![Control Techniques 0477-0008-01 Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/control-techniques/0477-0008-01/0477-0008-01_user-manual_2658670005.webp)
DeviceNet Module User Guide
5
Issue 1
www.controltechniques.com
Engl
is
h
F
ran
çai
s
D
eu
tsch
It
a
lia
n
o
Es
pa
ñol
中文
Figure 2-2 Remove the module from the starter
Remove the module using the following procedure:
1.
Take the module off-line.
2.
Remove the DeviceNet connector.
3.
Remove control power and mains supply from the soft starter.
4.
Push a small flat-bladed screwdriver into the slots at the top and bottom of the module
and depress the retaining clips.
5.
Pull the module away from the soft starter.
03550.
A
3.
DeviceNet Module Connection and Configuration
3.1
Adjustment
The factory default settings for the rotary adjustment switches are:
Figure 3-1 Adjustment switches
DATA RATE
PGM
500 kB
250 kB
125 kB
0
2
4
6
PGM
0
2
4
6
8
LSD
NODE ADDRESS
( 00 - 63, PGM )
MSD
Changes to the rotary switch settings take effect when the DeviceNet network is next powered up.
NOTE
The Data Rate and Node Address (MAC ID) must be set locally on the module. These cannot be set using DeviceNet
management software.
When the Data Rate and MSD Node Address (MAC ID) rotary switches are set on PGM position, the module uses the
previously used valid on-line Data Rate and Node Address (MAC ID).
Содержание 0477-0008-01
Страница 20: ...20 Guide de mise en service Module DeviceNet www controltechniques com Indice 1 ...
Страница 30: ...30 DeviceNet Modul Betriebsanleitung www controltechniques com Ausgabe 1 ...
Страница 40: ...40 Guida dell utente del modulo DeviceNet www controltechniques com Versione numero 1 ...
Страница 50: ...50 Guía del Usuario Módulo DeviceNet www controltechniques com Versión 1 ...
Страница 60: ......