UD70/MD29 Installation Guide
12
Issue Number: 3
www.controltechniques.com
3.3.5
Cascade
Mode 4 - Cascade Mode
Mode 4 provides allows UD70 and/or MD29 RS485 ports to be “cascaded”. This
mode is similar to the Master/Slave mode, except that each node can be a slave to
an “upstream” node, AND a master to a “downstream” node.
3.3.6
I/O Box Mode (UD70 and MD29AN only)
Mode 10 - I/O Box Mode
Unlike the MD29, the UD70 and MD29AN do not have a dedicated port for use with
the I/O Box. The general purpose RS485 port can be configured to communicate
directly with an I/O Box by configuring the RS485 port to use Mode 10
communications.
3.4
Storing configuration parameters
In all cases, the configuration parameters must be stored, and the UD70 or MD29
reset before changes will take effect.
3.4.1
Unidrive
•
To store changes in menu 17 parameters, set #MM.00 to 1000 and press the
red RESET button.
•
To reset the UD70, set #MM.00 to 1070 and press the red RESET button.
3.4.2
Mentor II
•
Ensure that the Mentor II is disabed
•
To store changes in menu 11 and 14 parameters, set #MM.00 to 1 and press
RESET. This will also reset the MD29.
Unidrive or
Mentor II
parameters
Scale to +/-
16000
Pointer 2
Scaling
parameter
Pointer 1
1
Receive data from
previous node
Transmit data to
next node
RS485 port
3
7
1 6 2