Parity
none, even, or odd
Word Length
7 or 8 bits
Stop Bits
1 or 2 bits
Duplex (COM1,
COM2, COM 4)
full or half with RTS/CTS control
Cable Length
RS-232 –maximum 50 ft (15.2 m)
RS-485 –maximum 4000 ft (1200 m)
Ethernet
Termination
RJ-45 modular connector
10BaseT (twisted pair)
10M bits per second.
Protocol
TeleBUS (compatible with Modbus RTU and Modbus ASCII)
Protocol Modes
slave, master, master/slave, store and forward
8.4 Visual
Indicators
COM1,COM2,
COM4
received data
(RxD) LED
transmitted data (TxD)
LED
clear to send
(CTS) LED
data carrier detect
(DCD) LED
Ethernet LAN
Ethernet network receive or transmit data
LAN LED
Ethernet port connected to a network
LINK LED
I/O module LED power status LED
Status LED (shows functional status)
5V power LED (LED power not applicable)
Run LED
Forced I/O LED
Counter Inputs 0, 1, 2 and 3 LEDs
Push-button
LED power toggle
8.5 Power
Supply
Power Input
AC/DC PWR IN
16Vrms
±
20%
13 to 24Vdc nominal
30Vdc maximum
DC power Input
DC PWR
30V maximum
10.7V typical turn on
9V typical turn off
5 Volt Power
Output
5V at 1.3A capacity
5V at 500 mA required by SCADAPack 32P
DC power
Output
16Vrms applied
20-24V with 1.0Vp-p maximum ripple.
300mA available at 5V/0.5A, de-rate linearly to 100mA
available at 5V/1.3A
Efficiency
80%, 12V on DC PWR input
Transient
Protection
Transient: 2.5kV surge withstand capability as per ANSI/IEEE
C37.90.1-1989
SCADAPack 32P Controller Hardware Manual
May 26, 2006
38