Operation
For automatic operation of the back-up
DC
supply, this supply should be
connected continuously.
The following table shows the results of a combination of supply conditions.
A 400V
AC
supply is considered to be removed when it is below
approximately 230V
RMS
.
AC
supply Back-up
DC
supply
Resulting effect
Present Present or
absent
Control circuits and power stages operate
(Drive fully operational, including the precision analog input)
Absent Present If the
AC
supply is present, then removed, parameters that are saved
at power-down are saved
Only the control circuits operate
The Drive cannot power a motor
The Drive displays
LOPS
The Drive can be programmed either manually or via
serial communications, but parameter values cannot be saved
Model sizes 1 and 2: Heatsink fan operates
Model sizes 3 and 4: Heatsink fans do not operate
Power-up delays
The following delays occur:
AC
supply disconnected
Back-up
DC
supply
being
connected
5 second delay for Drive display and serial
communications to become active
Back-up
DC
supply
already
connected
AC
supply
being
connected
5 second delay before the Drive can be
enabled
Note
Stator resistance test (open-loop only)
If parameter
5.14
(
0.07
) is set at
Ur_I
for the Drive to perform a stator
resistance test at power-up, and the
AC
supply is disconnected, the Drive
will trip if the Back-up
DC
supply is connected. The Drive will display trip
code
rS
, indicating failure to perform the stator resistance test.
To prevent this occurring, set parameter
5.14
(
0.07
) at one of the
following, and refer to
Voltage boost
in Chapter 4
Menu 0 parameters
in the
Unidrive User Guide
:
Ur_S
,
Ur
,
Fd