The external horn 

provides an acoustic signal in other premises away from the monitored space. The 

external  horn  is  activated  together  with  the  extinguishing  command.  It  can  be  disconnected  by  the 
“MUTE ”button on the LES-RACK-M1 front panel. 
The horn supply is 12V DC, maximum current 150 mA 

 

 The manual activation button

  activates  extinguishing from other places than the  monitored space. 

The integrity of manual activation button is continuously monitored. 
The connection diagram for the door contact is in Fig. No.:6 

 

 

The resistance values in the diagram are as follows: 
Rp: 1K8 Ohm, 0.1 W 
Rs: 470 Ohm, 0.1 W

 

 

 
 

 
 
 

 

External  sensors. 

The  extinguishing  process  can  be  remotely  activated  by  signals  for  the  other 

detectors or other extinguishing equipment. The inputs marked with the text “Sensor 1 ”to “Sensor 3 ”

are for this. 
The  sensitivity  of  the  external  sensors  circuits  is  also 
continuously monitored. 
The  connection  diagram  for  the  external  sensors  is  in  Fig. 
No.:7 

 

 

The resistance values in the diagram are as follows: 

Rp: 1K8 Ohm, 0.1 W 

      Rs: 470 Ohm, 0.1 W

 

 
 

 
 

 

External temperature sensor 

- installed in the space where the temperature must be monitored. The 

temperature sensor checks the temperature in the monitored space. If the default temperature limits 
are exceeded, the user selected relay is activated. 

 
 

Signalling 

Local  signalling  is  by  multi-coloured  LED  diodes  under  the  labels  of  the  function  description  of  the 
respective device or the system state. Individual statuses are described in Table No. 5. 
 
The meaning of the letters in the “colour ”column are as follows: 

red  

green 

yellow 

blue 

orange 

Fig. No. 6 

Fig. No. 

Содержание LES-RACK-M1

Страница 1: ...dures for assembling commissioning operating and maintenance of the LES RACK M1 fire extinguisher The equipment must only be used for the described applications with the approved extinguishing agent F...

Страница 2: ...19 Temperatures 20 Mail 21 Outputs 21 Date and time 22 Logs 22 Download 22 INSTALLATION 23 General provisions 23 Safety provisions 23 Assembling the equipment 23 Filling adding extinguishing liquid 23...

Страница 3: ...g to the operating conditions and the maintenance plan In necessary the maintenance and service must be documented Device operators of must announce all changes and modifications of the monitored and...

Страница 4: ...n in Fig 1 The fire fighting equipment consists of Tank with extinguishing agent 1 consisting of non pressure stainless storage vessel 1 filled with the extinguishing agent FK 5 1 12 dodekafluor 2 met...

Страница 5: ......

Страница 6: ...he energy requirements of the system during extinguishing AC inlet 13 for connecting the DC source 14 to 230V AC distribution network Control board 16 the heart of the system It concentrates and evalu...

Страница 7: ...ress the micro switch to the left of the communication connector The internal relay is activated a click is heard and connects the battery to the system BATTERY G S De aerating the pump after adding f...

Страница 8: ...at the same time by switching the micro switch in the left lower part of the box which is accessible from the bottom after partially ejecting the box about 5 cm from the 19 frame BATTERY R S50 Extingu...

Страница 9: ...with the cap connect the external equipment on the rear face and insert the equipment back into the frame Secure The system error signal goes off FAULT SYSTEM Press TEST MUTE the pump is activated th...

Страница 10: ...would escape outside the monitored space and its concentration for effectively extinguishing a fire would be insufficient The integrity of the circuit of the door contact is continuously monitored Th...

Страница 11: ...ectors or other extinguishing equipment The inputs marked with the text Sensor 1 to Sensor 3 are for this The sensitivity of the external sensors circuits is also continuously monitored The connection...

Страница 12: ...the network EXTINGUISHING R S50 3 seconds delay before extinguishing activated R S Extinguishing in progress or terminated Y S Extinguishing blocked door open FAULT SENSOR R S Fault sensor PUMP G S Th...

Страница 13: ...operators by the extinguishing agent as well as decomposition products mainly by regular training The start of the fire extinguisher may be accompanied by a loud noise that could cause fright but not...

Страница 14: ...isplayed To repeat the login close the browser and run it again it is its property and it is not possible to do otherwise NOTE Transferred login data is not encrypted ATTENTION The display may not be...

Страница 15: ...state is displayed when MAJOR system error MINOR is in yellow The battery is disconnected from the system but it is present The fan is not rotating The level is low Here the state is displayed when Th...

Страница 16: ...Network...

Страница 17: ...IP address exchange address Gate must be typed even if it is not used Primary and secondary DNS if mail is used SNMP trap1 2 IP SNMP address of the server...

Страница 18: ...ed Group extinguish group for common extinguishing If the exchanges have the same group with the exception of 0 if extinguishing is activated on any of them extinguishing on the others is activated Us...

Страница 19: ...or failure sends the trap Mail change of the state or error sends e mail Error Major error is assigned to Major Error Minor error is assigned to Minor State Major the state is assigned to Mirror Stat...

Страница 20: ...he line and press the Read sensor button and press the Save button Then select the temperature type the line disconnect the first sensor and connect the second sensor read serial number and save Repea...

Страница 21: ...User Password SMTP server requires login To addressee of the mail From sender of the mail must be typed Subject Subject of the message Outputs Relay_ window used to change the name of the output The n...

Страница 22: ...Date and time Logs Lists events from the newest to the oldest Download MIB opens the MIB file window LOG opens events window...

Страница 23: ...the box From the front the skid has 3 holes with M5 threads with the same pitch as the 1U drilling in the 19 bar Fix the bar to the rear wall of the front 19 bar using the conical headed M5 bolt The r...

Страница 24: ...network and operated connect the battery It must be connected for at least 12 hours to charge the backup source battery After charging the equipment must be disconnected and then it is possible to pu...

Страница 25: ...are properly located and undamaged Inspection of signal lamps on the front panel Inspection after 1 month Checking that all staff who could work with equipment are properly trained and have appropriat...

Отзывы: