Contrel EMA11 Скачать руководство пользователя страница 44

EMA11 - USER MANUAL 

-44- 

11.3) GENERAL 

The general menu is subdivided in the following sub menu: 

 

KCT

, allows to set the current transforming ratio setting the primary and 

secondary values of the CT, if it’s used, in order to show the measured 
values in primary terms. Primary Range: 1÷5000A; Secondary Range: 1 
or 5A (for EMA11-1A is fixed to 1). I.e. Set KCT-Pri.=200 and KCT-
Sec.=1 if a CT used is an 200/1 A. 

 

KVT

, allows to set the voltage transforming ratio setting the primary and 

secondary values of the VT, if it’s used, in order to show the measured 
values in primary terms. Primary Range: 1÷400000V; Secondary Range: 
1÷750V. I.e. Set KVT-Pri.=20000 and KVT-Sec.=100 if a VT used is an 
20000/100V. 

 

Mode

, concerns the operation or measuring mode, it is possible to select 

4 wires, 3 wires and Aron, following the connection mode as described on 
chapter 6.4). 

 

Measure Time

, is the filter time in the visualization measure. The range is 

0÷50. The 0 value indicates none average on the measures, others 
values indicates the average time (in seconds). If this value is very big 
and the average powers storing is active, the values stored could be 
wrong. It’s better to set a value less than 5 seconds. 

 

Warnings

, enables [Yes] or disables [No] the visualization every 15 second of the warnings page 

alternatively at default page if current transformer connection is wrong or there is an inversion of the 
phase sequence. The condition of battery low, it will appear independently of the set of this voice. 

 

B.Light

, is the time (from 0 to 360 seconds) in which the display remains on, after the keyboard’s 

inactivity. To hold the display always on, it has to be set the value as 0. The brightness of display 
declines about 10% every 1000 hour of work. 

 

Display

, it’s possible to choose between positive visualization (dark characters on clear 

background) and negative visualization (clear characters on dark background). 

 

Def. Page Time

, is the time of wait before to come back to default page. Range 10÷900 seconds. 

 

Synchronization

, to set the fundamental frequency. 

Mode

: internal or external (V

L1

). 

Freq.

: programmable frequency value (range 5÷500Hz). 

 

Set Clock

, sets the internal clock of the instrument with relative date. The 

format of the date is:  dd:mm:yy and of the time is:  hh:mm:ss 

Day Light

 allow to set the yearly summer time change. It’s possible to 

enable the time shift of the summer time and the return at the solar time 
at the fixed data. The instrument manages the summer time from the 
1997 to the 2030. 

 

Password

, it’s possible to set a numeric password to modify the SETUP. 

The default password is 0000: the setup can be always opened and it’s always possible to change 
any parameter. If the password is different by 0000 (from 0001 to 9999), at the entrance of setup, 
the password will be request. if the password is ignored, it will be possible to see every parameter 
but it will be impossible to modify it. Only with the correct password it’s possible to change every 
parameter. To set the new password as 0000, the instrument come back at default status. Call the 
constructor to have an emergency password if you lose the password. 

 

Access

, allows to input a code of 6 digits to enable the calculation end 

the visualization of the harmonics and/or the time-bands. These options 
are both enabled if it’s an H instrument: the code is on a report. These 
options are disabled if it’s an L instrument but one or both can be 
enabled. To make this it’s necessary to give the serial number and the 
option(s) to enable at Contrel Elettronica Srl that will send the access 
code corresponding at the instrument and the selected option(s). 

 

User Page

, select 5 parameters to visualize in the relative page. 

 

V

 

Unbalance

 

calculates

 

the

 

voltage

 

unbalance

 

between

 

the

 

line

 

or

 

phase. 

Содержание EMA11

Страница 1: ...1 ELECTRICAL MULTIFUNCTION ANALYZER User Manual IM 135 U v 4 1 EMA11 IM135 U v4 1 doc ELECTRICAL MULTIFUNCTION ANALIZER RECORDER SELECT P UP ENTER P DOWN SELECT ELECTRICAL MULTIFUNCTION ANALIZER RECOR...

Страница 2: ...eplacement of equipment parts which are recognized as faulty due to manufacturing defects Warranty does not cover those parts which results defective due to misuse or improper use incorrect installati...

Страница 3: ...________________________________13 4 3 MOUNTING ____________________________________________________________14 5 INTERNAL BATTERY ______________________________________________________15 5 1 REPLACEME...

Страница 4: ...ATION PAGES ______________________________________40 11 SETUP __________________________________________________________________42 11 1 SETUP ITEMS ____________________________________________________...

Страница 5: ...ent software has been installed It is possible to monitor via digital outputs 2 dig out standard alarms sirens or strategically factory loads EMA11 with optional harmonic analyzes can carry out networ...

Страница 6: ...2 VA 0 04 VA Consumption 4VA typical 6VA max full optional Serial output RS485 RS232 configurable on board half duplex isolated signals Tx Rx Gnd Programmable baud rate from 1 200 to 19 200 bps Commun...

Страница 7: ...5 F to 70 C 158 F Operating humidity 90 not condensing Protection standards IP 52 front EN60529 IP65 with gasket on request IP 20 screw and terminals Weight and dimension 0 430 kg app equipped with 2...

Страница 8: ...at 60 Hz 3 88kHz Zero self regulation Offset 0 1 second RTC REAL TIME CLOCK Accuracy 5 PPM standard CEI EN 61038 2 3 PROGRAMMABLE PARAMETERS SETUP SECTION VT and CT ratio Mode insertion type 4 wires 3...

Страница 9: ...PFL2 PFL3 THREE PHASE SYSTEM POWER FACTOR PF COS COS L1 COS L2 COS L3 THREE PHASE SYSTEM COS COS APPARENT POWER SL1 SL2 SL3 VA THREE PHASE SYSTEM APPARENT POWER S VA ACTIVE POWER PL1 PL2 PL3 W THREE P...

Страница 10: ...hLi ALi W Li PFLi Q Li W Li W Li Li I LiN V LiN ALi P iLi k vLiNk Q Li P iLik vLiNk W Li P i LiNk I Li P v LiNk V LiN P k P k P k P k 0 Energy Active Factor Power 2 2 cos Cos Power Appearent Power Rea...

Страница 11: ...V L L V P v Lijk V Lij dt Q Li Qh Li P k 0 3 3 Energy Reactive 0 3 3 Energy Active 3 2 1 3 rent PhaseAppea 3 3 2 1 3 Power Reactive Phase 3 3 2 1 3 Power Active Phase 3 3 3 2 1 3 Current System Phase...

Страница 12: ...128x128 dot dot pitch 0 35mm x 0 35mm dot size 0 32mmx0 32mm high viewing direction 60 positive and negative visualization at low reflection 2 KEYBOARD In the Acquisition Mode the up and down arrows a...

Страница 13: ...or repairs must only be carried out by qualified and authorized personnel If in any doubt about the instrument s safety take it out of service and implement the necessary procedures to prevent its ina...

Страница 14: ...ipment on vibration free switchboards and with an environmental temperature ranging between 10 C and 50 C The panel cut out of the unit is the following Following the picture below mentioned insert th...

Страница 15: ...trument Instruction to change the internal battery 1 It s necessary to cut off the power supply of instrument and to disconnect all inputs and all outputs 2 Remove the seal from the rear door 3 Open a...

Страница 16: ...20mm dimensions 315mA 250V Fast i e Schurter FSF If the instrument is off with presence of power supply it s necessary to verify the internal fuse In case of fuse replacement disconnect the instrument...

Страница 17: ...PUTS Connect the instrument following up the wiring diagrams described on chapter 6 4 WARNING before connecting the current inputs to the terminals of the instrument are advised that the maximum allow...

Страница 18: ...oltage transformers L1 L2 L3 N LOAD P1 P2 S1 S2 L1 L2 L3 N L1 L2 L3 L1 L2 L3 N LOAD N P1 P2 S1 S2 L1 L2 L3 L1 4 wires insertion 3 current transformers and 3 voltage transformes 4 wires insertion 3 cur...

Страница 19: ...used to insert the option board of the digital input digital output analog output and serial port a 6DI 6 digital inputs b 2DI 2DO 2 digital inputs 2 digital outputs c 4DO 4 digital outputs d 2AO 2 an...

Страница 20: ...me level of the slot see the following picture 9 Close the instrument using the rear door with the hole in which will enter the plug in module of the slot number 1 You can use a screwdriver to help yo...

Страница 21: ...the chapter 11 9 If long distances must be covered the wires connected to the EMA11 needs to be wired in a separate channel from the power supply cables if an intersection occurs between the power su...

Страница 22: ...ed by the operator on min max threshold external band always ON or and pulse output consult the chapter 11 8 The signs and on outputs in the picture have electric meaningless If long distances must be...

Страница 23: ...is optional board the instrument will be equipped with 8 digital inputs 2 standards 6 optional and 2 digital outputs This module has an output 0 12Vcc usable like power supply for digital inputs The f...

Страница 24: ...manage 2 digital inputs 2 digital outputs and 2 analog outputs See the chapter 11 10 to program 0 20mA or 4 20mA these outputs The following table shows the pin out 1 7 2 8 3 9 OUTPUT 2 4 10 OUTPUT 2...

Страница 25: ...IN The instrument with this option will manage 2 digital inputs 2 digital outputs and 4 analog outputs The pin out is showed in the following table 1 7 OUTPUT 3 2 8 OUTPUT 3 3 9 OUTPUT 2 4 10 OUTPUT...

Страница 26: ...mum suggested length of a RS 485 connection is about 1200 mt while for a RS232 connection about 5 mt For longer distances cables with low attenuation or connection to line amplifier are recommended Up...

Страница 27: ...TION If a RS232 communication line is shorter of 5 mt and a multidrop network will not use it s not necessary to use a serial line converter because the serial output is compatible with the PC as show...

Страница 28: ...C0 ignore CD R1 ignore RTS S0 2 set at two as the ring number after the which the modem automatically reply the number can be different by 2 but it must be different by 0 W0 store the configuration i...

Страница 29: ...AL 29 8 4 5 OPTION RS485 RS232 COM2 PLUG IN Warning The hardware modification of instrument will change the Setup in the default configuration RS485 RS232 Personal Computer Modem TX RX COM 1 2 3 4 5 6...

Страница 30: ...ey allows to enter in the setting menu or submenu in order to program and or set values and confirm the operation s SYSTEM RESET To reset the unit directly from the keyboard without entering in the Se...

Страница 31: ...ltage Min Max 3 Ph Va Power H V 20 29 IL1 Harmonics Storage Samples Total Energy TB P3 P4 Cos Average Powers Line Voltage Avg Current Thd Current L2 Phase V C L1 Phase Active Powers TB Energy Today P3...

Страница 32: ...rrent L1 I1 W kW MW GW active power L1 W1 PF power factor L1 PF1 Variable reading of phase L2 V kV RMS voltage L2 phase V2 A kA RMS current L2 I2 W kW MW GW active power L2 W2 PF power factor L2 PF2 V...

Страница 33: ...phase voltage V kV rms voltage between L1 and L2 V1 2 V kV rms voltage between L2 and L3 V2 3 V kV rms voltage between L3 and L1 V3 1 percentage of unbalance phase voltage Vunb Note the unbalance volt...

Страница 34: ...nt L1 phase I1maxav A kA rms maximum average current L2 phase I2maxav A kA rms maximum average current L3 phase I3maxav A kA rms maximum average neutral current N Inmaxav Note The maximum average curr...

Страница 35: ...ctive power P W kW MW GW active power L1 P1 W kW MW GW active power L2 P2 W kW MW GW active power L3 P3 Variable reading phase reactive power VAr kVAr MVAr GVAr three phase system reactive power Q VAr...

Страница 36: ...r L2 PF2 P F power factor L3 PF3 Variable reading phase cos cos three phase system cos cos cos cos L1 cos 1 cos cos L2 cos 2 cos cos L3 cos 3 Phasor option Fresnel diagram Phase angles in degree volta...

Страница 37: ...active energy counter kWh kWh negative active energy counter kWh kVArh inductive reactive energy counter kVArh kVArh capacitive reactive energy counter kVarh Note If Energy Type is set like Heavy the...

Страница 38: ...rnal signals connected to digital inputs and with a right programming can change the bands in the time If the energy is Heavy the values are displayed in MWh and MVArh Variable reading MIN MAX values...

Страница 39: ...on of current L3 phase Thd3 8 pages show the harmonic components up to 31 st of voltage and current of each line in numerical form Variable reading total harmonic distortion and harmonic components of...

Страница 40: ...Type of section of memory for examples samples Status ON if memory enabled or OFF if memory disabled Record s number of stored events in memory Memory Kb Available static memory expressed in Kb which...

Страница 41: ...s the warnings page of inversion of current transformer and phases sequence will be display automatically alternatively at the default page each time that happens an inversion The second page shows th...

Страница 42: ...0 1999 99 HOLIDAYS Day Index 1 40 Month 1 12 Day 1 31 AVG POW Enable On Off HARM Enable On Off GENERAL SERIAL COMM Address 01 255 01 128 Modbus ASCII COM1 COM2 Baud 1200 19200 Parity none even odd Da...

Страница 43: ...ettings of MINMAX minimum and maximum values storing AVG POW the average consumption of active and reactive powers storing HARM harmonic storing up to the 31 st order for both current and voltage for...

Страница 44: ...e visualization dark characters on clear background and negative visualization clear characters on dark background Def Page Time is the time of wait before to come back to default page Range 10 900 se...

Страница 45: ...age RS485 or RS232 11 5 AVERAGE The AVERAGE menu allows the settings of parameters in the calculation of average values Sync Avg defines the type of the synchronism for the start and the stop of the a...

Страница 46: ...in different period To program the time bands function to accede at the TIMEBANDS menu with the following sub menu Update day sets the day in which change the month in the time bands range 0 31 If the...

Страница 47: ...ime StartHour and StartMin in TIME 2 with band P3 Type and 18 00 like start time StartHour and StartMin in TIME 3 with band P1 Type in this way the P1 band will maintain until 8 00 of the day after wi...

Страница 48: ...his variable with UP and DOWN keys Rate min acquisition time This is the acquisition time of minimum and maximum values range 1 9999 minutes For example to store the minimum and the maximum value of p...

Страница 49: ...The range is 1 9999 minutes and the default value is 60 minutes No congruent set between TRIGGER storage enabled and Type of the digital input will involve the visualization of the warning message on...

Страница 50: ...ergy pulses must be emitted every 1 kWh program 1 00 programmable from 0 01 to 100 kWh pulse Time is the threshold delay for intervention expressed in second 0 655 seconds or duration time of Pulse ex...

Страница 51: ...set the energy counters increment continue on the last band enabled independently of the digital inputs status until the change of the minute of the internal clock or the change of the status of one o...

Страница 52: ...t a user definition the others are names already fixed USER DEF The name of the counter is defined by the user When this item is selected a field appear to input the name of the counter To input the n...

Страница 53: ...to associate at the analog output Min full scale value of the lower limit of the programmed value Measure Code Once the minimum full scale has been programmed the instrument automatically will associa...

Страница 54: ...SETUP The last voice of the setup menu is EXIT SETUP which allows the operator to leave the instrument setup and go back to the REAL TIME VISUALIZATION PAGES Operator may also exit the setup by pressi...

Страница 55: ...eactive power 3Ph Wh Three phase positive active energy 3Ph VArh Three phase inductive reactive energy 3Ph Wh Three phase negative active energy 3Ph Varh Three phase capacitive reactive energy THDV L1...

Страница 56: ...ation parameters Verify the correct wiring Verify that the communication protocol of the instrument coincides with the one used in the sw Verify the wiring type RS232 or RS485 and the settings of the...

Страница 57: ...management software allowing to use all the available functions automatically search of the unit in the network automatic data downloading etc Even so the NRG software supports the MODBUS protocol Ab...

Страница 58: ...EMA11 USER MANUAL 58...

Отзывы: