![Connecticut Electric EmerGen Switch 10-7501G2 Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/connecticut-electric/emergen-switch-10-7501g2/emergen-switch-10-7501g2_owners-manual-and-installation-instructions_2652970009.webp)
COMPLETING THE INSTALLATION
1) When the preceding steps have been completed for all desired circuits, the
EmerGen Switch white (neutral) wire needs to be installed.
a.
Select any unused hole on the neutral bar in the load center.
b.
Cut and strip the wire appropriately. Insert the wire into the hole
in the neutral bar and tighten securely.
2) The EmerGen Switch green (ground) wire needs to be installed into an unused
hole in the ground bar in the load center.
a.
Select an unused hole in the ground bar in the load center.
b.
Cut and strip the wire appropriately. Insert the wire into the hole in
the ground bar and tighten securely.
NOTE: If no separate Ground Bar exists, connect the green wire to an unused
position in the Neutral bar.
3) Replace the load center cover. All circuit breakers can now be turned on
including the MAIN circuit breaker.
4) All EGS switches should be in the “Line” position. The “Off” position is
generally not used.
5) Fill out the chart supplied with your EmerGen Switch describing each
emergency circuit and corresponding circuit breaker. Place this label on or
near your EmerGen Switch for easy reference.
EGS
Circuit No.
Circuit
Circuit
at Load Center
Description
A
8A
Freezer
B
5B
Rec Room Lights
C
2A
Barn Pump
D
3A
E
4B
Lights
F
10B
Furnace Fan
EmerGen Switch
9