Installation Environment Requirements
Item
CPS-MCS341-DS1-111
CPS-MCS341-DS1-131
Operating ambient temperature -20 - +60°C *4
Operating ambient humidity
10 - 90%RH (No condensation)
Non-operating ambient
temperature
-20 - +60°C
Non-operating ambient humidity 10 - 90%RH (No condensation)
Floating dust particles
Not to be excessive
Corrosive gases
None
Line-noise
resistance
Line noise
AC Line/±2kV *5
Signal Line /±1kV (IEC61000-4-4 Level 3, EN61000-4-4 Level 3)
Static
electricity
resistance
Touch /±4kV (IEC61000-4-2 Level 2, EN61000-4-2 Level 2)
Air /±8kV (IEC61000-4-2 Level 3, EN61000-4-2 Level 3)
Vibration
resistance
Sweep
resistance
10 - 57Hz *6 /semi-amplitude vibration 0.15mm, 57 - 150Hz/2.0G
40minutes each in X, Y, and Z directions (JIS C60068-2-6-compliant,
IEC60068-2-6-compliant)
Shock resistance
15G half-sine shock for 11ms in X, Y, and Z directions
(JIS C 60068-2-27 -compliant, IEC 60068-2-27 -compliant)
Grounding
Class D grounding (previous class 3 grounding), SG-FG/ non-conduction
Standard
VCCI Class A, FCC Class A,
CE Marking (EMC Directive Class A, RoHS Directive), UL
*4 If you use the USB with bus power, operate the product at between -20 and +55°C.
*5 When you use an optional power product
*6 When you use an optional power product: 10-55Hz (See the manual of optional power product
for details)
CAUTION
You can set the modules as you desire to the configurable controller up to 16 modules.
The total current consumption of the modules should be less than 3.3A.
ATTENTION
Le nombre maximum de modules empilés en fonctionnement avec le contrôleur de type empilable