Notes on the instruction manual
16
The movement detectors must be mounted to a solid wall, since each movement of the device
has the same effect as the movement of a heat source in the detection range.
– The optimum function of the movement detector is assured when it is mounted laterally to
the direction of movement (tangential approach).
– Since infrared waves cannot penetrate solid objects, ensure that nothing obstructs the "line
of vision" of the movement detector.
– A minimum distance of 2 m is to be kept from the direct light of lamps.
Mounting heights / Detection levels
■
The movement detector has a selective lens which
has a detection level of approximately 3° upwards
and approximately 2° downwards.
Detection range
■
The detection range is 180°, which is composed of
two 90° segments.
■
The transmission range at a tangential / vertical
approach amounts to at least 6 m.
Narrowing the detection range
■
The detection range can be narrowed via the
parameter setting within the Engineering Tool
Software (ETS) (Power-Tool)*
*Use ETS 5.6 or higher
ca. 14˚
ca. 5˚
1
,1
m
-
1
,3
m
6
m
3 m
3 m