SYMPTOM

PROBLEM

TEST SOLUTION

Carbon is being 
deposited on 
glass, logs, 
rocks, media 
or combustion 
chamber surfaces.

Air shutter has become 
blocked.

 

-

Ensure air shutter opening is free of lint or other 
obstructions.

Flame is impinging on the 
glass, logs, rocks, media 
or combustion chamber.

 

-

Check that the glass, logs, rocks or media are 
correctly positioned. 

 

-

Open air shutter to increase the primary air.

 

-

Check the input rate: check the manifold pressure 
and orifi ce size as specifi ed in the instructions.

 

-

Check that the door gasketing is not broken or 
missing and that the seal is tight.

Continues to 
spark and pilot 
lights, but main 
burner will not
light.

Short or loose
connection in sensor rod.

 

-

Verify all connections. Verify the connections 
from the pilot assembly are tight; also verify these 
connections are not grounding out to any metal.

Poor fl ame rectifi cation
or contaminated
sensor rod.

 

-

Verify the fl ame is engulfi ng the sensor rod. This 
will increase the fl ame rectifi cation. Verify correct 
pilot orifi ce is installed and inlet gas specifi cations 
to manual. (Remember, the fl ame carries the 
rectifi cation current, not the gas. If the fl ame lifts 
from pilot hood, the circuit is broken. A wrong orifi ce 
or too high of an inlet gas pressure can cause 
the pilot fl ame to lift.) The sensor rod may need 
cleaning.

Poor grounding between
pilot assembly and
gas valve.

 

-

Verify that the wire harness is fi rmly connected to 
module Verify that the ceramic insulator around the 
sensor rod is not cracked, damaged, or loose. Verify 
the connection from the sensor rod to the sensor wire.

Damaged pilot or dirty
sensor rod.

 

-

Clean sensor rod with an emery cloth to remove 
any contamination that may have accumulated on 
the sensor rod. Verify continuity with multimeter with 
ohms set at the lowest range.

Pilot lights 
Stops sparking
/ pilot remains lit
but burner will
not turn on.

Wiring / Connection.

 

-

Inspect all wires, ensure good tight connections. 
Verify that all wiring is installed exactly as specifi ed.

Wiring harness.

 

-

Inspect the wiring harness, and verify the harness 
is tightly connected to the module. Verify that all 
wires are connected in the right order. See “WIRING 
DIAGRAM” section.

White / grey fi lm 
forms.

Sulphur from fuel is being 
deposited on glass, logs or 
combustion chamber
surfaces.

 

-

Clean the glass, see “CARE OF GLASS” section

DO NOT CLEAN GLASS WHEN HOT.

 

-

If deposits are not cleaned off regularly, the glass 
may become permanently marked.

Noisy Burner

Media Placement.

 

-

In some installations, the glass media can lead to 
a “puffi ng” sound. Simply remove media covering 
burner ports.

42.20_2

Содержание CWHVF31N

Страница 1: ...ilding Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must b...

Страница 2: ...7 MINIMUM CLEARANCE TO COMBUSTIBLES 12 4 0 FINISHING 13 4 1 HOUSING PANEL INSTALLATION 13 4 2 DOOR REMOVAL INSTALLATION 14 4 3 BRICK PANEL INSTALLATION 14 4 4 GLASS MEDIA 15 4 5 SURROUND INSTALLATION...

Страница 3: ...e Wall Mantel see MINIMUM CLEARANCES TO COMBUSTIBLES section Side Wall see MINIMUM CLEARANCES TO COMBUSTIBLES section Rating plate see RATING PLATE INFORMATION section Surround see FINISHING section 1...

Страница 4: ...protect children from hot surfaces These screens and guards must be fastened to the floor Any safety screen or guard removed for servicing must be replaced prior to operating the appliance It is impe...

Страница 5: ...AS INDICATED ON THE RATING PLATE THIS APPLIANCE IS NOT CONVERTIBLE FOR USE WITH OTHER GASES OBJECTS PLACED IN FRONT OF THE HEATER SHOULD BE KEPT A MINIMUM OF 48 AWAY FROM THE FRONT FACE OF THE APPLIAN...

Страница 6: ...m at test pressures in excess of 1 2 psig 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas...

Страница 7: ...les which are designed to filter out harmful gases and limit carbon monoxide output It is likely that with the appliance in operation the catalytic tiles will actually scrub the carbone monoxide norma...

Страница 8: ...IN SUPPLY PRESSURE 4 5 WATER COLUMN NG MAX SUPPLY PRESSURE 7 WATER COLUMN NG MANIFOLD PRESSURE 10 WATER COLUMN LP MIN SUPPLY PRESSURE 11 WATER COLUMN LP MAX SUPPLY PRESSURE 13 WATER COLUMN LP NOT FOR...

Страница 9: ...t vent gas appliances which draw their input and output air from and to the outdoors Unusually tight construction is defined as construction where A Walls and ceilings exposed to the outside atmospher...

Страница 10: ...lume of Room 1 10x10x8 800 cubic feet The volume of Room 2 10x15x8 1200 cubic feet 19 2 EXAMPLE 1 In this example because there is no door to the adjoining room the volume of the adjoining room may be...

Страница 11: ...line up to the wooden wall studs If this is not possible mark the template where the studs are located and transfer these locations to the mounting plate C Remove the paper template from the wall and...

Страница 12: ...Canada or to the current National Fuel Gas Code ANSI Z223 1 NFPA 54 in the United States D When flexing any gas line support the gas valve so that the lines are not bent or kinked E The gas line flex...

Страница 13: ...ARANCES TO COMBUSTIBLES 20 to top 7 to sides 0 to bottom of trim 0 to rear TYPICAL INSTALLATION ALCOVE INSTALLATION SIDE VIEW The front trims for the WHVF31 are different sizes See DIMENSIONS section...

Страница 14: ...M OR SCRATCH GLASS DO NOT OPERATE APPLIANCE WITH GLASS REMOVED CRACKED BROKEN OR SCRATCHED 72 4 4 1 HOUSING PANEL INSTALLATION Secure the housing panels as illustrated using the 17 8 X 3 8 screws supp...

Страница 15: ...OOL TO THE TOUCH DOORS ARE HEAVY AND FRAGILE SO HANDLE WITH CARE 75 1 A Remove the surround see SURROUND INSTALLATION REMOVAL section B Remove the 3 screws that secure the door C Lift the door up and...

Страница 16: ...nstallation Clean the glass with mild dish soap drain rinse thoroughly and dry before placing over the burner CLEAN THE GLASS MEDIA PRIOR TO INSTALLATION BEFORE APPLYING THE CLEANED GLASS ENSURE THAT...

Страница 17: ...frame and secure by using 3 screws to attach the safety screen and door retainer brackets 5 2 REMOTE RECEIVER LOCATION WIRING If installing an optional remote control the receiver must be located as...

Страница 18: ...battery back up If this backup is used install four AA batteries not supplied into the holder and connect to the wire harness Place near the IPI board Connect the battery holder to the wire harness b...

Страница 19: ...PHONE IN YOUR BUILDING IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOUR S PHONE FOLLOW THE GAS SUPPLIER S INSTRUCTIONS IF YOU CANNOT REACH YOUR GAS SUPPLIER CALL THE FIRE DEPARTMENT C DO NOT TRY T...

Страница 20: ...the burner ports The flame may not appear yellow immediately allow 15 to 30 minutes for the final flame colour to be established AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED INSTALLER AIR...

Страница 21: ...ple thermopile as well as reaches the burner 5 Replace the cleaned logs rocks or glass Failure to properly position the media may cause carboning which can be distributed in the surrounding living are...

Страница 22: ...KEN DOOR GLASS OR DAMAGED COMPONENTS BE SURE TO VACUUM UP ANY BROKEN GLASS FROM INSIDE THE APPLIANCE BEFORE OPERATION DO NOT STRIKE SLAM OR SCRATCH GLASS DO NOT OPERATE APPLIANCE WITH GLASS REMOVED CR...

Страница 23: ...R 41 1 FAILURE TO POSITION THE PARTS IN ACCORDANCE WITH THIS MANUAL OR FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED WITH THIS APPLIANCE MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY WARNING COMP...

Страница 24: ...ONVEX SURROUND BLACK 19 S31CVSS CONVEX SURROUND STAINLESS STEEL 20 LK31 LED LIGHT KIT 21 W660 0081 THERMOSTAT WALL MOUNT DIGITAL 22 F40 ON OFF REMOTE 23 F50 THERMOSTATIC REMOTE 24 F50DR THERMOSTATIC R...

Страница 25: ...into the module Check voltage of the transformer under load at the spade connections on the module with the ON OFF switch in the ON position Acceptable readings of a good transformer are between 6 2 a...

Страница 26: ...s broken A wrong orifice or too high of an inlet gas pressure can cause the pilot flame to lift The sensor rod may need cleaning Poor grounding between pilot assembly and gas valve Verify that the wir...

Страница 27: ...caused by environmental conditions such as rooftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pres...

Страница 28: ...28 W415 1115 06 13 12...

Отзывы: