EMA11 - USER MANUAL
-53-
11.10)
ANALOG OUTPUT (OPTION)
Selecting the analog output voice, the following programming page
appears:
•
Out Index
, expresses the number of output to select or program, which
are present on the hardware of the instrument.
•
Type
, allows to select the value of current output, (disabled, 0-20mA, 4-
20mA).
Through the up & down keys, it may be possible to select the type of the
output current, by pressing the “ENTER” key the configuration is saved.
•
Measure Code,
is the measure (see cap. 12) to associate at the analog
output.
•
Min.
, full-scale value of the lower limit of the programmed value (Measure
Code).
Once the minimum full-scale has been programmed, the instrument
automatically will associate the minimum current value (0 or 4 mA) at this
value.
•
Max.
, full-scale value of the upper limit of the programmed value
(Measure Code).
Once the maximum full-scale has been programmed, the instrument
automatically will associate the maximum current value (20 mA) at this
value.
If the minimum end-scale value is lower of maximum end-scale value, the out of current will be directly
proportional at variable set, otherwise it will be inversely proportional. Minimum and maximum can be
negative value.