TD040900-0IJ 

6

 

-TB5    Twisted-pair Bus 

The -TB5 transceiver accommodates twisted-pair cabling via a pair of 
RJ-45 jacks which allow the unit to be daisy-chained at any location on 
the bus segment.  Usually IBM type 3 unshielded twisted-pair cable 
(UTP) is used, but shielded cable (STP) can also be used to provide 
continuous shielding between devices. 

When the USB22-TB5 is located at the end of a bus segment, apply the 
provided 100-ohm terminator to the empty RJ-45 jack to match the 
cable impedance. 

-485    DC-Coupled EIA-485 

Two models support DC-coupled EIA-485 segments.  The USB22-485 
provides dual RJ-45 jacks and the USB22-485/S3 offers a 3-pin screw 
terminal.  Each segment can be up to 900 feet of IBM type 3 (or better) 
STP or UTP cable while supporting up to 17 nodes.  Make sure the phase 
integrity of the wiring remains consistent throughout the network.  All 
phase A signals on NIMs and hubs must connect together.  The same 
applies to phase B.  Refer to 

Figures 1

 and 

2

 for connector wiring. 

Termination 

If the NIM is located at the end of a segment, apply 100 ohms of 
termination.  For the USB22-485, insert a terminator in its empty RJ-45 
jack.  For the USB22-485/S3, attach a resistor to its 3-pin connector. 

Bias 

Bias must also be applied to the network to prevent the differential 
receivers from assuming invalid logic states when the signal line is 
floated.  Bias is provided on the USB22-485 by a set of 806-ohm pull-up 
and pull-down resistors. 

Ground 

All devices on the segment should be referenced to the same ground 
potential to achieve the common mode voltage (+/–7 Vdc) required  for 
the EIA-485 specification.  A ground connection is not provided by the 
NIM.  It is assumed adequate grounding is supplied by the existing 
equipment.  Refer to the existing equipment user manual for a discussion 
of grounding requirements. 

Содержание USB22 Series

Страница 1: ...SB 1 1 devices The NIM is powered from a computer USB port or a USB hub Models exist for the most popular ARCNET physical layers A USB cable is also provided NOTE The USB22 Series of NIMs are for user...

Страница 2: ...se without the prior written permission of Contemporary Control Systems Inc 2431 Curtiss Street Downers Grove Illinois 60515 USA Tel 1 630 963 7070 Fax 1 630 963 0109 E mail info ccontrols com Web www...

Страница 3: ...temperature 0 C to 60 C Storage temperature 40 C to 85 C Humidity 10 to 95 non condensing ARCNET Data Rates Shipping Weight 1 lb 45 kg Compatibility ANSI ATA 878 1 USB 1 1 and USB 2 0 Regulatory Comp...

Страница 4: ...Y All USB22 models comply with Class A radiated and conducted emissions as defined by EN55022 and CFR 47 Part 15 This equipment is intended for use in non residential areas Warning This is a Class A p...

Страница 5: ...ed by the suffix 4000 485 CXB or TB5 separated from the main number by a hyphen CXB Coaxial Bus Generally two types of coaxial cables are used with ARCNET RG 62 u and RG 59 u RG 62 u is recommended be...

Страница 6: ...ring remains consistent throughout the network All phase A signals on NIMs and hubs must connect together The same applies to phase B Refer to Figures 1 and 2 for connector wiring Termination If the N...

Страница 7: ...AC coupled transceivers operate only at 1 25 2 5 5 0 and 10 Mbps whereas DC coupled transceivers function over all standard data rates Two models support AC coupled EIA 485 segments The USB22 4000 pr...

Страница 8: ...over repair of products that have been damaged by abuse accident disaster misuse or incorrect installation User modification may void the warranty if the product is damaged by the modification in whic...

Отзывы: