UM-15093500-AA1
Page
32
Minimum Cooling
Setpoint
AV 39
R/W
Minimum Cooling Setpoint
°C:0~500 (0.0
~
50.0
℃
)
°F: 320~1220
(32.0~122.0°F
)
Maximum Heating
Setpoint
AV 40
R/W
Maximum Heating Setpoint
°C:0~500 (0.0
~
50.0
℃
)
°F: 320~1220
(32.0~122.0°F)
Minimum Fan
Output
AV 41
R/W
Minimum Fan Output at Auto
Fan Mode (for Modulating
Fan Application)
0%~Reg 51
Maximum Fan
Output
AV 42
R/W
Maximum Fan Output at
Auto Fan Mode (for
Modulating Fan Application)
Reg 50~100%
Low Fan Speed
Setting
AV 43
R/W
Low Fan Speed Setting (for
Modulating Fan Application)
0%~Reg 53
Med. Fan Speed
Setting
AV 44
R/W
Med. Fan Speed Setting (for
Modulating Fan
Application)
Reg 52~Reg54
Hi Fan Speed
Setting
AV 45
R/W
Hi Fan Speed Setting (For
Modulating Fan Application)
Reg 53~100%
Minimum Off
Time
AV 46
R/W
Minimum Off Time
0~600 seconds
Minimum On Time
AV 47
R/W
Minimum On Time
0~600 seconds
Integral-Cycle
Time 2
AV 48
R/W
Integral Time and Output
Cycle Time 2
0~500 (Sec.)
Set Point for
Humidity
AV 49
R/W
Set Point for Humidity
Control
0~1000 (0.0
~
100.0%RH)
Dew Point Set
Point
AV 50
R/W
Dew Point Temperature
Set Point
-999~9999: -99.9
~
999.9
℃
/°F
Occupancy Status
BI 0
R
Status of Occupancy
0: Room Occupied
1: Room Unoccupied
Window-Door Status
BI 1
R
Window/ Door Status
0: Door/Window Closed
1: Door/Window Open
Cooling-heating
Status
BI 2
R
Status of Cooling/Heating
Control
Output
0: Close & Off 1: Open & On
Relay 1 Status
BI 3
R
Status of Relay 1
0: Off, 1: On
Relay 2 Status
BI 4
R
Status of Relay 2
0: Off, 1: On
Relay 3 Status
BI 5
R
Status of Relay 3
0: Off, 1: On
Relay 4 Status
BI 6
R
Status of Relay 4
0: Off, 1: On
Relay 5 Status
BI 7
R
Status of Relay 5
0: Off, 1: On
Relay 6 Status
BI 8
R
Status of Relay 6
0: Off, 1: On