Contec AIO-160802LI-PE Скачать руководство пользователя страница 4

 

Ver.1.05 

  AIO-160802LI-PE   

  4   

The following figure shows an example of shield cable connection. Use 
shielded cable if the distance between the signal source and board is 
long or if you want to provide better protection from noise.   For each 
analog input channel on CN1, connect the core wire to the signal line 
and connect the shielding to ground. 

Analog Output Connection (Shield Cable) 

 

*2  The number of channels depends on each board.  The AIO-160802LI-PE has two channels. 

 

 

CAUTION 

When the power supply is turned on, the output voltage of all channels becomes 0V. 

If the board or the connected wire receives noise, or the distance between the board and the 
target is long, data may not be outputted properly. 

Do not short the analog output signal to analog ground, digital ground, and/or power line.  
Doing so may damage the board. 

Do not connect an analog output signal to any other analog output, either on the board or on 
an external device, as this may cause a fault on the board. 

Analog ground of CN1 is isolated from the ground in the PC. 

 

 

 

Digital I/O signals, Counter signals and Control 
signals Connection 

 

The following sections show examples of how to connect digital I/O 
signals, counter I/O signals, and other control I/O signals (external 
trigger input signals, sampling clock input signals, etc.). 
All the digital I/O signals and control signals are TTL level signals. 

Digital Input Connection 

 

Digital Output Connection 

 

About the counter input control signal 
Counter Gate Control Input (refer to the chapter 3 Connector Pin 
Assignment) acts as an input that validate or invalidate the input of an 
external clock for the counter.   This function enables the control of an 
external clock input for the counter.   The external clock for the counter 
is effective when input is "High", and invalid when input is "Low".   If 
unconnected, it is a pull-up in the board (card) and remains "High". 
Therefore the external clock for the counter is effective when the 
counter gate control input is not connected. 

 

CAUTION 

Do not short the output signals to analog ground, digital ground, and/or power line.  Doing so 
may damage the board. 

Do not connect a digital output signal to any other digital output, either on the board or on an 
external device, as this may cause a fault on the board. 

Analog ground of CN1 is isolated from the ground in the PC. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Block Diagram 

 

 

 

 

Difference from ADAI16-8/2(LPCI)L 

 

The functions same with conventional product of ADAI16-8/2(LPCI)L 
are provided with the AIO-160802LI-PE.  In addition, as there is 
compatibility in terms of connector shape and pin assignments, it is 
easy to migrate from the existing system.  So you can use the same 
operating procedures as ADAI16-8/2(LPCI)L. 

There are some differences in specifications as shown below. 

 

AIO-160802LI-PE 

ADAI16-8/2(LPCI)L 

Power 
consumption 

+3.3VDC 1100mA (Max.) 

+5VDC 680mA (Max.) 

Bus specification 

PCI Express Base  
Specification Rev. 1.0a x1 

PCI (32-bit, 33MHz,  
Universal key shapes supported) 

Dimension (mm)  169.33(L) x 110.18(H) 

121.69(L) x 63.41(H) 

Weight 

120g 

65g 

 

 

Analog Ground

Shield cable

Analog Output 0..3*2

BOARD

CN1

Target

Digital Input

Digital Ground

BOARD

CN1

Cable

Target

10k

Digital Ground

BOARD

CN1

Cable

Target

Digital Output

I

OL

=16mA

8 Single-end

Analog Inputs

4 Digital Inputs / 4 Digital Outputs

External Trigger Inputs

Counter Input / Output

PCI Express bus

CN1

2 Analog Outputs

DC/DC

converter

FPGA

Multiplexer

OP

Amplifer

A/D

Converter

OP

Amplifer

OP

Amplifer

DA

Converter

DA

Converter

Isolator

Buffer

 