Installing 240 Volt (2 pole) Circuits

EmerGen Switch products provide circuits for the connection of 240 volt
appliances that are connected to 2 pole branch circuit breakers in your load 
center. These EmerGen Switch circuits for 240 volt operation have a handle tie 
included with the switch that ties two circuit selector switches C & D together.
If you do not wish to use the designated circuits as 2 pole circuits, simply 
remove the handle tie by removing the two screws.  

a)  The red EmerGen Switch “C” wire is trimmed, stripped and securely installed 

into one side of the 2 pole circuit breaker. 

b)  The black EmerGen Switch “C” wire and one of the hot wires from the circuit 

breaker are placed up the side of the load center. Insert both wires into a 

yellow wire connector and twist tightly. Push the wires back into the wiring 

compartment of the load center. 

c)  The red EmerGen Switch “D” wire is trimmed, stripped and securely installed 

into the remaining side of the 2 pole circuit breaker. 

d)  The black EmerGen Switch “D” wire and the remaining hot wire from the 

circuit breaker are placed up the side of the load center. Insert both wires 

into a yellow wire connector and twist tightly. Push the wires back into the 

wiring compartment of the load center. 

Note: For this example, a 125 amp panel is used for illustration purpose only 

Содержание EmerGen L14-20R

Страница 1: ...en Switch is easy for a licensed electrician or qualified professional to install safe for a homeowner to operate and will work with 120 240V single phase AC generators factory equipped with NEMA type receptacles L14 20R Your EmerGen Switch will not permit connection to both utility and generator power at the same time Wiring to the Load Center Page 4 Installing 240 volt 2 pole Circuits Page 5 Com...

Страница 2: ...plug the power cord set into your generator and into the EmerGen Switch before starting the generator and always shut the generator down before detaching the power cord set 3 Do not overload your generator or its circuit breakers will trip Using the EmerGen Switch s built in watt meters you can balance the loads to avoid impeding your generator s performance INSTALLATION PREPARATION 1 Decide which...

Страница 3: ...is does not affect the wires on the line side of the main breaker they will remain live Remove the cover of the load center 3 Identify 3 4 knockout to remove 4 Insert the wires from the flex conduit up through the knockout take care not to nick or gouge the wires on the metal edge Tighten the locknut securely onto the load center The wires can hang freely 5 Without over manipulating the flex condu...

Страница 4: ...he red and black EmerGen Switch wires labeled A Using good workmanship route both of these wires close to the selected circuit breaker a The red EmerGen Switch A wire is trimmed stripped and installed into the circuit breaker securely tightening the breaker lug b The black EmerGen Switch A wire and the hot wire from the circuit breaker removed in step 1 are placed up the side of the load center to...

Страница 5: ...de of the 2 pole circuit breaker b The black EmerGen Switch C wire and one of the hot wires from the circuit breaker are placed up the side of the load center Insert both wires into a yellow wire connector and twist tightly Push the wires back into the wiring compartment of the load center c The red EmerGen Switch D wire is trimmed stripped and securely installed into the remaining side of the 2 p...

Страница 6: ... ground bar in the load center b Cut and strip the wire appropriately Insert the wire into the hole and tighten securely 3 Replace the load center cover All circuit breakers can now be turned on including the MAIN circuit breaker 4 All EmerGen switches should be in the Line position The Off position is generally not used 5 Fill out the chart supplied with your EmerGen Switch describing each emerge...

Страница 7: ...rt your generator according to the manufacturer s instructions 5 At your EmerGen Switch move one circuit to the GEN position making a note of how much wattage is used on the watt meter While monitoring the load flip each circuit one at a time to the GEN position You do not need to go in order and you want to balance the loads so that both meters read approximately the same Do not switch on more lo...

Страница 8: ...are in OFF or LINE position 1 Move switches to GEN position 2 Generator circuit breaker has tripped 2 Reset circuit breaker 3 Poor connection or defective cord set 3 Check and repair 4 Connected device is bad 4 Select a different load or appliance that is in good condition 5 Fault in generator 5 Contact a qualified professional Appliances do not operate after utility power is restored 1 Switches a...

Отзывы: