Under normal circumstances, no maintenance should be required. If clean dry air is not used the orifice can 
become blocked. To clean, first turn off supply air, unscrew and remove orifice assembly (large silver screw 
head located above the out port). Then  unplug orifice by using a wire that has a smaller diameter than 0.015 in. 
(0.38 mm). Use compressed air to blow out any loose particles inside the orifice assembly. Screw orifice 
assembly back into unit. 

 

 

 

 

PROBLEM 

CHECK 

No or low output 

Zero adjustment * 
Clogged orifice 
Supply pressure too low 

Leakage 

Connections 

Low or improper span 

Zero and Span adjustments 
Supply pressure too low 
Output leakage 

Erratic operation 

Electrical input signal 
Loose wires or connections 
Liquid in air supply 

 

 

   

 

  *most common

 

 

 

 

If problems are not solved by troubleshooting 
procedures, contact a factory application’s 
engineer at (603) 886-9400 for further assistance. 

 

 

 

 

 

 
ControlAir LLC products are warranted to be free from defects in materials and workmanship for a period of eighteen 
months from the date of sale, provided said products are used according to ControlAir LLC recommended usages.  
ControlAir LLC’s liability is limited to the repair, purchase price refund, or replacement in kind, at ControlAir, Inc.’s 
sole option, of any products proved defective.  ControlAir LLC reserves the right to discontinue manufacture of any 
products or change products materials, designs or specifications without notice.  Note: ControlAir does not assume 
responsibility for the selection, use, or maintenance of any product.  Responsibility for the proper selection, use, and 
maintenance of any ControlAir product remains solely with the purchaser and end user. 

These products are intended for use in industrial compressed-air systems only.  Do not use these 
products where pressures and temperatures can exceed those listed under Specifications. 

Before using these products with fluids other than air, for non-industrial applications, life-support systems, or other 
applications not within published specifications, consult ControlAir LLC.

 

4. MAINTENANCE  

5. TROUBLESHOOTING 

NOTE 

6. WARRANTY & DISCLAIMER 

WARNING 

Содержание 500X

Страница 1: ...allation 3 3 0 Operation 4 4 0 Maintenance 6 5 0 Troubleshooting 6 6 0 Warranty 6 Type 500X Electro Pneumatic Transducer I P E P Installation Operation and Maintenance Instructions 8 Columbia Drive Amherst New Hampshire 03031 USA Phone 603 886 9400 Fax 603 889 1844 sales controlair com www controlair com ...

Страница 2: ... at 10 psig 0 7 bar above 20 psig 1 3 bar setpoint Impedance 4 20 mA 90 Ohms 4 20 mA 90 Ohms 4 20 mA 180 Ohms 0 5 VDC 615 Ohms 1 9 VDC 985 Ohms 4 20 mA 220 Ohms 0 5 VDC 530 Ohms 1 9 VDC 840 Ohms 4 20 mA 220 Ohms 0 5 VDC 530 Ohms 1 9 VDC 840 Ohms 4 20 mA 250 Ohms 4 20 mA 225 Ohms 0 5 VDC 500 Ohms 4 20 mA 260 Ohms 0 10 VDC 805 Ohms Performance Specifications Terminal Based Linearity 0 75 of span 1 5...

Страница 3: ...through the coil 2 3 Mounting 2 3 1 Unit may be pipe panel or bracket mounted Mounting may be at any angle though may require field adjustment High external vibration may cause output fluctuations Mounting in a vibration free area is recommended 2 4 Pneumatic Connections 2 4 1 The 1 4 NPT 1 4 BSP option supply and output ports are marked IN and OUT respectively on the base of the unit Clean all pi...

Страница 4: ...w counterclockwise for up to 30 revolutions until output pressure rises 5 Increase electrical input signal to its maximum value e g 20 mA for a 4 20 mA unit 6 Observe the output pressure If necessary adjust the span screw until reaching maximum output pressure setting For I P current input models turn span screw counterclockwise to increase pressure clockwise to decrease pressure For E P voltage i...

Страница 5: ...SURES FOR ELECTRICAL EQUIPMENT 1000 VOLTS MAX NOTES 1 INSTALLATION TO BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE NFPA 70 ARTICLE 504 AND ANSI ISA RP 12 6 2 APPARATUS CONNECTED TO THE SYSTEM SHALL NOT USE OR GENERATE VOLTAGE GREATER THAN 250 V 3 INSTALL INTRINSICALLY SAFE BARRIERS IN ACCORDANCE WITH BARRIER INSTRUCTIONS 4 FM APPROVALS APPROVED AS INTRINSICALLY SAFE FOR CLASS I II AND III DIV ...

Страница 6: ...o be free from defects in materials and workmanship for a period of eighteen months from the date of sale provided said products are used according to ControlAir LLC recommended usages ControlAir LLC s liability is limited to the repair purchase price refund or replacement in kind at ControlAir Inc s sole option of any products proved defective ControlAir LLC reserves the right to discontinue manu...

Отзывы: