33
W415-1540 / 08.04.15
EN
Combustible Mantel clearance can vary according to the mantel depth. Use the graph to
help evaluate the clearance needed.
!
WARNING
RISK OF FIRE, MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES. FAILURE
TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO
OVERHEAT. ENSURE ALL CLEARANCES (I.E. BACK, SIDE, TOP, VENT, MANTEL, FRONT, ETC.) ARE
CLEARLY MAINTAINED.
WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL, THE PAINT OR LACQUER MUST BE
HEAT RESISTANT TO PREVENT DISCOLOURATION.
73.1
5.4 MINIMUM COMBUSTIBLE MANTEL CLEARANCES
0
3 4
7
14
16
1 2
5 6
12
+
(
,
*
+
7
0
$
1
7
(
/
MANTEL DEPTH
8
10
6
4
18
20
8
10
9
22
24
26
E
D
C
B
A
TOP OF
OPENING
MANTEL DIMENSIONS
Ref
Height
Depth
A
33 1/8" (841mm)
B
12" (305mm)
2" (51mm)
C
14" (356mm)
4" (102mm)
D
16" (406mm)
6" (152mm)
E
18" (457mm)
8" (203mm)
5.5 NAILING TAB INSTALLATION
55.2
A.
To determine the
fi
nal location and where to bend the nailing tabs you must
fi
rst determine the thickness of your
fi
nishing material (i.e. drywall). This will
determine the dimension from the front edge of the corner post to the nailing
tab. Once the desired tab has been choosen, bend and secure to the framing.
NAILING
TABS