31
W415-1540 / D / 03.23.17
EN
Combustible Mantel clearance can vary according to the mantel depth. Use the graph to help evaluate the
clearance needed.
!
WARNING
RISK OF FIRE, MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES. FAILURE
TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO
OVERHEAT. ENSURE ALL CLEARANCES (I.E. BACK, SIDE, TOP, VENT, MANTEL, FRONT, ETC.) ARE
CLEARLY MAINTAINED.
WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL, THE PAINT OR LACQUER MUST BE
HEAT RESISTANT TO PREVENT DISCOLOURATION.
73.1
5.5 MINIMUM COMBUSTIBLE MANTEL CLEARANCES
0
3 4
7
14
16
1 2
5 6
12
H
E
IG
H
T
M
AN
T
E
L
MANTEL DEPTH
8
10
6
4
18
20
8
10
9
22
24
26
E
D C
B
A
E
D
C
B
A
TOP OF
APPLIANCE
MANTEL DIMENSIONS
Ref
Height
Depth
A
34 5/8" (88cm)
B
12" (305mm)
2" (51mm)
C
14" (356mm)
4" (102mm)
D
16" (406mm)
6" (152mm)
E
18" (457mm)
8" (203mm)
5.6 NAILING TAB INSTALLATION
55.2
A.
Nailing tabs are provided as part of the frames, as shown. To determine the fi nal
location and where to bend the nailing tabs you must fi rst determine the thickness
of your fi nishing material (i.e. drywall). This will determine the dimension from the
front edge of the corner post to the nailing tab. Once the nailing tab is in the desired
location, secure with a sheet metal screw*.
* Additional screws may be installed.
NAILING
TABS