even if 
the power button is 
pressed

ISSUE / QUESTION

This is a common option for certain models of 
actuators. In this case, steps 1, 2 and 3 can be 
done directly inside the case of the actuator.

Please contact 

Controlli

 and order the right eNode!

You are using the wrong Enerbrain eNode model, as 
this is ONLY for 0-10V signal and 24V power supply.

The eNode is studied to resist most weather 
conditions, but still it is very important to install it in 
a safe area, protected from water, snow, rain and 
direct sunlight.
If impossible to find a good location near the 
existing actuator, you can install the eNode 
extending the cables up to 3mt or install it directly 
in the Electrical Box where the switches and BMS 
cables are located. However it is preferrable to 
install the eNode near the actuator to be controlled.

Double check the following:
- Is there power from the electric cables 24V?
- Is the eNode cabled correctly?
- Is the button firmly pressed in the ON position?

If this is the case, and the eNode LED light is still 
off, please follow the steps:
- Turn off the eNode by pressing the button
- Turn ON the eNode by pressing the button again
- Wait for approximately 3 minutes.

If still the LED is off please contact 

Controlli

 

Support.

SOLUTION

FAQ - FREQUENT ASKED QUESTIONS