EMM-µD3h  EMM-µD3h-p  EMM-µD3h-485  instruction manual 

IM380-U v3.1 

pag. 4 / 12

 

DESCRIPTION: 

 

LEGEND: 

A

Key  for  visualising  the  three  phase  system 
parameters  with  its  corresponding 

LED

.  By 

pressing again this key, the instrument returns to 
reading  each  individual  phase.  By  keeping  the 
key  pressed  for  5  seconds  the  instrument 
reaches  the  programming  mode  (

SETUP

).  In 

SETUP

  mode,  this  key  confirms  the  values  set 

and  by  pressing  the 

B

  key  simultaneously,  it 

starts decreasing the value. 

B

Key for selecting the measured parameters to be 
shown  at  the 

C

  display.  In 

SETUP

  mode  selects 

and  modifies  the  value  of  the  parameters  to  be 
set. 

A+B

:  With  the  simultaneous  pressing  of  both  keys  the 

instrument  reaches  the  visualisation  of  the 
maximum  and  average  values,  which  may  be 
selected  with  the 

B

  key.  To  escape  from 

maximum and average values visualisation, don

’t 

press any key for 8 seconds. 

C

:  

Three  displays  for  visualising  the  measures, 
subdivided  by  phase  of  the  parameters  indicated 
by the LED 

D

 bar. In case that the 

L

 LED (

G

) is 

glowing, the instruments shows the three phase values of the measures, indicated by the LED 

D

 bar. 

D

:  

LED bar for indicating the measures visualised on display 

C

E

:  

Terminals for wiring the voltage measures input and auxiliary supply. 

F

:  

Terminals for wiring the current measures input and the digital output (when present in the instrument). 

G

LED for indicating of a three phase value visualisation. 

 

MENU FOR PROGRAMMING THE INSTRUMENT (SETUP) 

The  instrument’s  SETUP  menu  is  reached  by  pressing  the 

A

  key  during  3  seconds.  Once  in  the  SETUP  menu,  it  is 

possible to select or modify the visualised parameter’s value, by pressing the 

B

 key. 

If no pressing is made on any key during 8 seconds, the instrument escapes from the SETUP menu. 
For  a  correct  operation  of  the  multimeters  the  instrument  has  to  be  programmed  with  the  transformation  ratio  of  the 
external CT’s. 
It will only be possible to reset the energy meters in those instruments fitted with such a characteristic, so as to program 
the digital outputs only if the digital outputs is available in the instruments. 
The set values are kept without auxiliary supply even. 

 

> 5 seconds,

 

access to the programming menu (SETUP) 

 

 
for selecting of a parameter or modifying the 

parameter’s value for programming (SELECT) 

 

 
for confirming the selection or confirming the programmed parameter’s value (ENTER) 
 
 

L

SET

L

SET

C

E

F

L1

L2

L3

L

V

L-N

A

kW

kVAr

kVA

V

L-L

...h

Hz/

out

SET

P.F.

e le ctr ica l m ulti m ete r

EMM-µD3

max

avg

VL1

VL2

VL3

N

aux2 aux1

voltage  inputs

V aux

S1

S1

S1

S2

S2

S2 Do2

c

Co

B

Do1

A

IL1

IL2

IL3

current inputs

A

B

D

G

Содержание EMM-mD3h

Страница 1: ...ard version 110V rated 50 60Hz optional version 400V rated 50 60Hz optional version INTRODUCTION The EMM D3h are only featured for local visualising the electrical parameters The EMM D3h p has two dig...

Страница 2: ...he terminals aux1 and aux2 The rated supply voltages can be standard Vn 230V 15 50 60Hz under request Vn 110V 15 50 60Hz under request Vn 400V 15 50 60Hz measuring voltage inputs 4 terminals are avail...

Страница 3: ...PHASE LINE WITH 3 OR 4 WIRES EMM LOAD aux1 aux2 auxiliary supply VL1 VL2 VL3 N measur ing voltage inputs EMM aux1 aux2 auxiliary supply VL1 VL2 VL3 N measuring voltage inputs EMM aux1 aux2 auxiliary s...

Страница 4: ...r wiring the voltage measures input and auxiliary supply F Terminals for wiring the current measures input and the digital output when present in the instrument G LED for indicating of a three phase v...

Страница 5: ...or EMM D3h p kWh kVAr pulse Set pulse weight kWh kVAr pulse kWh kVAr pulse kWh kVAr pulse only for EMM D3h p Increase from to mS in step by 100 mS Decrease only for EMM D3h 485 Increase Set address of...

Страница 6: ...e connection It s possible to chose 3 wires or 4 wires With the 4 wires connection the neutral parameter are displayed and enabled to use for the digital outputs settings Programming of the synchronis...

Страница 7: ...arm In mode the digital output DO1 will emit pulses proportional to the active energy counted while the digital output DO2 will emit pulses proportional to the reactive energy counted The proportional...

Страница 8: ...B key pressed to decrease the values The range depends by the parameter and it is linked to the CT and VT ratios Pressing A key to confirm The threshold set is linked with CT and VT ratios for this re...

Страница 9: ...the energy meters are shown with the lighting of the LED kW h indicating the active energy values kWh whilst the lighting of the LED kVAr h are indicating the reactive energy values kVArh The lightin...

Страница 10: ...lti meter Visualization page 7 Three Phase Hour counter 520 2 h L1 L2 L3 L EMM D3 electrical multi meter VL N A kW kVAr kVA VL L h Hz out max avg SET P F Visualization page 1 VL1 N L1 on IL1 on L2 kWL...

Страница 11: ...max V L3 N max phase current I L1 max I L2 max I L3 max average phase current maximum demand I L1 max avg I L2 max avg I L3 max avg three phase system powers W max VAr max VA max average three phase s...

Страница 12: ...dance 1 M 3 4 and single phase wiring Current inputs From 0 02 to 5A permanent overload 50 from external CT s with secondary 5A optional 1A Primary programmable from 5 to 2000A self consumption 0 5VA...