Operation / Test Procedure 

1.  Switch positions should remain in the “LINE” position under normal utility 

power. The “OFF” position is generally not used. The “GEN” positions are used 

when connecting circuits to your generator power source. 

2.  When testing and/or switching to generator power after a power outage, 

ensure all switches are in the “LINE” position. (There is no need to turn off 

any load center circuit breakers). 

3.  Plug your power cord set into your generator by aligning the male prongs with 

the female terminals of your generator’s receptacle, push the connector in 

and twist clockwise to lock (some connectors do not twist). Align the female 

socket of the cord set into your EmerGen Switch, push it in and turn 

clockwise to lock. 

4.  Move your generator outdoors before starting it up. Check to see that fluids 

and fuel are adequate and start your generator according to the 

manufacturer’s instructions. 

5.  At your EmerGen Switch, move one circuit to the “GEN” position, making a 

note of how much wattage is used on the watt meter. While monitoring the 

load, flip each circuit—one at a time—to the “GEN” position. You do not need 

to go “in order” and you want to balance the loads so that both meters read 

approximately the same. Do not switch on more loads than your generator 

can supply. 

Note: Wattage must not exceed the maximum printed on the meters. 

Load Management 

1.  All circuits can be used simultaneously only if your generator has sufficient 

wattage capacity. If an electrical load on the EmerGen Switch is exceeded by 

it’s capacity, the mini-breaker may trip.  

 To 

Reset: 

 

a. 

Eliminate the overload condition. 

 

b. 

Move the switch with the tripped breaker to the “OFF” position. 

 

c. 

Reset the breaker by pressing it in, making sure it stays in. 

 

d. 

Move the switch back to the “GEN” position. It should now operate 

 

 

properly. If it does not, you may need to contact an electrician or 

  qualified 

professional. 

Содержание EmerGen L14-20R

Страница 1: ...en Switch is easy for a licensed electrician or qualified professional to install safe for a homeowner to operate and will work with 120 240V single phase AC generators factory equipped with NEMA type receptacles L14 20R Your EmerGen Switch will not permit connection to both utility and generator power at the same time Wiring to the Load Center Page 4 Installing 240 volt 2 pole Circuits Page 5 Com...

Страница 2: ...plug the power cord set into your generator and into the EmerGen Switch before starting the generator and always shut the generator down before detaching the power cord set 3 Do not overload your generator or its circuit breakers will trip Using the EmerGen Switch s built in watt meters you can balance the loads to avoid impeding your generator s performance INSTALLATION PREPARATION 1 Decide which...

Страница 3: ...is does not affect the wires on the line side of the main breaker they will remain live Remove the cover of the load center 3 Identify 3 4 knockout to remove 4 Insert the wires from the flex conduit up through the knockout take care not to nick or gouge the wires on the metal edge Tighten the locknut securely onto the load center The wires can hang freely 5 Without over manipulating the flex condu...

Страница 4: ...he red and black EmerGen Switch wires labeled A Using good workmanship route both of these wires close to the selected circuit breaker a The red EmerGen Switch A wire is trimmed stripped and installed into the circuit breaker securely tightening the breaker lug b The black EmerGen Switch A wire and the hot wire from the circuit breaker removed in step 1 are placed up the side of the load center to...

Страница 5: ...de of the 2 pole circuit breaker b The black EmerGen Switch C wire and one of the hot wires from the circuit breaker are placed up the side of the load center Insert both wires into a yellow wire connector and twist tightly Push the wires back into the wiring compartment of the load center c The red EmerGen Switch D wire is trimmed stripped and securely installed into the remaining side of the 2 p...

Страница 6: ... ground bar in the load center b Cut and strip the wire appropriately Insert the wire into the hole and tighten securely 3 Replace the load center cover All circuit breakers can now be turned on including the MAIN circuit breaker 4 All EmerGen switches should be in the Line position The Off position is generally not used 5 Fill out the chart supplied with your EmerGen Switch describing each emerge...

Страница 7: ...rt your generator according to the manufacturer s instructions 5 At your EmerGen Switch move one circuit to the GEN position making a note of how much wattage is used on the watt meter While monitoring the load flip each circuit one at a time to the GEN position You do not need to go in order and you want to balance the loads so that both meters read approximately the same Do not switch on more lo...

Страница 8: ...are in OFF or LINE position 1 Move switches to GEN position 2 Generator circuit breaker has tripped 2 Reset circuit breaker 3 Poor connection or defective cord set 3 Check and repair 4 Connected device is bad 4 Select a different load or appliance that is in good condition 5 Fault in generator 5 Contact a qualified professional Appliances do not operate after utility power is restored 1 Switches a...

Отзывы: