Programming of the transformation ratio of the external current transformers (

SET CT

The programming of the CT ratio, intended as the ratio between the primary and the secondary circuit (example: with 
CT 1000/5 it must be set 200), has to be performed by using the front keys. 
After the enter in the setup (message 

SETUP

 on 

F

 display) pressing the 

C

 key, the message 

seT

 will appear on the 

G

 display and the message 

CT

 

(Current transformer ratio) on the first 

F

 display; the transformation ratio value (set to 

1 by the manufacturer) on the second and the third 

F

 display. Press 

B

 or 

C

 keys to increase or decrease the value 

respectively (the variation is performed unit by unit). In order to speed up the operation, keep the 

B

 or 

C

 key pressed, 

the variation will be performed by tens and hundreds. To increase or decrease the value by unit, it is necessary to 
release and to press the button again. To confirm the set value, press the 

A

 button; in this way it is possible to enter 

the next programming. If none key is pressed for 10 seconds, the instrument will automatically leave the programming 
menu and the eventual setting SHALL NOT be stored. 

 

-  Programming of the transformation ratio of the external voltage transformers (

SET VT

After the precedent programming phase, on 

F

 display will appear the inscription 

Vt

 (voltage transformer) and the 

value of the transformation rate of the external TV (set to 1 from the constructor), considered as the rate between 
primary and secondary (example with TV 15/0.1 kV the value will be 150). In the same way at the programming of the 
CT rate will be possible to set this value. If the external TV are not used the value to set will be 1. To confirm the value 
press the 

A

 button. 

If the instrument has not options the programming continues with the set of average time 

AVG T’

 and after with the 

password 

PASS

, then it come back at the first page 

SETUP

. The presence or the absence of the options, neutral 

current, digital output and serial output, will allow the visualization or not of the other settings. 

 

Programming of the transformation ratio of the current transformer for the neutral current input (

CTN

(version with neutral current input) 

This setting is active only for the models with this option installed; the message 

SET

 will appear on 

G

 display; the 

message 

CTN

 (Current transformer neutral ratio) and the set value on the 

F

 display. In the same way at the 

programming of the CT rate will be possible to set this value (example with CT 1000/5the value will be 200). 
Pressing the 

A

 key, confirm and go away with the next setting. 

 

Programming of the average time (

seT AVG T’

After the programming phase previously described, pressing another time the 

A

 key, on the 

F

 display will appear the 

message 

AVG T’

 and the average time settable from 1 to 30 minutes. 

To increase the value press the 

B

 key. To decrease it, press the 

C

 key. To confirm it press the 

A

 key. 

The average time is the time used to calculate the average parameters (

avg

) and the maximum demand (

maxD

). 

 

Programming of the energy visualization type and the use of the digital input (

seT EN

This setting allows to define the energy visualization type after the visualization of the temperature. 
With 

TB1 TB2

 will have the separated visualization of the two bands of the active, reactive, and apparent energy; the 

digital input will select the band (tb1 if opened, tb2 if closed). The 

TB1

 

TB2

 function is not present if the digital input 

option is not installed. With 

TOT PAR

 will have the visualization of the partial and total energy counters; the digital 

input is used (when it’s closed) to reset the partial counters. With 

NORMAL

 there will be only the visualization of total 

counters (that it’s possible to reset from 

RESET

 menu). The status of the digital input is always readable from serial. 

 

Programming insertion mode (

3PH

In

 

a

 

unbalance

 

three

 

phase

 

system

 

it’s

 

necessary

 

to

 

set

 

UN_BAL

 

(unbalance)

 

while

 

in

 

a

 

balance

 

system

 

(only

 

one

 

CT

 

and

 

only

 

one

 

VT)

 

the

 

correct

 

set

 

is

 

BALANC

 

(balance).

 

For

 

a

 

single

 

phase

 

insertion

 

it’s

 

necessary

 

to

 

set

 

1PH L1

 

Programming wiring connection mode (

MDE

This setting allows to definite the wiring type connection. It’s possible to chose 3 wires or 4 wires. With the 4 wires 
connection the neutral parameter are displayed and enabled to use for the digital and analog outputs settings. 

 

Programming of the synchronism type (

SYN MDE

In this setting for the synchronization type, it’s possible to choose 

L1

 to use the external frequency (on L1 phase) or 

50

60

 Hz to use the internal clock. 

 

Programming

 

of

 

the

 

weight

 

of

 

the

 

active

 

and

 

reactive

 

energy

 

pulse

 

(

seT

 

PULSE

)

 

(only

 

for

 

vers.

 

with

 

digital

 

output) 

After the above mentioned programming, by pressing the 

A

 key again, the message 

PUlse

 will appear on the 

F

 

display and the value of the weight of one pulse settable on three phase values: 

0,01

 - 

0,1 

10

 kWh or kVArh 

(for each emitted pulse the instrument will have counted 0,01 - 0,1 - 1 - 10 kWh o kVArh). 
Press the 

B

 key to increase the value or 

C

 key to decrease the value and 

A

 to confirm. 

 

Programming of the duration pulse (

SET TPL

) (only for vers. with digital output) 

The message 

TP

L

 will appear together the value of the duration pulse expressed in mS. It’s possible to select the 

value from 100 mS to 500 mS, with 100 ms steps by using 

B

 key (to increase the value) and 

C

 (to decrease the 

value). Confirm the value pressing the 

A

 key. 

This setting is used by all digital outputs. 

Содержание EMM-D4h

Страница 1: ...s version with analog output OPTIONS Power Supply 20 60 Vac dc C1 Power Supply 90 250 Vac dc C2 Current Input 1A 1A Insulated current inputs t Neutral current input n Digital input DI it s not availab...

Страница 2: ...Vac dc version Terminals Power Supply Terminals Power Supply Terminals Power Supply 19 20 0 110V 100 125Vac 50 60Hz 19 21 20 60Vac 24 72Vdc 19 21 85 230Vac 90 250Vdc 19 21 0 230V 220 240Vac 50 60Hz 1...

Страница 3: ...28 29 30 31 32 33 34 35 36 EMM D4hp 485 EMM D4hp 485 A S2 S2 S1 S1 VL3 VL2 VL1 N S1 S2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 CURRENT INPUT S VOLTAGE INPUTS IL1 IL2 IL3 S2 S1 In 400V COM 230V B...

Страница 4: ...measure voltage inputs auxiliary power supply P1 P1 P1 P2 S1 S1 S1 S2 N L1 L2 L3 S2 S2 S2 S1 S1 S1 I1 I2 I3 VL1 VL2 VL3 N measure current inputs measure voltage inputs 0 110 230 400 auxiliary power su...

Страница 5: ...s Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy counters excluded The voltage values a...

Страница 6: ...nchronism 50 type 60 version with digital output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase fr...

Страница 7: ...g Programming of the average time seT AVG T After the programming phase previously described pressing another time the A key on the F display will appear the message AVG T and the average time settabl...

Страница 8: ...B key at the same time If the password is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instr...

Страница 9: ...R HI and ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum va...

Страница 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Страница 11: ...ng the C key the message SET AN OUT will appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will a...

Страница 12: ...ge appears in F displays on the first part L1 the status of digital input on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digital output...

Страница 13: ...the segment of the right digit of the G display in correspondence of h on the front panel turn on to indicate the visualization of the apparent energy counter To complete the visualization the led k o...

Страница 14: ...1 max avg I L2 max avg I L3 max avg I N max avg max maxD avg maximum of average phase and neutral currents max demand three phase power W max avg VAr max avg VA max avg max maxD avg maximum of average...

Страница 15: ...nnect various instruments in the same network The maximum suggested length for a RS485 connection is 1200m For longer distances provide the use of low attenuation cables or signal amplifiers On the sa...

Страница 16: ...OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse Pulse duration 100 200 300 400...

Отзывы: