EMA-D9 - USER MANUAL
-6-
2) TECHNICAL
FEATURES
2.1) GENERAL
SPECIFICATIONS
Power supply / Auxiliary voltage
90-250 V 50/60 Hz/cc.
20-60 V
50/60 Hz/cc (option).
Isolation voltage
3700 Vac rms x 1 minute.
Voltage input
3 inputs, range 10-600Vrms between phase-phase.
Over voltage up to 750 Vac permanent, beyond this value it is imperative to use voltage transformers.
Over voltage category:
III
(fixed installation)
Pollution degree: 2 (normally not conductive; temporary conductive for condensation)
Resistor input: >2 M
Ω
.
Burden 0.2 VA.
Current input
Model
EMA-D9
Model
EMA-D9-1A
3 isolated inputs (internal CT) range
10mA-5A rms
4mA-1A rms
Over current max
10A (100A for 1 second)
2A (10A for 1 second)
Consumption
4VA typical.
6VA max, full optional.
Serial output
RS485/RS232 (configurable on board), half duplex isolated, signals Tx/Rx, Gnd.
Programmable baud rate from 1.200 to 19.200 bps.
Protocols: ASCII and Modbus.
Second serial output RS485 isolated (optional).
Input signals
2 passive opt isolated inputs (1000V), 12 - 24 Vdc.
4 passive opt isolated inputs (1000V), 12 - 24Vcc (option).
Output signals
2 photomos outputs 12-260 Vca-cc / 100mA max (series).
Memory data retention
RAM: 128 KB (useful 50KB); 1 Mbyte (all useful) option.
No volatile memory data using internal battery.
Data retention: 5 years (typical) at +25°C (77°F).
Stored variables: Average power, Min/max values, Harmonics (option), Energy, Samples.
Display interface
Alphanumeric LCD 2x20 characters at high contrast (adjustable) and with led backlight.
Keyboard interface
5 functional keys for paging and programming.