Contrel EMM-D4h Скачать руководство пользователя страница 2

 

EMM-D4h 

instruction manual 

IM443-U v0.7 

pag. 2  

INSTALLATION 

WARNING FOR THE USER 

Read carefully the instructions/indications contained in this manual before installing and using the instrument. 
The instrument described in this manual is intended for use by properly trained staff only. 

SAFETY 

This instrument has been manufactured and tested in compliance with EN 61010-1 standards. In order to maintain these conditions 
and to ensure safe operation, the person must comply with the indications and markings contained in the manual. When the 
instrument is received, before beginning installation, check that it's O.K. And it has not suffered any damage during transport. When 
starting installation make sure that the operating voltage and mains voltage are compatible with the device instructions. The 
instrument power supply must not be earthed. Maintenance and/or repair must be carried out only by qualified and authorized 
personnel. If there is ever the suspicious that, that there is a lack of safety ,during operation, the instrument must be disconnected 
and cautions taken against accidental use. 

Operation is no longer safe when: - The instrument doesn't work. / - The measured value are obviously wrong or 
unreasonable / - There is clearly visible damage. / - After serious damage incurred during transport. / - After a storage 
under unfavourable conditions 

 

CONNECTION 

For a correct use of the device, the wiring diagram contained in the present manual, must be respected. 
The connections are the same for all models and are subdivided in three groups: 

 

-  auxiliary power supply: 

On the instrument are available 4 terminals to connect the auxiliary power supply to the instrument: 

Vac version 

Vac/dc version 

Vac/dc version 

Terminals 

Power Supply 

Terminals 

Power Supply 

Terminals 

Power Supply 

19-20 

0-110V = 100-125Vac 50-60Hz 

19-21 

20-60Vac 
24-72Vdc 

19-21 

85-230Vac 
90-250Vdc 

19-21 

0-230V = 220-240Vac 50-60Hz 

19-23 

0-400V = 380-415Vac 50-60Hz 

It’s possible, for example, to take the auxiliary power supply between phase and neutral, in a 4 wires system, or 
phase-phase in a 3 wires system, without neutral or from a VT in a medium voltage application. 

 

-  measure voltage inputs: 

4 terminals are available for the connection to the 3 phase and neutral of the network of measure, the maximum 
voltage phase to phase shouldn't be over 500 V rms. 
In case of a 3 phase system without neutral, or non distributed neutral to leave terminal N free. 

 

-  measure current inputs: 

6 terminals are available for the connection to 3 external amperometric transformers with secondary 5A, it’s possible 
to use 2 TA on lines with 3 wires (insertion three phase Aron). 

The utilization of external TA is obligatory.

 

With the neutral current input option installed, the multimeter allows the measure of the neutral current, using a current 
transformer /5A; the secondary must be connected to the In S1 and S2 terminals available on the rear of the 
instrument (see the wiring diagram). 

 

REMARKS: It's a must to respect the phase sequence. The connections between current and voltage phase inputs must not be 
inverted (for example, CT placed on phase L1 must correspond to the I1 input). So as it is not correct to invert S1 and S2 terminals, 
since power factors and powers might not be reliable. 
For fixing the flush mount version instrument to the panel, use the fixing devices supplied, by inserting them in the side groves of the 
enclosure and tighten the screws. 
For safety reasons, place an external fuse protection at the input voltages, and use adequate cables for the working voltages and 
currents, with a cross sections from 0,5 to 2,5 mm

2

Содержание EMM-D4h

Страница 1: ...s version with analog output OPTIONS Power Supply 20 60 Vac dc C1 Power Supply 90 250 Vac dc C2 Current Input 1A 1A Insulated current inputs t Neutral current input n Digital input DI it s not availab...

Страница 2: ...Vac dc version Terminals Power Supply Terminals Power Supply Terminals Power Supply 19 20 0 110V 100 125Vac 50 60Hz 19 21 20 60Vac 24 72Vdc 19 21 85 230Vac 90 250Vdc 19 21 0 230V 220 240Vac 50 60Hz 1...

Страница 3: ...28 29 30 31 32 33 34 35 36 EMM D4hp 485 EMM D4hp 485 A S2 S2 S1 S1 VL3 VL2 VL1 N S1 S2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 CURRENT INPUT S VOLTAGE INPUTS IL1 IL2 IL3 S2 S1 In 400V COM 230V B...

Страница 4: ...measure voltage inputs auxiliary power supply P1 P1 P1 P2 S1 S1 S1 S2 N L1 L2 L3 S2 S2 S2 S1 S1 S1 I1 I2 I3 VL1 VL2 VL3 N measure current inputs measure voltage inputs 0 110 230 400 auxiliary power su...

Страница 5: ...s Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy counters excluded The voltage values a...

Страница 6: ...nchronism 50 type 60 version with digital output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase fr...

Страница 7: ...g Programming of the average time seT AVG T After the programming phase previously described pressing another time the A key on the F display will appear the message AVG T and the average time settabl...

Страница 8: ...B key at the same time If the password is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instr...

Страница 9: ...R HI and ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum va...

Страница 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Страница 11: ...ng the C key the message SET AN OUT will appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will a...

Страница 12: ...ge appears in F displays on the first part L1 the status of digital input on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digital output...

Страница 13: ...the segment of the right digit of the G display in correspondence of h on the front panel turn on to indicate the visualization of the apparent energy counter To complete the visualization the led k o...

Страница 14: ...1 max avg I L2 max avg I L3 max avg I N max avg max maxD avg maximum of average phase and neutral currents max demand three phase power W max avg VAr max avg VA max avg max maxD avg maximum of average...

Страница 15: ...nnect various instruments in the same network The maximum suggested length for a RS485 connection is 1200m For longer distances provide the use of low attenuation cables or signal amplifiers On the sa...

Страница 16: ...OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse Pulse duration 100 200 300 400...